5 TESTING THE HEATING UNIT

5.1 Preliminary checks

Before starting up the heating unit, carry out the following checks: 
- Make sure the heating unit has been installed in compliance with 

legal requirements. 

- Make sure the flue gas discharge pipe is installed correctly.    

When the heating unit is switched on, there must be no leakage 
of combustion products from any of the seals. 

- Check that the supply voltage is 230 V - 50 Hz. 
- Make sure the system is full of water (water pressure 0.8-1 bar). 
- Make sure any cut-off valves in the system are open.
- Make sure there are no oil leaks. 
- Switch on the main switch. 

- Check that the safety valve is not blocked.
- Check for water leaks. 

If the heating unit is not installed in compliance with the relevant 
laws and standards, do not attempt to switch it on and inform the 
Service Centre.

5.2. Switching on and off 

For instructions on how to switch the heating unit on and off, refer 
to the “User Manual”.

6 MAINTENANCE

In order to ensure correct and efficient heating unit operation, have it serviced according to the following schedule and complying to the 
legal requirements.
Correct maintenance allows for efficient and correct functioning of the equipment, granting the better working conditions, optimizing 
performance and safety for people, animals, things and environment.

All maintenance and repairs must be carried out by a properly qualified service engineer. 

It is advisable for the heating unit to be serviced and repaired by an authorised Service Centre, which can provide properly trained quali-
fied personnel. 

Before carrying out any maintenance involving the replacement of components or cleaning inside the unit, always turn off the main 
switch.

6.1 Maintenance schedule

Periodic maintenance covers the following

Checks and Inspections 

- Perform a general check and inspection of the heating unit. 
- Check the oil supply circuit for leaks. 
- Check that the heating unit switches on correctly. 
- Check the combustion parameters by means of flue gas analyses. 
- Check the condition, state and tightness of the flue gas discharge pipes.  
- Check that all the safety devices are intact and operational. 
- Check the fittings for water leaks and oxidation.
- Check the efficiency of the safety valve. 
- Check the safety thermostat.
- Check the contents of the expansion vessel

Cleaning operations:

- Clean the inside of the heating unit. 
- Clean the burner and reset if necessary (see par. 4.4 “Regulating combustion”). 
- Clean the ventilation grille in the room in which the unit is installed. 
- Clean the heat exchange on the flue gas side.

When repairing or servicing the unit for the fist time, perform the following checks:

- Make sure the room of installation is suitable. 
- Check the ventilation openings. 
- Check the diameters, length and state of the flue gas discharge pipes . 
- Make sure the heating unit is installed according to the instructions in this manual.

If the heating unit does not operate correctly or is likely to cause a hazard for people and animals or damage to property, inform 
the Service Centre and fill in the relevant form.

Содержание LYRA C

Страница 1: ...3 45 5 0 64 5 34...

Страница 2: ...FBS VTUPNFS 5IBOL ZPV GPS DIPPTJOH BOE CVZJOH POF PG PVS CPJMFST 1MFBTF SFBE UIFTF JOTUSVDUJPOT DBSFGVMMZ JO PSEFS UP JOTUBMM PQFSBUF BOE NBJOUBJO UIJT FRVJQNFOU QSPQFSMZ...

Страница 3: ...TF PG UIF QBDLBHJOH BT BMM UIF NBUFSJBMT DBO CF SFDZDMFE 5IF QBDLBHJOH NVTU UIFSFGPSF CF TFOU UP TQFDJGJD XBTUF NBOBHFNFOU TJUFT FFQ UIF QBDLBHJOH PVU PG UIF SFBDI PG DIJMESFO BT CZ JUT OBUVSF JU NBZ...

Страница 4: ...OTUBMMJOH UIF VOJU QBHF POOFDUJPOT UP GVFM PJM NBJOT TVQQMZ QBHF 7FOUJMBUJPO QBHF JS JOUBLF BOE GMVF HBT EJTDIBSHF QJQFT QBHF 5ZQFT BOE DMBTTJGJDBUJPO PG BJS JOUBLF BOE GMVF HBT EJTDIBSHF QJQFT QBHF F...

Страница 5: ...NNECTION BETWEEN BOILER AND REMOTE CONTROL IS INTERRUPTED OR THERE ARE SIGNAL PASSAGE DIFFICULTIES NCE THE CONNECTION IS RESTORED THE LIGHT WILL TURN OFF AND THE BOILER WILL RESUME OPERATION NDICATION...

Страница 6: ...FE UIF SFTQPOTF UJNF TIPVME UIFSF CF B EFNBOE GPS EPNFTUJD IPU XBUFS 5IF 5 GVODUJPO JT OPU FOBCMFE XIFO UIF TFMFDUPS JT JO UIF 5 3 QPTJUJPO 0 45 05 8 5 3 5IF EPNFTUJD IPU XBUFS GVODUJPO TUBSUT XIFO UI...

Страница 7: ...S PRESSURE INCREA SES BOILER SAFETY VALVE MAY OPEN AND WATER mOW OUT 3HOULD BOILER FREQUENTLY SHUT DOWN DUE TO INSUFlCIENT WATER PRES SURE HAVE IT SERVICED BY AN UTHORIZED 3ERVICE ENTRE OR QUA LIlED P...

Страница 8: ...QPXEFST 6OJU FMFDUSPOJD NBOBHFNFOU DBSE FBUJOH FYQBOTJPO WFTTFM XJUI MJUSF DBQBDJUZ FBUJOH TBGFUZ WBMWF BU CBS 5ISFF TQFFE IFBUJOH DJSDVMBUPS 4JOHMF TQFFE EPNFTUJD IPU XBUFS DJSDVMBUPS FBUJOH TZTUFN...

