154. The remaining modules are automatically assigned to the
next five higher addresses. Provisions are included for disabling
a maximum of three unused modules to release the addresses to
be used elsewhere. Each module also has panel controlled green
LED indicators. The panel can cause the LEDs to blink, latch on,
or latch off.
In order to synchronize strobes, horn/strobes, and speaker/
strobes, a SYNC-1 accessory card (sold separately) must be used
with the XP6-C. See the SYNC-1 installation manual for details on
how to install.
Each module has terminals for connection to an external supply
circuit for powering devices on its NAC. Each supply must be
power limited and its voltage/current limits must be at or below
those specified. There is a short circuit protection monitor for
each module. This is provided to protect the external power sup-
ply against short circuit conditions on the NAC.
BEFORE INSTALLING
If the modules will be installed in an existing operational system,
inform the operator and local authority that the system will be
temporarily out of service. Disconnect the power to the control
panel before installing the modules. This system contains static
sensitive components. Always ground yourself with a proper
wrist strap before handling any circuits so that static charges are
removed from the body. The housing cabinet should be metallic
and suitably grounded.
NOTICE:
This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The XP6-C Six Circuit Supervised Control Module is intended
for use in an intelligent alarm system. Each module is intended
for switching applications involving AC, DC, or audio, which
require wiring supervision. A common SLC input is used for all
modules. Each module has its own address. A pair of rotary code
switches is used to set the address of the first module from 01 to
N500-79-00
1
I56-1805-012
INSTALLATION AND MAINTENANCE INSTRUCTIONS
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203/484-7161
XP6-C
Six Circuit Supervised Control Module
SPECIFICATIONS
Normal Operating Voltage:
15-32 VDC
Stand-By Current:
2.25 mA
Alarm Current:
35 mA (assumes all six relays have been switched once and all six LEDs solid on)
Temperature Range:
32°F to 120°F (0°C to 49°C); –10°C to 55°C (For EN54 applications only)
Humidity:
10 to 93% Non-condensing
Dimensions:
6.8
″
H x 5.8
″
W x 1.25
″
D
Accessories:
CHS-6 Chassis; BB-25 Cabinet; BB-XP Cabinet; CAB-3 Series Cabinet, CAB-4 Series Cabinet
Wire Gauge:
12-18 AWG
Max. NAC Circuit Line Loss:
4 VDC
Power Rating Per Circuit (Speakers):
63 W @ 70.7 VAC; 50 W @ 25 VAC
Max. NAC Current Ratings:
For class B wiring systems, 3A
For class A wiring systems, 2A
Table 1: Short Circuit Protection - UL 864 9th Edition Requirements
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with requirements in the Standard for
Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific
values or not used at all as indicated below.
Program Feature or Option
Permitted in
UL 864 (Y/N)
Possible Settings
Settings Permitted in UL 864
Disabling short circuit
protection when a single
power supply is shared by
multiple NACs
No
Enable or Disable
short circuit
protection
Enable short circuit protection when a single power
supply is shared by multiple NACs. Short circuit
protection can be disabled only when a power supply
is not shared by multiple NACs.
I56-180
5-0
12