The Lingo

®

Energy Infosystem is the next generation control processor that

functions as a system network manager and control monitor in Novar Controls
Corporation’s Advanced Building Control System.

Lingo monitors and logs the operations of the local control modules, manages
network communications, and provides expandable and integrated control of the
building’s equipment. Lingo’s processing power, compatibility, and multiple
network capabilities provide optimum control to cut energy costs, increase
comfort, and reduce equipment maintenance.

This document provides the installation procedures for mounting the Lingo
electronic assembly, connecting it to the telephone network, and checking the
installation.

Lingo Specifications

Agency Approvals

Listed device:

CUL/UL E90949

Standards used:

UL 916, Energy Management Equipment
CSA C22.2, No. 205-M1983, Signal Equipment

Power Requirements

Voltage:

24 VAC, Class 2

Consumption:

40 VA

Input/Output Ratings

Analog Inputs:

4 to 20 mA

Digital Inputs:

Contact closure only

Output (Fault):

24 VAC or VDC, 2 amp (pilot duty), Class 2

Operating Environment

Temperature:

32

°

to

140°

F (0

°

to 60

°

C)

Humidity:

0 to 95% Relative, noncondensing

Physical Dimensions (Electronics only)

Height:

19 inches

Width:

13.25 inches

Depth:

2.5 inches

Weight:

5.85 lb (All aluminum enclosure)

Doc. #569066000—B

7/30/04

1

Lingo Electronic Assembly Installation Instructions

Содержание lingo

Страница 1: ...Lingo Electronic Assembly Installation Instructions DOC 569066000 B 7 30 04 PRINTED IN U S A...

Страница 2: ...ontrols Corporation could void your authority to operate this equipment Industry Canada This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set o...

Страница 3: ...llation procedures for mounting the Lingo electronic assembly connecting it to the telephone network and checking the installation Lingo Specifications Agency Approvals Listed device CUL UL E90949 Sta...

Страница 4: ...Module Address Every Lingo module must have a unique address for it to be properly identified on the local area network LAN Addresses are assigned in the software during system programming NOTE The Li...

Страница 5: ...the telephone cable see Connecting to the Telephone Network below for more detail Ethernet Cable and or RS 232 direct connect cable as required for the application 6 Check all wiring connections and r...

Страница 6: ...ar Controls Part No 600540000 The Ethernet port at the bottom right side of the Lingo electronics assembly using the proper Ethernet components and cables contact the network administrator for more in...

Страница 7: ...ptions Options Lingo with Integral Touchscreen Lingo with Integral Touchscreen and Modem Lingo with Modem Lingo 750000000 750007000 750004000 750005000 24 VAC 40 VA Class 2 Transformer Kit 24V XFR 730...

Страница 8: ...This page intentionally left blank 6 Doc 569066000 B 7 30 04 Lingo Electronic Assembly Installation Instructions...

Отзывы: