4

 

SITE SELECTION 

The rain gauge exposure is important to collecting accurate information. Refer to the manual for your rain 
gauge for specific recommendations. Ensure the rain gauge is level, otherwise the system may not 
operate correctly. 

If possible, locate the 260-RGAI-70 transmitter enclosure indoors or other protected location. The 
enclosure is watertight if the cover is installed properly, however, the temperature specification of the 
standard unit is only 30°F (~0°C), and therefore protection from extreme cold is desirable. 

5

 

POWER SUPPLY 

 

CAUTION:

 

Do not apply power to the rain gauge input terminals, as this will damage the 
transmitter board. 

 

NOTE:

 

The power supply voltage ripple must be less than 100 volts per second for proper 
operation. 

 
A 12-24 VDC loop power supply is recommended for operation of this instrument. The input voltage 
must take into account all of resistance in the current loop. If the input voltage is too low the output 
will not reach full scale. 
 
Total resistance of the current loop includes the 
input impedance of the monitoring system plus the 
resistance of the wiring. 

 

Find the input impedance of your system by 
consulting the user manual.  

 

Calculate the wiring resistance using the chart. 

 

Add together to obtain the total loop resistance. 

 

Consult the chart below to determine the 
required minimum power supply voltage. 

 

AWG

Ohms / foot

12

0.0016

14

0.0026

16

0.0041

18

0.0065

20

0.0103

22

0.0165

24

0.0262

RESISTANCE OF COPPER WIRE

Содержание 260-RGAI-70

Страница 1: ...DOC 260 RGAI 70 UM 20220525 260 RGAI 70 User Manual 260 RGAI 70 Rain Gauge Analog Output Interface Phone 530 823 7185 Email nova novalynx com Website www novalynx com...

Страница 2: ...items If packing facilities are not available take the equipment to the nearest Post Office UPS or other freight service and obtain assistance with the packaging Please write the RA on the outside of...

Страница 3: ...ELECTION 5 5 POWER SUPPLY 5 6 WIRING 6 7 OPERATION 7 7 1 Ramp Mode 7 7 2 Rain Detector Mode 7 7 3 Mode Comparison Graphs 7 8 MAINTENANCE 8 9 TROUBLESHOOTING GUIDE 8 POWER SUPPLY CURRENT METER 260 RGAI...

Страница 4: ...esents 100 tips of the bucket During periods of no rain there is no change in the output signal as long as power is not interrupted to the transmitter board In rain detector mode the output stays at 4...

Страница 5: ...s as this will damage the transmitter board NOTE The power supply voltage ripple must be less than 100 volts per second for proper operation A 12 24 VDC loop power supply is recommended for operation...

Страница 6: ...the INPUT terminal block Polarity is not important as long as the rain gauge switch is dry contact 2 Connect the user equipment to the LOOP terminal block Apply positive power supply voltage to the te...

Страница 7: ...ration factor expressed as inches or millimeters per tip To calculate the full scale range multiply the calibration factor by 100 Example 260 2501 Rain Gauge with a calibration factor of 0 01 tip Full...

Страница 8: ...2 second intervals This will simulate pulses from the rain gauge If the output of the transmitter fails to respond contact NovaLynx for a Return Authorization RA number 9 TROUBLESHOOTING GUIDE TROUBL...

Отзывы: