background image

NovaLynx Corporation 
 

 

260-RGAI-70 

Page 6 

May 2022 

 

6

 

WIRING 

 
CAUTION:

 

Do not apply power to the rain gauge input terminals, as this will damage the 
transmitter board. 

 

CAUTION:

 

Turn off power to the equipment before making any connections. 

 
 

CURRENT METER

POWER SUPPLY

260-RGAI-70

Rain Gauge

User Equipment

DWG 890-0124-01

INPUT

   MODE SELECT SWITCH

0

1-9

1

2

3

4

5

6

7

8

9

RAMP MODE (Default)

RAIN DETECT MODE

1

2

5

10

20

30

45

60

80

Position            Minutes

LOOP

 

 

1.

 

Connect the rain gauge to the INPUT terminal block. Polarity is not important as long as the rain 
gauge switch is dry contact. 

2.

 

Connect the user equipment to the LOOP terminal block. Apply positive power supply voltage 
to the "+" terminal as shown in the diagram above. Connect the 4-20 mA output "-" terminal to 
your monitoring equipment. 

3.

 

Visually confirm that the MODE SELECT SWITCH is at the desired setting. Position 0 (RAMP 
MODE) is the default setting for incrementing the output as rain accumulates. All other 
positions place the unit in RAIN DETECT MODE, with the timeouts shown in the chart. 
 

NOTE:

 there is a pushbutton switch on the circuit board, below the selector switch. The pushbutton 

has no function. 

 

 

Содержание 260-RGAI-70

Страница 1: ...DOC 260 RGAI 70 UM 20220525 260 RGAI 70 User Manual 260 RGAI 70 Rain Gauge Analog Output Interface Phone 530 823 7185 Email nova novalynx com Website www novalynx com...

Страница 2: ...items If packing facilities are not available take the equipment to the nearest Post Office UPS or other freight service and obtain assistance with the packaging Please write the RA on the outside of...

Страница 3: ...ELECTION 5 5 POWER SUPPLY 5 6 WIRING 6 7 OPERATION 7 7 1 Ramp Mode 7 7 2 Rain Detector Mode 7 7 3 Mode Comparison Graphs 7 8 MAINTENANCE 8 9 TROUBLESHOOTING GUIDE 8 POWER SUPPLY CURRENT METER 260 RGAI...

Страница 4: ...esents 100 tips of the bucket During periods of no rain there is no change in the output signal as long as power is not interrupted to the transmitter board In rain detector mode the output stays at 4...

Страница 5: ...s as this will damage the transmitter board NOTE The power supply voltage ripple must be less than 100 volts per second for proper operation A 12 24 VDC loop power supply is recommended for operation...

Страница 6: ...the INPUT terminal block Polarity is not important as long as the rain gauge switch is dry contact 2 Connect the user equipment to the LOOP terminal block Apply positive power supply voltage to the te...

Страница 7: ...ration factor expressed as inches or millimeters per tip To calculate the full scale range multiply the calibration factor by 100 Example 260 2501 Rain Gauge with a calibration factor of 0 01 tip Full...

Страница 8: ...2 second intervals This will simulate pulses from the rain gauge If the output of the transmitter fails to respond contact NovaLynx for a Return Authorization RA number 9 TROUBLESHOOTING GUIDE TROUBL...

Отзывы: