N-COM Setup manual
17
5.2
S-com (alternative RS586) option
Besides the NCOM protocol we offer an alternative RS485 control (S-com) for dimming and power ON/OFF. Please use the
NCOM App to switch the protocol.
•
RS485
•
Half duplex
•
Frame based
•
Baudrate 9600
•
Data bits 8
•
1 stop bit
•
no parity
Address based on Unit number. Use the NCOM App to set the number: Configuration-tab, Unit number-set to:
Available parameters: BRM(0-255), BRI(0-255), BRU(0-255), POT(0-255), TMP,
PWR (0=OFF,255=ON)
5.2.1.1
Change COM settings in the NCOM app:
-
Switch to S-com
: [Open port], [Lookup], in ‘Tools’
-tab [Set DC to S-com], [Change com to S-com]
o
Test setting: Select message ‘TMP’, DC address ‘1’, [Send to Address], Wait for the result (noreply might
appear shortly)
-
Switch back to NCOM: [Open port], [Lookup
], in ‘Tools’
-tab [Set DC to standard], [Change com to standard], re-power
monitor and restart NCOM App