background image

4

Simplex 4010 NION Installation/Operation Manual  Version 2   Document 51998  Rev. A1  03/26/03

WARNING 

Several different sources of power can be con-

nected to the fire alarm control panel.  Disconnect all sources of
power before servicing.  Control unit and associated equipment
may be damaged by removing and/or inserting cards, modules,
or interconnecting cables while the unit is energized.  Do not
attempt to install, service, or operate this unit until this manual is
read and understood.

CAUTION - 

System Reacceptance Test after Software

Changes.  To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after any
programming operation or change in site-specific software.  Re-
acceptance testing is required after any change, addition or de-
letion of system components, or after any modification, repair or
adjustment to system hardware or wiring.

All components, circuits, system operations, or software func-
tions known to be affected by a change must be 100% tested.  In
addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50 devices, must
also be tested and proper system operation verified.

This system  meets NFPA requirements for operation at
0-49° C/32-120° F

 

 and at a relative humidity of 85% RH - 93%

per ULC - (non-condensing) at 30°

 

C/86° F.  However, the useful

life of the system's standby batteries and the electronic compo-
nents may be adversely affected by extreme temperature ranges
and humidity.  Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal
room temperature of 15-27° C/60-80° F.

Verify that wire sizes are adequate for all initiating and
indicating device loops.  Most devices cannot tolerate more than
a 10% I.R. drop from the specified device voltage.

Like all solid state electronic devices, this system may

operate erratically or can be damaged when subjected to light-
ning-induced transients.  Although no system is completely im-
mune from lightning transients and interferences, proper ground-
ing will reduce susceptibility.  

Overhead or outside aerial wiring

is not recommended, due to an increased susceptibility to
nearby lightning strikes.  Consult with the Technical Services
Department if any problems are anticipated or encountered.

Disconnect AC power and batteries prior to removing or in-
serting circuit boards.  Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure.  When possible, make all
cable entries from the sides or rear.  Before making modifica-
tions, verify that they will not interfere with battery, transformer,
and printed circuit board location.

Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal re-
moval.

Though designed to last many years, system components
can fail at any time.  This system contains static-sensitive com-
ponents.  Always ground yourself with a proper wrist strap be-
fore handling any circuits so that static charges are removed
from the body.  Use static-suppressive packaging
to protect electronic assemblies removed from the unit.

Follow the instructions in the installation, operating, and
programming manuals.  These instructions must be followed to
avoid damage to the control panel and associated
equipment.  FACP operation and reliability depend upon proper
installation by authorized personnel.

WARNING: This equipment generates, uses, and can radiate
radio frequency energy and if not installed and used in accor-
dance with the instruction manual, may cause interference to
radio communications.  It has been tested and found to com-
ply with the limits for class A computing device pursuant to
Subpart B of Part 15 of FCC Rules, which is designed to pro-
vide reasonable protection against such interference when
operated in a commercial environment.  Operation of this
equipment in a residential area is likely to cause interference,
in which case the user will be required to correct the interfer-
ence at his own expense.

Canadian Requirements

This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications.

Le present appareil numerique n'emet pas de bruits radio-
electriques depassant les limites applicables aux appareils
numeriques de la classe A prescrites dans le Reglement sur
le brouillage radioelectrique edicte par le ministere des Com-
munications du Canada.

FCC Warning

Installation Precautions

Adherence to the following will aid in problem-free installation with long-term reliability:

Precau-L-4-2002.p65

Acclimate Plus™HARSH™NOTI•FIRE•NET™ONYX™, and VeriFire™ are trademarks, and FlashScan® and VIEW® are registered trademarks of NOTIFIER.
NION™ and UniNet™ are trademarks of NIS.  NIS™ and Notifier Integrated Systems™ are trademarks and NOTIFIER® is a registered trademark of Fire•Lite
Alarms, Inc.  Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation.  ARCNET® is a registered trademark of Datapoint
Corporation.  Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.  LEXAN® is a registered trademark of GE Plastics, a subsidiary
of General Electric Company.

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Содержание UniNet 2000 Simplex 4010 NION

Страница 1: ...x 4010 NION A1 51998 A1 ECN 02 298 Document 51998 03 26 03 Rev UniNet 2000 Simplex 4010 NION Installation and Operation Manual Version 2 Technical Manuals Online http www tech man com firealarmresourc...

Страница 2: ...2 Simplex 4010 NION Installation Operation Manual Version 2 Document 51998 Rev A1 03 26 03 This page intentionally left blank Technical Manuals Online http www tech man com firealarmresources com...

