154.  The  remaining  modules  are  automatically  assigned  to  the 
next five higher addresses. Provisions are included for disabling 
a maximum of three unused modules to release the addresses to 
be used elsewhere. Each module also has panel controlled green 
LED indicators. The panel can cause the LEDs to blink, latch on, 
or latch off.

In  order  to  synchronize  strobes,  horn/strobes,  and  speaker/
strobes, a SYNC-1 accessory card (sold separately) must be used 
with the XP6-C. See the SYNC-1 installation manual for details on 
how to install.

Each module has terminals for connection to an external supply 
circuit  for  powering  devices  on  its  NAC.  Each  supply  must  be 
power limited and its voltage/current limits must be at or below 
those  specified.  There  is  a  short  circuit  protection  monitor  for 
each module. This is provided to protect the external power sup-
ply against short circuit conditions on the NAC.

BEFORE INSTALLING

If the modules will be installed in an existing operational system, 
inform  the  operator  and  local  authority  that  the  system  will  be 
temporarily  out  of  service.  Disconnect  the  power  to  the  control 
panel  before  installing  the  modules.  This  system  contains  static 
sensitive  components.  Always  ground  yourself  with  a  proper 
wrist strap before handling any circuits so that static charges are 
removed from the body. The housing cabinet should be metallic 
and suitably grounded.

NOTICE:

This manual should be left with the owner/user of this equipment.  

GENERAL DESCRIPTION

The  XP6-C  Six  Circuit  Supervised  Control  Module  is  intended 
for use in an intelligent alarm system. Each module is intended 
for  switching  applications  involving  AC,  DC,  or  audio,  which 
require wiring supervision. A common SLC input is used for all 
modules. Each module has its own address.  A pair of rotary code 
switches is used to set the address of the first module from 01 to 

N500-79-00 

I56-1805-012

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

12 Clintonville Road

Northford, CT 06472-1653

Phone: 203/484-7161

XP6-C 
Six Circuit Supervised Control Module

SPECIFICATIONS

Normal Operating Voltage: 

15-32 VDC

Stand-By Current: 

2.25 mA

Alarm Current: 

35 mA (assumes all six relays have been switched once and all six LEDs solid on) 

Temperature Range: 

32°F to 120°F (0°C to 49°C); –10°C to 55°C (For EN54 applications only) 

Humidity: 

10 to 93% Non-condensing 

 

 

Dimensions: 

6.8

H x 5.8

W x 1.25

D

Accessories: 

CHS-6 Chassis; BB-25 Cabinet; BB-XP Cabinet; CAB-3 Series Cabinet, CAB-4 Series Cabinet

Wire Gauge: 

12-18 AWG 

Max. NAC Circuit Line Loss: 

4 VDC

Power Rating Per Circuit (Speakers): 

63 W @ 70.7 VAC; 50 W @ 25 VAC

Max. NAC Current Ratings: 

For class B wiring systems, 3A

 

For class A wiring systems, 2A

Table 1: Short Circuit Protection - UL 864 9th Edition Requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with requirements in the Standard for 

Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific 

values or not used at all as indicated below.

Program Feature or Option

Permitted in  

UL 864 (Y/N)

Possible Settings

Settings Permitted in UL 864

Disabling short circuit 
protection when a single 
power supply is shared by 
multiple NACs

No

Enable or Disable 
short circuit 
protection

Enable short circuit protection when a single power 
supply is shared by multiple NACs.  Short circuit 
protection can be disabled only when a power supply 
is not shared by multiple NACs.

I56-180

5-0
12

Содержание XP6-C

Страница 1: ...wiring supervision A common SLC input is used for all modules Each module has its own address A pair of rotary code switches is used to set the address of the first module from 01 to N500 79 00 1 I56...

Страница 2: ...has a built in chassis that will accommodate one or two XP6 C modules N500 79 00 2 I56 1805 012 0 1 2 3 4 5 6 7 8 9 0 7 8 6 5 4 3 2 1 9 10 11 12 13 14 15 BASE ADDRESS ADDRESS DISABLE NONE ONE TWO THR...

Страница 3: ...1 C0226 00 Figure 6b Installation of XP6 C module in front chassis position Step 1 Insert the bottom edge of the XP6 C module down into a front slot of the chassis Step 2 Carefully swing the upper edg...

Страница 4: ...nd short circuit protection must be enabled on the NAC circuits that are sharing a power supply NOTE Short circuit protection can only be disabled if a power supply is not being shared by multiple NAC...

Страница 5: ...le supply figures 10 and 12 are typical can be shared among multiple NACs If a sup ply is to be shared between NACs wired to a common PCB use the short power supply jumpers shown on page 1 The jumpers...

Страница 6: ...NSTRUCTION MANUAL FOR WIRE REQUIREMENTS POWER LIMITED AND SUPERVISED TOP OF T0 EOLR 1 TYP RED VIO VIO RED BLK BLK C0818 02 Figure 10 Example of Class B Style Y NAC configuration with a single supply s...

Страница 7: ...WIRE REQUIREMENTS POWER LIMITED AND SUPERVISED TOP OF T0 SLC SLC SLC SLC A2143 10 47K C0179 04 Figure 12 Example of Class A Style Z NAC configuration with a single supply shared by 2 NACs BASE ADDRESS...

Страница 8: ...vide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance w...

Отзывы: