Dual Action NBG-12LA

NBG-12LA Manual Pull Station

Document 51300   Revision A1   ECN: 01-293   09/14/01

Door ‘keys’ into

backplate at this point

12LAdoormount.wmf

1. Position the door and backplate side

by side in the full open position.  (i.e.

180-degrees  with  respect  to  each

other.)

2. With  the  backplate  position  fixed,

move the door behind the backplate,

as shown in the illustration, part A.

3. Align the hinge posts and holes by

bringing  the  door  up  to  meet  the

backplate,  paying particular attention

to the ‘keying’ that occurs when the

door’s  post  hole  is  aligned  to  the

backplate’s hinge post.  Refer to the

illustration, part B.

4. With  the  two  pieces  aligned  and

‘keyed’  together,  slide  the  holes

down onto the posts.  Refer to the

illustration, part C.

5. Holding the backplate, close the door

slightly to lock the door and backplate

together.

Door Reattachment

If the door becomes detached,

 complete the following steps to

reattach the door to the backplate.  The door cannot be connected

to the pull station if the unit is mounted to a backbox.

Switch Contact Rating

FACP Circuit (Terminals 1 & 2):

Rated to .25 Amp at 30 Volts (AC or DC).

Auxiliary Contact Circuit (Terminals 3 & 4):

Rated to 3 Amps at 30 Volts (AC or DC).

Mounting

Surface mount the NBG-12LA pull station to a SB-10 surface

backbox.  Semi-flush mount the NBG-12LA to a standard single-

gang, double-gang, or 4-inch (10.16 cm) square electrical box.

Description:

The NBG-12LA Pull Station is a non-coded manual pull station

which provides a Fire Alarm Control Panel (FACP) with a single

alarm initiating input signal.  The pull station also provides a

second set of contacts rated up to 3 Amps at 30 volts (AC or

DC), for auxiliary functions.  The NBG-12LA is a dual action

model equipped with a key lock reset.  It is UL listed and meets

the ADA requirement of a 5-lb. maximum pull down force to

activate.  Operating instructions are molded into the handle.

Molded terminal numbers can also be found adjacent to the

wiring terminals.

With the door and backplate

aligned and ‘keyed’ together,

slide the holes down onto the

posts.

Door mated to Backplate

at this stage.

Closing the door slightly

locks  the  door  and

backplate together.

UL

Product ID

Label

UL

Product ID

Label

      Post

      Hole

Post

 Hole

Post

NBG12-Face2.cdr