Страница 9: ...1MVNCJOH EJBHSBN GPS UIF VOJU QJD 4 130 13 16 1 13 03 5 08 5 3 3 63 3 4 8 130 14 8 16 1 54 5 5 3 045 5 5 300 5 3 045 5 015 0 08 8 3 563 0 8 5 3 GJH PP 7 7 JS JOUBLF 5 WFSTJPO VFM TVQQMZ PP JNFOTJPOT...

Страница 10: ...TJEF 5 1B BJOUBJOJOH MPTT 5 UFNQFSBUVSF TFUUJOH SBOHF BYJNVN XPSLJOH QSFTTVSF CBS FYQBOTJPO WFTTFM DBQBDJUZ M 8 UFNQFSBUVSF TFUUJOH SBOHF BYJNVN 8 XPSLJOH QSFTTVSF CBS 8 TVQQMZ 5 M NJO 1PXFS TVQQMZ 7...

Страница 11: ...OFDU UIF IFBUJOH VOJU UP UIF 8 BOE EFMJWFSZ BOE SFUVSO QJQFT PJO UIF VOJU UP UIF DIJNOFZ BOE UP UIF BJS JOUBLF QJQF GPS WFSTJPOT POOFDU UIF CVSOFS UP UIF GVFM PJM TVQQMZ QJQFT TFF TVC TFDUJPO POOFDU U...

Страница 12: ...CMF NBUF SJBM NBLF TVSF UIF EJTDIBSHF QJQF IBT TVJUBCMF UIFSNBM JOTV MBUJPO NJO NN 1035 5 8IFO nVF HBT TZTUFN JT EJTDIBSHFE UISPVHI QJQFT EJBNFUFS NN JU JT DPNQVMTPSZ UP JOTUBMM PO UIF BJS JOUBLF QJQF...

Страница 13: ...E UP UIF SFTQFDUJWF u UUJOHT PO UIF IFBUJOH VOJU 5IF NBJOT QSFTTVSF NVTU OPU CF NPSF UIBU CBS PUIFSXJTF B QSFT TVSF SFEVDFS OFFET UP CF QSPWJEFE 5IF QSFTTVSF JO UIF 8 DJSDVJU TIPVME CF CFUXFFO BOE CBS...

Страница 14: ...FO 4XJUDI PO UIF NBJO TXJUDI IFDL UIBU UIF TBGFUZ WBMWF JT OPU CMPDLFE IFDL GPS XBUFS MFBLT 4XJUDIJOH PO BOE PGG PS JOTUSVDUJPOT PO IPX UP TXJUDI UIF IFBUJOH VOJU PO BOE PGG SFGFS UP UIF i6TFS BOVBMu...

Страница 15: ...QVNQ JT EFTJHOFE UP PQFSBUF XJUI B UXJO QJQF TZTUFN G ZPV OFFE UP XPSL XJUI B TJOHMF QJQF VOTDSFX UIF DBQ BOE SF NPWF UIF HSVC TDSFX GUFSXBSET SFQMBDF UIF DBQ QJD 1035 5 8JUI UXJO UVCF TZTUFNT CFGPSF...

Страница 16: ...H 5IF DPNCVTUJPO BJS DBO CF SFHVMBUFE CZ UVSOJOH UIF TPDLFU TDSFX TIPXO JO QJD 5IF TFUUJOH JT TIPXO PO B HSBEVBUFE TDBMF 5IF PJM QSFTTVSF DBO CF SFHVMBUFE CZ UVSOJOH TDSFX JO QJD 3FGFS UP UIF UFDIOJDB...

Страница 17: ...UMZ BOE EJTDPOOFDU UIF IJHI WPMUBHF XJSFT QJD QJD VSOFS JHOJUJPO O UIF FWFOU PG TIVUEPXO UIF SFE CF QSFTTFE UP SFTFU 5IF CVSOFS JHOJUJPO DZDMF JT MJHIU PO UIF DPOUSPM QBOFM QJD TVNNBSJTFE JO UIF HSBQI...

Страница 18: ...H QSPDF EVSF BOE UIFO TIVUT EPXO 5IF QIPUPSFTJTUBODF JT EJSUZ MFBO JU 5IF QIPUPSFTJTUBODF JT GBVMUZ 3FQMBDF JU 5IF GMBNF HPFT PVU PS EPFT OPU MJHIU IFDL UIF PJM QSFTTVSF IFDL UIBU PJM GMPXT TNPPUMZ GS...

Страница 19: ...ating unit to be serviced and repaired by an authorised Service Centre which can provide properly trained quali fied personnel Before carrying out any maintenance involving the replacement of componen...

Страница 20: ...PMWFE MPX QSPCF JT GBVMUZ MPX QSPCF JT EJTDPOOFDUFE 3FQMBDF JU MPX QSPCF JT GBVMUZ 3FQMBDF JU 5IF CPJMFS IBT TIVU EPXO BOE SFE MJHIU OP JT BTIJOH PJMFS XJMM BVUPNBUJDBMMZ SFTVNF PQFSBUJPO BT TPPO BT U...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...IO 7KH PDQXIDFWXUHU UHVHUYHV WKH ULJKW WR LPSOHPHQW DQ QHFHVVDU DQG RU XVHIXO YDULDWLRQ WR SURGXFWV ZLWKRXW PRGLI LQJ IXQGDPHQWDO FKDUDFWHULVWLFV ONDITAL 3 P 6IA OCENIGO 6 34 RESCIA TALY 4EL AX E MAIL...

Отзывы: