Notifier LCD2-80 Скачать руководство пользователя страница 3

LCD2-80 Instruction Manual —

 P/N 53242:B1 10/25/2012   

3

Installation Precautions

Adherence to the following will aid in problem-free installation with 

long-term reliability:

WARNING - Several different sources of power can 
be connected to the fire alarm control panel.

  Dis-

connect all sources of power before servicing.  Control 
unit and associated equipment may be damaged by 
removing and/or inserting cards, modules, or intercon-
necting cables while the unit is energized.  Do not 
attempt to install, service, or operate this unit until man-
uals are read and understood. 

CAUTION - System Re-acceptance Test after Soft-
ware Changes:

 To ensure proper system operation, 

this product must be tested in accordance with NFPA 
72 after any programming operation or change in site-
specific software.  Re-acceptance testing is required 
after any change, addition or deletion of system com-
ponents, or after any modification, repair or adjustment 
to system hardware or wiring. All components, circuits, 
system operations, or software functions known to be 
affected by a change must be 100% tested.  In addi-
tion, to ensure that other operations are not inadver-
tently affected, at least 10% of initiating devices that 
are not directly affected by the change, up to a maxi-
mum of 50 devices, must also be tested and proper 
system operation verified.  

This system

 meets NFPA requirements for operation 

at 0-49º C/32-120º F  and at a relative humidity  93% ± 
2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F).   
However, the useful life of the system's standby batter-
ies and the electronic components may be adversely 
affected by extreme temperature ranges and humidity.  
Therefore, it is recommended that this system and its 
peripherals be installed in an environment with a nor-
mal room temperature of 15-27º C/60-80º F. 

Verify that wire sizes are adequate

 for all initiating 

and indicating device loops.  Most devices cannot tol-
erate more than a 10% I.R. drop from the specified 
device voltage. 

Like all solid state electronic devices,

 this system 

may operate erratically or can be damaged when sub-
jected to lightning induced transients.  Although no sys-
tem is completely immune from lightning transients and 
interference, proper grounding will reduce susceptibil-
ity. Overhead or outside aerial wiring is not recom-
mended, due to an increased susceptibility to nearby 
lightning strikes.  Consult with the Technical Services 
Department if any problems are anticipated or encoun-
tered. 

Disconnect AC power and batteries

 prior to remov-

ing or inserting circuit boards.  Failure to do so can 
damage circuits. 

Remove all electronic assemblies

 prior to any drill-

ing, filing, reaming, or punching of the enclosure. When 
possible, make all cable entries from the sides or rear.  
Before making modifications, verify that they will not 
interfere with battery, transformer, or printed circuit 
board location. 

Do not tighten screw terminals

 more than 9 in-lbs.  

Over-tightening may damage threads, resulting in 
reduced terminal contact pressure and difficulty with 
screw terminal removal. 

This system contains static-sensitive compo-
nents.

  Always ground yourself with a proper wrist 

strap before handling any circuits so that static charges 
are removed from the body.  Use static suppressive 
packaging to protect electronic assemblies removed 
from the unit.

Follow the instructions

 in the installation, operating, 

and programming manuals. These instructions must be 
followed to avoid damage to the control panel and 
associated equipment. FACP operation and reliability 
depend upon proper installation.

Precau-D1-9-2005

FCC Warning

WARNING: 

This equipment generates, uses, 

and can radiate radio frequency energy and if not 
installed and used in accordance with the instruction 
manual may cause interference to radio communica-
tions. It has been tested and found to comply with the 
limits for class A computing devices pursuant to Sub-
part B of Part 15 of FCC Rules, which is designed to 
provide reasonable protection against such interfer-
ence when devices are operated in a commercial 
environment. Operation of this equipment in a resi-
dential area is likely to cause interference, in which 
case the user will be required to correct the interfer-
ence at his or her own expense.

Canadian Requirements

This digital apparatus does not exceed the Class A 
limits for radiation noise emissions from digital appa-
ratus set out in the Radio Interference Regulations of 
the Canadian Department of Communications.  
Le present appareil numerique n'emet pas de bruits 
radioelectriques depassant les limites applicables 
aux appareils numeriques de la classe A prescrites 
dans le Reglement sur le brouillage radioelectrique 
edicte par le ministere des Communications du Can-
ada.  

HARSH™

NIS™

, and 

NOTI•FIRE•NET™

 are all trademarks; and 

Acclimate® Plus

FlashScan®

NION®

,

NOTIFIER®

ONYX®

ONYXWorks®

UniNet®

VeriFire®

, and 

VIEW®

 are all registered trademarks of Honeywell

International Inc.  

Echelon®

 is a registered trademark and 

LonWorks™

 is a trademark of Echelon Corporation.

ARCNET®

 is a registered trademark of Datapoint Corporation.  

Microsoft®

 and 

Windows® 

are registered

trademarks of the Microsoft Corporation. 

 

©2011 by Honeywell International Inc.  All rights reserved. Unauthorized use of this document is strictly
prohibited.  

Содержание LCD2-80

Страница 1: ...B1 P N 53242 B1 ECN 12 0233 Document 53242 10 25 2012 Rev Liquid Crystal Display LCD2 80 Instruction Manual ...

Страница 2: ...rning of a fire Smoke detectors cannot be expected to provide ade quate warning of fires caused by arson children play ing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reach...

Страница 3: ...oards Failure to do so can damage circuits Remove all electronic assemblies prior to any drill ing filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may dama...

Страница 4: ...priate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printe...

