Page 5 

January 2021 

 

4

 

SPECIFICATIONS 

 

 

5

 

INSTALLATION 

5.1

 

Outdoors 

For outdoor applications, use the U-bolt to clamp the sensor to a vertical pipe up to 1 ½" (38mm) in 
diameter.

 The 

380-RHRS Solar Radiation Shield 

must

 be in place to protect the tip of the probe from 

rain or sunshine. Remove the cover of the enclosure, then route your cable through the cord grip on 
the bottom of the enclosure. Follow the wiring diagram to make the connections to the screw terminal 
block, then tighten the cord grip, leaving some slack inside. Use cable ties to secure the cable to the 
support pipe. Complete the installation by connecting to your monitoring system. 

5.2

 

Indoors 

The sensor may be mounted indoors without a solar radiation shield. It should be mounted in a 
location that receives adequate air flow for proper operation. The transmitter should be mounted such 
that the cord grip points down to prevent moisture from entering. The U-bolt can be removed and the 
mounting bracket bolted to a wall or post. 

5.3

 

Duct Mount 

The tip of the probe is sometimes inserted into an HVAC duct. In this application, drill a 1" diameter 
hole in the duct at the desired location (away from fans, corners, heating and cooling coils, and other 
equipment that will affect the measurement of the relative humidity). Insert the probe until the 

225-RHP-2Sxx Temperature and Relative Humidity Sensor

Relative Humidity Range

0 to 100% RH

Temperature Range

-40 to 140°F (-40 to 60°C)

Accuracy, RH

±2% 10 to 90% RH @ 25°C

Accuracy, Temperature

±0.9°F @ 72°F (±0.3°C @ 25°C)

Hysteresis

±1%

Repeatability

±0.1% typical

Temperature Limits

-40 to 140°F (-40 to 60°C)

Storage Temperature

-40 to 176°F (-40 to 80°C)

Compensated Temperature Range

-4 to 140°F (-20 to 60°C)

225-RHP-2S11

: 10 to 35 VDC; Output signal: 4 to 20 mA (loop powered).

225-RHP-2S33

: 15 to 35 VDC or 15 to 29 VAC; Output signal: 0 to 5 V @ 5 mA max.

Response Time

15 seconds

Electrical Connections

Removable screw terminal block

Drift

<1% RH/year

RH Sensor

Capacitance polymer

Temperature Sensor

Solid state band gap

Enclosure / Rating

Polycarbonate / NEMA 4X (IP65)

Cable

not included
Transmitter only: 1 lb (.45 kg) / 2 lbs (.9 kg)
Transmitter and Solar Radiation Shield: 2 lbs (.9 kg) / 3 lbs (1.4 kg)

Agency Approvals

CE

Power Requirements

Weight / Shipping

Содержание 225-RHP-2S Series

Страница 1: ...User Manual 225 RHP 2S11 4 20 mA output 225 RHP 2S33 0 5 V output Temperature and Relative Humidity Transmitter 225 RHP 2Sxx Transmitter with 380 RHRS Solar Radiation Shield Phone 530 823 7185 Email n...

Страница 2: ...e items If packing facilities are not available take the equipment to the nearest Post Office UPS or other freight service and obtain assistance with the packaging Please write the RA on the outside o...

Страница 3: ...NSTALLATION 5 5 1 Outdoors 5 5 2 Indoors 5 5 3 Duct Mount 5 6 WIRING 6 6 1 Dual 4 20 mA Output Wiring Model 225 RHP 2S11 6 6 2 Dual 0 5 V Output Wiring Model 225 RHP 2S33 6 7 TROUBLESHOOTING 7 7 1 Tro...

Страница 4: ...tion shield NovaLynx 380 RHRS protects the sensor from rain and radiated heat when installed outdoors The weatherproof enclosure cord grip cable entry point and a filter protect the electronics and se...

Страница 5: ...st 5 3 Duct Mount The tip of the probe is sometimes inserted into an HVAC duct In this application drill a 1 diameter hole in the duct at the desired location away from fans corners heating and coolin...

Страница 6: ...The channels are common on the positive side of the current loop Sensor excitation power is derived from the RH channel so power must always be applied to that channel If the temperature channel is n...

Страница 7: ...emains within these limits under all power line conditions Ripple on the supply should not exceed 100 mV Loop Resistance The maximum allowable loop resistance depends on the power supply voltage Maxim...

Страница 8: ...the humidity sensor while watching for a change in the meter reading The change may take 10 to 40 seconds To increase the temperature reading hold the probe in your hand for several seconds If no chan...