6.7 Compensated Watts and VARs (Line and Transformer Loss Compensation)
The total Watt and Var losses can be calculated using five user entered parameters
and measured current and voltage values. These losses are added or subtracted
to/from the measured Total Watts and Total Vars when accumulating Energy.
Loss compensation on the M650 takes the following general form:
P
COM
=
P
UNC
+
A
·
I
2
+
B
·
V
2
+
E
·
P
UNC
Q
COM
=
Q
UNC
+
C
·
I
2
+
D
·
V
4
+
E
·
Q
UNC
Where:
P
COM
Compensated three-phase total watts. Note the accumulators for +kWh and –
kWh in the M650 are calculated by integrating the
P
COM
measurement over time.
P
UNC
Uncompensated three-phase total watts measured at the point where the meter
is connected.
Q
COM
Compensated three-phase total VARs. Note the accumulators for +kVARh and –
kVARh in the M650 are calculated by integrating the
Q
COM
measurement over
time.
Q
UNC
Uncompensated three-phase total VARs measured at the point where the meter
is connected.
I
RMS line current measured at the point where the meter is connected.
V
RMS
line-line
voltage measured at the point where the meter is connected.
A
Meter setting
that accounts for the sum of the full-load-watt-losses from all
sources.
B
Meter setting
that accounts for the transformer’s no-load-watt-losses.
C
Meter setting
that accounts for the sum of the full-load-VAR-losses from all
sources.
D
Meter setting
that accounts for the transformer’s no-load-VAR-losses.
E
Meter setting
that accounts for any “system” losses, proportional to the
uncompensated power.
Configuring the meter to perform loss compensation simply requires the user to
calculate the coefficients
A, B, C, D,
and
E
defined above, and enter them in the
appropriate fields in the M650’s webserver interface on the Settings/Input page as
shown in the screen shot below
The
sign
of the settings
A
,
B
, C,
D
, and
E
determines whether losses will be added to
or subtracted from the uncompensated measurements in order to determine the
compensated power and energy. To add losses, be sure the settings are all positive.
To subtract losses, be sure the settings are all negative. Settings should always have
the same sign.
Making all of the settings equal to zero
turns off
loss compensation.
System losses (
E
) are a fixed percentage, mutually agreed upon between two electric
utilities, about an interchange point that lies on a branched line. As such,
E
is not a
physical property of any particular line, transformer or the meter, so no further
Содержание Bitronics 50 Series
Страница 2: ...2 ML0035 September 22 2017 Copyright 2017 Bitronics LLC...
Страница 12: ......
Страница 52: ...52 ML0035 September 27 2017 Copyright 2017 Bitronics LLC Figure 7 Typical RS 485 Cable Wiring...
Страница 53: ...53 ML0035 September 27 2017 Copyright 2017 Bitronics LLC Figure 8 RS 232 Cable Wiring Diagram...
Страница 58: ...58 ML0035 September 27 2017 Copyright 2017 Bitronics LLC...
Страница 59: ...59 ML0035 September 27 2017 Copyright 2017 Bitronics LLC...
Страница 62: ...ML0035 September 27 2017 62 Copyright 2017 Bitronics LLC Data page Two views Instantaneous and Demands...
Страница 64: ...ML0035 September 27 2017 64 Copyright 2017 Bitronics LLC Contact Page...
Страница 66: ...ML0035 September 27 2017 66 Copyright 2017 Bitronics LLC Identity...
Страница 67: ...ML0035 September 27 2017 67 Copyright 2017 Bitronics LLC Input...
Страница 68: ...ML0035 September 27 2017 68 Copyright 2017 Bitronics LLC Network Serial Port if option ordered...
Страница 70: ...ML0035 September 27 2017 70 Copyright 2017 Bitronics LLC Modbus DNP3...
Страница 71: ...ML0035 September 27 2017 71 Copyright 2017 Bitronics LLC DNP Serial DNP TCP...
Страница 72: ...ML0035 September 27 2017 72 Copyright 2017 Bitronics LLC Modbus RTU...
Страница 73: ...ML0035 September 27 2017 73 Copyright 2017 Bitronics LLC Modbus TCP...
Страница 74: ...ML0035 September 27 2017 74 Copyright 2017 Bitronics LLC Screen Enable...
Страница 77: ...ML0035 September 27 2017 77 Copyright 2017 Bitronics LLC Password Security Settings Firmware Upload...
Страница 93: ...ML0035 September 27 2017 93 Copyright 2017 Bitronics LLC Figure 10 0 1mA Transducer Output Connections...
Страница 94: ...ML0035 September 27 2017 94 Copyright 2017 Bitronics LLC Figure 11 4 20mA Transducer Output Connections...
Страница 96: ...ML0035 September 27 2017 96 Copyright 2017 Bitronics LLC Figure 12 Signal Connections M650...
Страница 97: ...ML0035 September 27 2017 97 Copyright 2017 Bitronics LLC Figure 12 Signal Connections M650...
Страница 100: ...ML0035 September 27 2017 100 Copyright 2017 Bitronics LLC A3 Display Screens Visual Representations...
Страница 101: ...ML0035 September 27 2017 101 Copyright 2017 Bitronics LLC...
Страница 102: ...ML0035 September 27 2017 102 Copyright 2017 Bitronics LLC...
Страница 103: ...ML0035 September 27 2017 103 Copyright 2017 Bitronics LLC...
Страница 104: ...ML0035 September 27 2017 104 Copyright 2017 Bitronics LLC...
Страница 105: ...ML0035 September 27 2017 105 Copyright 2017 Bitronics LLC...
Страница 106: ...ML0035 September 27 2017 106 Copyright 2017 Bitronics LLC...
Страница 107: ...ML0035 September 27 2017 107 Copyright 2017 Bitronics LLC...
Страница 108: ...ML0035 September 27 2017 108 Copyright 2017 Bitronics LLC...
Страница 109: ...ML0035 September 27 2017 109 Copyright 2017 Bitronics LLC...
Страница 110: ...ML0035 September 27 2017 110 Copyright 2017 Bitronics LLC...
Страница 111: ...ML0035 September 27 2017 111 Copyright 2017 Bitronics LLC...
Страница 112: ...ML0035 September 27 2017 112 Copyright 2017 Bitronics LLC...
Страница 113: ...ML0035 September 27 2017 113 Copyright 2017 Bitronics LLC...
Страница 114: ...ML0035 September 27 2017 114 Copyright 2017 Bitronics LLC...
Страница 117: ...ML0035 September 27 2017 117 Copyright 2017 Bitronics LLC...
Страница 118: ...Bitronics LLC 261 Brodhead Road Bethlehem PA 18017 610 997 5100 Fax 610 997 5450 www novatechweb com bitronics...