1
/
4
˝ of insulation from the end of wire, sliding the bare end of
the wire under the clamping plate screw.
3. Set the address on the modules per the job drawing. Use the
rotary code switches to set the address of the first module (be-
tween 01 and 154).
In Class B operation, the remaining modules
are automatically assigned to the next five
higher addresses. For example, if the base ad-
dress switch is set to 28, the next five modules
will be addressed to 29, 30, 31, 32 and 33.
The module is shipped in Class B position,
remove shunts for Class A. When operating in
Class A, alternate modules are paired together
(+0/+1, +2/+3, +4/+5), resulting in a
total of three modules. For example, if the base address switch
is set to 28, then 30 and 32 will be automatically assigned to the
modules while 29, 31 and 33 are available to be used for other
modules on the SLC. For Class A and B operation, DO NOT set the
lowest address above 154, as the other modules will be assigned
to nonexistent addresses.
NOTE:
The XP6-MA must have power cycled for shunt changes
to take effect.
NOTE:
Some panels support extended addressing. In order to set
the module above address 99 on compatible systems, carefully
remove the stop on the upper rotary switch (see Figure 7). If the
panel does not support extended addressing, do not set the lowest
address above 94.
4. A shunt is provided to disable a maximum of two unused modules
in Class B operation and Class A operation. Modules are disabled
from the highest address and work downward. If two modules
are disabled, the lowest four addresses will be functional, while
the highest two will be disabled. For example, in Class B opera-
tion, if the shunt for Address Disable is placed on “two” and the
base switch is set to 28, the modules will be assigned to 28, 29,
30 and 31 while disabling the highest two positions.
NOTE:
Place unused shunts on single pin to store on board for
future use.
NOTE:
Power must not be applied to the unit when changing
functionality on the shunts.
WIRING NOTES
Power-limited circuits must employ type FPL, FPLR, or FPLP
cable as required by Article 760 of the NEC.
All wiring must be in accordance with the NEC, NFPA 72 and
all other applicable codes and standards. All external power
supplies must be power limited with battery back-up. All ex-
ternal power supplies and detectors must be UL listed for fire
protection signaling applications.
PROGRAMMING
The XP6-MA module operates with the following Fire Alarm
Control Panels:
• AM2020/AFP1010
• System 5000 with AIM-200
• AFP-200
• AFC-600
• AFP-300/AFP-400
• NFS-640 (ONYX™ Series System)
• NFS-3030
The modules are programmed as devices in each system according
to the programming instructions in the appropriate FACP manual.
•
•
N500-80-00
3
I56-1806-006
Step 1: Insert the bottom of the XP6-MA module down into a
rear slot on the chassis.
Step 2: Carefully swing the upper edge of the board back
towards the back of the chassis until it touches
the two standoffs.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the instruc-
tions in this manual.
The steps in Figures 6a and 6b describe and illustrate module in-
stallation when the rear chassis position and the position in front
of it will be filled. Front position installation is possible only if
the rear position is filled with an XP module.
Figure 6a. Installation of XP6-MA module in a rear
chassis position, method two:
1
C0225-00
Step 1: Insert the bottom edge of the XP6-MA module down into
a rear slot of the chassis.
Step 2: Carefully swing the upper edge of the board towards the
back of the chassis until it touches the short standoff
attached to the chassis.
Step 3: Align the long standoff with the short standoff and tighten.
Figure 6b. Installation of XP6-MA module in front
chassis position:
2
3
1
C0226-00
Step 1: Insert the bottom edge of the XP6-MA module down
into a front slot of the chassis.
Step 2: Carefully swing the upper edge of the board
towards the back of the chassis until it touches the 1
1
/
4
”
(31.75mm) standoffs installed on the rear module.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the
instructions in this manual.
WIRING
NOTE:
All wiring must conform to applicable local codes,
ordinances, and regulations.
1. Install module wiring in accordance with the job drawings and
appropriate wiring diagrams.
2. All wiring to the XP6-MA is done via terminal blocks. In order
to properly make electrical connections strip approximately
TENS
0
7 8
6
5
4
3
2
1
9
10
11
12
13
14
15
Figure 7.
C0227-00
Содержание XP6-MA
Страница 6: ......