Страница 3: ...ns caused by escaping gas improper storage of flammable mate rials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate o...

Страница 4: ...efore making modifica tions verify that they will not interfere with battery transformer and printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage...

Страница 5: ...4010 NION Architecture 15 Figure 2 2 Simplex 4010 NION to Simplex 4010 9811 Serial Connections 16 2 2 Simplex 4010 NION Enclosure and Mounting 17 Figure 2 3 Simplex 4010 NION Power Connection 17 Figu...

Страница 6: ...6 Simplex 4010 NION Installation Operation Manual Version 2 Document 51998 Rev A1 03 26 03 Technical Manuals Online http www tech man com firealarmresources com...

Страница 7: ...originating from a Simplex 4010 panel UniNet consists of graphical workstations monitoring and controlling local or remote twisted pair or fiber optic networks Remote network monitoring is achieved t...

Страница 8: ...8 Simplex 4010 NION Installation Operation Manual Version 2 Document 51998 Rev A1 03 26 03 This page intentionally left blank Technical Manuals Online http www tech man com firealarmresources com...

Страница 9: ...technologies The Simplex 4010 NION provides transparent or interpreted communications between the workstation and control panel The NION connects a LonWorks FT 10 or fiber optic network to a fire ala...

Страница 10: ...SW2 Network SW2 Network SW2 Network SW2 Network SW2 Network Binding Button Binding Button Binding Button Binding Button Binding Button SW1 Reset SW1 Reset SW1 Reset SW1 Reset SW1 Reset Button Button B...

Страница 11: ...ween monitored equipment and the network Connections One twisted pair of wires or dedicated fiber optic cable is used for data transmission in the UniNet network The wire must be Twisted pair cable UL...

Страница 12: ...transformer isolated making all network communication immune to ground fault conditions Therefore no ground fault supervision of the Echelon network is required or provided FTXC PCA and FTXC PCB Netwo...

Страница 13: ...when an error occurs This suppresses noise propagation throughout the network Figure 1 5 Sample Style 7 Networks For more information about Style 7 network configuration refer to the Local Area Server...

Страница 14: ...r allow runs of up to 12db of attenuation between each node with up to 64 nodes per segment DFXC DFXC DFXC DFXC DFXC Dual Fiber Optic Transceiver Figure 1 6 FOXC PCA and DFXC PCA Fiber Optic Network T...

Страница 15: ...ON NION NION NION NION NION EchelonT EchelonT EchelonT EchelonT EchelonTo Other Nodes o Other Nodes o Other Nodes o Other Nodes o Other Nodes Ethernet T Ethernet T Ethernet T Ethernet T Ethernet To Ot...

Страница 16: ...rial Connections The Simplex 4010 NION requires that a Simplex model 4010 9811 dual EIA 232 card be installed in the Simplex 4010 FACP The NION communicates to the 4010 FACP through serial port P6 onb...

Страница 17: ...er 3 Mount the enclosure to the wall Refer to the enclosure mounting hole layout below Figure 2 4 NISCAB 1 Enclosure Mounting Hole Layout Power Requirements and Connection The Simplex 4010 NION requir...

Страница 18: ...ting Studs w Standoffs Mounting Studs w Standoffs Mounting Studs w Standoffs Mounting Studs w Standoffs Figure 2 5 Installing the NION in a NISCAB 1 Mounting NION boards within the enclosure When inst...

Страница 19: ...CHANGE button on the form This will cause a dialogue box to be displayed with the names of all available configuration files Select SX4010 cfg and then click the OPEN button Finally click DONE to end...

Страница 20: ...Simplex 4010 Explorer The Simplex 4010 NION is easily configured to communicate with a Simplex 4010 FACP via the Simplex 4010 Explorer Only an operator with administrator privileges can access configu...

Страница 21: ...ces or labels are added or changed a Panel Learn must be performed again Figure 3 4 Duplicate Device Labels The Simplex 4010 devices must not have any duplicate device labels If duplicate device label...

Страница 22: ...ppress Psuedo Points box in the data display See figure 3 6 UL Functionality This option will be displayed only if the current operator is logged in as an administrator This option must always be chec...

Страница 23: ...M M M M M Mounting 17 N N N N N NFN Explorer Overview 19 NION NPB 9 NISCAB 1 17 P P P P P Power Requirements 11 R R R R R Required Equipment 9 Index S S S S S Serial Communication Settings 16 Serial C...

Страница 24: ...o NOTIFIER 12 Clintonville Road Northford Connecticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products...

Отзывы: