Supplying the HPC or
HPC Plus with Power

The HPC and HPC Plus are powered by 24-volts AC and rated at 8 VA. To
supply the module with power, connect the 24 volts to Terminals 15 and 16 by
the label marked “Power Input 8 VA.”

Figure 2 shows the power connections on the HPC or HPC Plus terminal strip.

NOTE! The 24-VAC power connection is isolated. One transformer

can be used to power multiple modules within the restrictions
of an 8-VA consumption.

Wiring the HPC or HPC
Plus

Wiring the Inputs

The HPC and HPC Plus have a removable terminal strip that uses screw
connections. The inputs are Terminals 1 through 10, located on the left side of
the terminal strip (see Figure 2).

NOTE! On the HPC Plus, Terminals 13 and 14 under the “Analog

Outputs” label are used as a digital input. A contact
closure safety switch can be connected to these terminals
as a general fault input.

DOC. #569062000

2/20/01

3

HPC/HPC Plus Installation Instructions

2

16

12

1

15

11

+5V

E

ADJ

24VAC

D

3

17

18

13

S1

+

F

4

14

COM

SHIELD

GND

TEMP

SENSOR

INPUT

MODULE

NETWORK

5V MAX

POWER

INPUT

8 VA

AUX
POT

ANALOG

OUTPUTS

0-10VDC, 1mA MAX

ALL INPUTS

AND OUTPUTS

ARE CLASS 2

STATUS

INPUT

OVER-

RIDE

SWITCH

RELAY OUTPUTS

1A, 24VAC MAX PILOT DUTY

5

19

S2

-

6

20

DI 1

T

R

7

21

RET

RET

A

8

22

DI 2

B

9

23

25

O/R

C

E

10

24

26

D

F

ADDRESS

SWITCH

Figure 2.

HPC/HPC Plus terminal strip

Содержание 738005000

Страница 1: ...INTERFERENCE AND 2 THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION MAX ALLOWABLE AMBIENT TEMP 38 C 100 F 70 C 158 F REFER TO INSTALLATION I...

Страница 2: ...tus does not exceed the Class B limits for radio noise emissions from digital apparatus set out in the interference causing equipment standard entitled Digital Apparatus ICES 003 of Industry Canada Ce...

Страница 3: ...neral fault input to receive contact closure signals from a variety of safety switches This input can be used to initiate an alarm or shut down the heat pump unit when the signal is received from the...

Страница 4: ...e 1 3 Drill holes at the locations marked on the mounting surface 4 Insert metal screws not included through the module and the mounting surface and tighten to secure the module 2 DOC 569062000 2 20 0...

Страница 5: ...ections The inputs are Terminals 1 through 10 located on the left side of the terminal strip see Figure 2 NOTE On the HPC Plus Terminals 13 and 14 under the Analog Outputs label are used as a digital...

Страница 6: ...abel Each HPC or HPC Plus must use a Remote Temperature Sensor RTS UVC for discharge air and one of the following sensors UVC Wall Mount Indoor Temperature Sensor WTS UVC Futura Temperature Sensor FTS...

Страница 7: ...have a status LED The software defines the length of time that the override remains in effect The Futura Temperature Sensor provides an override switch and status LED Refer to the installation instru...

Страница 8: ...lus Only The HPC Plus damper analog output terminals are listed under the label Analog Outputs immediately to the right of the input connections Figure 2 Step Procedure 1 Connect the damper actuator s...

Страница 9: ...regulated switched through Terminals 21 26 A F The relay outputs are isolated from the other connections to permit the additional power source The transformer powering the module can be used if it ha...

Страница 10: ...the address of the HPC or HPC Plus being installed Refer to Figure 3 and set the switches with the correct address from 00 to 63 If a Lingo is used as the executive processor address switches 64 127 d...

Страница 11: ...ed for proper operation by pressing it during a scheduled off mode The LED flashes rapidly until the override period ends The six relay output status LEDs indicate the status of each active digital ou...

Страница 12: ...This page intentionally left blank 10 DOC 569062000 2 20 01 HPC HPC Plus Installation Instructions...

Отзывы: