Included:
(7) 1
×
4 Terminal
Blocks
(2) 1
1
/
4
″
(32mm)
Stand offs
(15) Large Shunts
(4) Machine Screws
(5) Short Power
Supply Jumpers (2) Small Shunts
(2) Nuts
(2) EOL Relay
Connector
Assemblies
(6) 47k Ohm
End of Line
Resistors
(1) Long Power Supply Jumper
C0202-01
Shipped on Board:
(1)
Small shunt in A/B select position
(Shipped in Class B position, remove shunt for Class A)
(6) Large shunts on Enable Power Supply Monitors
(6) Large shunts on Disable Short Circuit Protection
(3) Large shunts on Sync Generator
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a
compatible Notifier system control panel.
COMPONENTS
Following are descriptions of the XP6-C mounting frameworks.
There are two mounting options for XP6-C modules:
• Up to six XP6-C modules can be installed on a CHS-6 in
a CAB-3 Series, CAB-4 Series, or BB-25 cabinet.
• One or two XP6-C modules can be installed in a BB-XP cabi-
net.
Chassis
The CHS-6 chassis is used to mount XP6-C modules in a BB-25
CAB-3 or CAB-4 Series cabinet. It accommodates up to six XP6-
C modules in a single cabinet row three modules wide and two
modules deep.
C0206-00
Figure 1: CHS-6 Chassis
The BB-XP cabinet has a built-in chassis that will accommodate
one or two XP6-C modules.
N500-79-00
2
I56-1805-012
0
1
2 3 4 5 6
7
8
9
0
7
8
6
5
4
3
2
1
9
101
1
12
13
14
15
BASE
ADDRESS
ADDRESS
DISABLE
N
O
N
E
O
N
E
TW
O
TH
R
E
E
0
1
2 3 4 5 6
7
8
9
0
7
8
6
5
4
3
2
1
9
101
1
12
13
14
15
BASE
ADDRESS
ADDRESS
DISABLE
NONE
ONE
TW
O
THREE
C0234-00
Figure 2: BB-XP Cabinet
The front XP6-C module positions of each chassis are offset below
the rear XP6-C module positions so that all of the status indicators
are visible.
Cabinets
A BB-25, CAB-3 Series or CAB-4 Series cabinet will house the
CHS-6 chassis with up to six XP6-C modules installed on it. Refer
to cabinet installation documents for dimensions and installation
instructions.
The BB-XP cabinet houses one or two XP6-C modules on the
internal chassis that is part of the cabinet. Refer to cabinet instal-
lation documents for dimensions and installation instructions.
INSTALLATION STEPS
1. Cabinet Mounting
In a clean, dry area, mount the backbox using the four holes pro-
vided in the back surface of the cabinet (Figure 3).
2. Chassis Installation
The CHS-6 chassis is mounted in the BB-25, CAB-3 Series or CAB-4 Series
cabinet. It is shipped with two self-threading screws, which are used to
fasten the chassis to the back wall of the cabinet (see Figure 4).
Backbox
Mounting
Holes
C0235-00
Figure 3: Typical mounting hole locations