Program
Point Program
38
NFS-3030 Programming Manual P/N 51345:C 11/4/03
this screen. The user may choose a Custom Action Message at this screen.
Figure 3.26 Custom Action Message Screen
Soft Keys
CUSTOM ACTION MESSAGE:
Enter the number of the Custom Action Message to be displayed
during alarm conditions for this point (refer to Figure 3.19 for an example).
VIEW:
Press this soft key to view the message associated with the number entered.
ACCEPT:
Press to save the entries made on this screen.
Sensitivity
Detector sensitivity levels for alarm and prealarm are set at this screen, which displays when the
SENSITIVITY
soft key is pressed at the Detector Point Programming (2) screen.
Figure 3.27 Detector Sensitivity Screen
The control panel provides nine levels of Prealarm and Alarm in percent per foot obscuration, or,
for heat detectors, in degrees Centigrade. Alarm sensitivity settings range from one to nine, with
one representing the most sensitive alarm level and nine the least sensitive.
Prealarm sensitivity settings range from zero to nine. Zero indicates no prealarm. A value of one
can be a self-optimizing setting where the control panel selects a suitable prealarm level for the
detector. Values one or two through nine represent decreasing sensitivity, with nine being the least
sensitive.
Refer to the section “Detector Sensitivity Settings” in Appendix D: AWACS™ Applications for a
D E T E C T O R C U S T O M A C T I O N M E S S A G E
L 0 3 D 1 2 3
C U S T O M A C T I O N M E S S A G E : 0 0 1
C u s t o m
A c t i o n
M e s s a g e
D i s p l a y e d h e r e .
A C C E P T
V I E W
B A C K
D E T E C T O R S E N S I T I V I T Y
L 0 3 D 1 2 3
O C C U P I E D
U N O C C U P I E D
S E N S I T I V I T Y
S E N S I T I V I T Y
A L A R M - 7
A L A R M = 3
O C C U P I E D
U N O C C U P I E D
S E N S I T I V I T Y
S E N S I T I V I T Y
P R E A L A R M - 5
P R E A L A R M = 3
A L A R M S E N S I T I V I T Y T A B L E
A C C E P T
1 = 0 . 5 0 %
4 = 1 . 1 9 %
7 = 1 . 8 9 %
2 = 0 . 7 3 %
5 = 1 . 4 3 %
8 = 2 . 1 2 %
3 = 0 . 9 6 %
6 = 1 . 6 6 %
9 = 2 . 3 5 %
B A C K
www.PDF-Zoo.com
Содержание NFS-3030/E
Страница 14: ...General Information Getting Started 14 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 76: ...Service Screens Application Corrupt Screen 76 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 120: ...CBE Zones and Equations Equations 120 NFS 3030 Programming Manual P N 51345 C 11 4 03 Notes www PDF Zoo com...
Страница 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...