Installation Instructions

®

Coaxial Surge Protectors

 

The outer conductor of the coaxial cable must be bonded to 

earth. This is best achieved by installing Novaris cable earth 

bonding kits. Recommended connection points for cable 

earth bonding kits are (Figure 6):

 

1. At the highest point of the vertical cable run to the tower

 

2. At the lowest point of the vertical cable run to the tower

 

3. At the entry point into the equipment hut to the cable entry 

 

panel or equipment earth bar

3.2 

 All outdoor installations should be made weatherproof using 

3.3

Optional mounting kits in Table 1.

butyl rubber, cold shrink, vinyl mastic tape or suitable 

equivalent material over all connections and the protector 

itself.

Figure 2b:  Connection of Novaris RF Coaxial Inline 

Table 1:  Coaxial optional mounting kits 

Protectors

4. After Installation

4.1 

The integrity of the installation should be veri

¿

ed by measuring 

the return loss and/or VSWR of the completed cable run.

 

Novaris RF coaxial surge protectors are extremely robust. 

Provided installation is performed correctly, Novaris 

coaxial cable protectors are virtually maintenance free. 

3HULRGLFLQVSHFWLRQRIFRQQHFWLRQVDQGZHDWKHUSURR¿QJLV

recommended.

 

A protector fault may be indicated by excessive VSWR 

/ return loss, low resistance between the inner and outer 

conductors or intermittent degradation of system operation.

Coax Protectors

Earth Bonding Kits

Equipment

Feeder

Figure 6:  Typical Installation

Optional Mounting Kits and Ordering Details

Bracket (Cx-M)

DIN Rail Clip (Cx-D)

Bracket with Sealing

(Cx-M1)

Equipment

Cable 

Entry 

Plate

Cable 

Gland

Earth Bonding Kit

Main Feeder

Flexible

Termination

Earth Connection

CN-MF

Protector

*CN connector type shown for illustration purposes