Installation Instructions

IMPORTANT:

 Please read these instructions carefully. Whilst straightforward, the installation of these devices is critical to their 

SHUIRUPDQFH,QVWDOODWLRQVKRXOGRQO\EHFDUULHGRXWE\DVXLWDEO\TXDOL¿HGSHUVRQLQDFFRUGDQFHZLWKDOOUHOHYDQWVWDQGDUGV

®

Coaxial Surge Protectors

1. Introduction

1.1

  These installation instructions apply to Novaris RF coaxial 

surge protectors with the following catalogue numbers:

 

Gas Tube Type

 

    Cat  No: 

Cx-yy-zz-f-o

 

 

 
 

x   Connection type.

 

y  Connector Gender, M=male, F=female.

 

z  Maximum continious operating voltage.

 

f  Maximum frequency, fc (GHz).

 

 

 

o  Options.

 

1.2

  Novaris Cx series gas discharge surge protectors are 

capable of passing RF signals to 3 GHz (limited by 

connector type.

 

1.3

  Novaris CN 6G series gas discharge surge protectors are 

capable of passing RF signals to 6GHz. They come with 

CN type connectors only and have power ratings up to 

125W maximum.

Figure 1:   RF Coaxial Cable Protectors Range

2. Before Installation

2.1 

For 

Gas Tube Type

:

 

Ensure that the maximum continious operating voltage 

of the Novaris RF coaxial protector is suitable for the RF 

power of the system:

 

Clamping voltage (V)

 

RF power (W)

               90 

0 - 25

              230 

  25 - 125

              350 

 125 - 300

              600 

 300 - 600

             1000 

 600 - 1000

 

 

 

2.2 

 For 

 

dimensions,  

 

refer to the individual product data sheets

 

 

 

 

 

 

  

 

 

 

3. Installation

3.1 

A Novaris RF coaxial surge protector should be installed at the 

termination points on 

each end

 of the cable run. 

 

The ideal installation comprises a bulkhead protector (e.g. 

CN-FF-90-3)  installed  at  the  cable  entry  panel, 

¿

gure  2a, 

if this is not possible, install a protector between the main 

feeder and 

ÀH[LEOH

 tail, alternatively at the equipment antenna 

receptacle, figure 2b.

Figure 2a:  Connection of Novaris RF Coaxial Bulkhead 

Protectors

 

CN-FF-zz-3-E

CN-FF-zz-6

CN-MF-zz-3

Equipment

Cable Tail

Cable Entry Plate

Earth Bonding Kit

Main Feeder

Termination

Earth Connection

CN-FF

Protector

*CN connector type shown for illustration purposes