Страница 5: ...ches and Indicators 10 1 6 1 LED Indicators 10 1 6 2 Piezo 11 1 6 3 Address Switches SW1 and SW2 11 1 6 4 ACS TERM Mode Switch SW10 11 1 6 5 DIP Switches SW3 11 Section 2 Terminal Mode Configuration 12 2 1 Switches 12 2 2 Terminal Mode EIA 485 Connections 13 Section 3 ACS Mode Configuration 15 3 1 Switches 15 3 2 ACS Mode EIA 485 Connections 16 3 3 Programming 16 3 3 1 General Tab 17 3 3 2 Point L...

Страница 6: ...ly with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 9th Edition The following products have not received UL 864 9th Edition certification and may only be used in retrofit applications Operation of the LCD2 80 with products not tested for UL864 9th Edition has not been evaluated and may not comply with NFPA 72 and or the latest edition of UL 864 ...

Страница 7: ... panel Device address from control panel EIA 485 connects to control panel terminal port No programming necessary mimics the host control panel In ACS Mode The LCD2 80 supplies a means to display a subset of the panel message text or to display custom messages programmed using VeriFire Tools The power limited EIA 485 interface provided by the control panel will support the installation of devices ...

Страница 8: ...85 mA Include these currents in your power supply loading and battery calculations Address Switches SW1 SW2 See Section 1 6 3 on page 11 DIP Switches SW3 See Section 1 6 5 on page 11 AKS 1B J2 See Section 1 5 3 on page 10 Terminal Connections TB1 TB2 See Section 1 5 1 on page 9 Piezo Sounder SP1 See Section 1 6 2 on page 11 LCD280wmodeswtch wmf NUP Connection J3 See Section 1 5 2 on page 10 ACS TE...

Страница 9: ...to 28 VDC Power can also be provided by an FACP with an integral power supply as long as the LCD2 80 is listed for use with the FACP The power run to the LCD2 80 must be power limited but need not contain a Power Supervision Relay since loss of power is inherently supervised through communication loss EIA 485 In EIA 485 Out EIA 485 In EIA 485 Out No connection Reference Common Out Common In 24 Vol...

Страница 10: ...leared Supervisory Yellow Indicates a Supervisory condition on the FACP This LED will remain lit until all supervisory conditions have been cleared System Trouble Yellow Indicates a Trouble condition on the FACP This LED will remain lit until all trouble conditions have been cleared Point Disable Yellow Indicates that a point on the FACP has been disabled This LED will remain lit until the point h...

Страница 11: ... if the LCD2 80 is used with a legacy panel 3 4 ON Set ON to connect to PC for updating LCD2 80 firmware OFF Set OFF when not connected to PC for updating LCD2 80 firmware 3 5 ON ACS Mode When the LCD2 80 is set for ACS Mode switch 3 6 is set to ON and it will be used in receive only mode switch 3 5 must be set to ON Otherwise set to OFF When in ACS receive transmit mode the panel supervises the L...

Страница 12: ...Mode annunciator interface The EIA 485 terminal interface does not support the use of RPT 485 repeaters 2 1 Switches DIP switches at SW3 must be set for terminal mode and SW10 ACS TERM Mode switch must be set to TERM Setting the DIP switches Refer to DIP Switches SW3 on page 11 for a full explanation of all the switch settings For switches 3 1 3 2 and 3 4 set as necessary according to the explanat...

Страница 13: ... supervised Maximum of 32 LCD2 80s may be connected to this circuit 6000 feet maximum distance 16 AWG between the control panel and the first or last LCD2 80 and between each LCD2 80 Use overall foil braided shield twisted pair cable suitable for EIA 485 applications terminated to earth at one end EIA 485 circuit rated 5 5 VDC max 60 mA max The LCD2 80s require connection of operating power Connec...

Страница 14: ...d SW3 5 ON All LCD2 80s except last one set DIP Switch SW3 7 and SW3 8 ON and SW3 5 OFF TB2 TB2 Twisted Shielded Pairs EIA 485 Return EIA 485 Out Return Out Return EIA 485 Out Cabinet See notes in preceding text 4 3 2 1 4 3 2 1 EIA 485 Connections on LCD2 80 OUT RET OUT RET NFS 320 NFS2 640 TB11 2 TB11 4 TB11 1 TB11 3 NFS2 3030 NCA 2 TB9 2 TB9 4 TB9 1 TB9 3 Table 2 1 EIA 485 Control Panel Connecti...

Страница 15: ...W3 must be set for ACS mode and SW10 ACS TERM Mode switch must be set to ACS Setting the DIP switches Refer to DIP Switches SW3 on page 11 for a full explanation of all the switch settings For switches 3 1 3 2 and 3 4 set as necessary according to the explanations DIP Switches 3 3 3 5 3 6 3 7 and 3 8 are unique to ACS Mode configuration 3 3 Set ON to do a database download Set OFF when download is...

Страница 16: ...The EIA 485 loop can support up to 32 devices on the loop subject to power supply loading limitations ACS LDM and LCD type devices 6000 feet maximum loop length from the CPU to the last device Do not T Tap the EIA 485 circuit it will not function properly Wire as illustrated Use twisted shielded pair cable with a characteristic impedance of approximately 120 ohms EIA 485 5 5 VDC max 60 mA max A UL...

Страница 17: ...t appear in the display Point Label Display Mode 40 Characters Select to display the 40 character point label in the second and third rows of the display for the first point event that is active Pressing the Step Display key will scroll through any other active events 20 Characters Select to display two 20 character point labels in the second and third rows of the display for the first and last po...

Страница 18: ...er 3 3 2 Point Labels Tab Installed ACS Circuit The drop down menu contains a list of all the ACS circuits programmed into the host panel Select the desired circuit for programming The type field and point grid will populate with the appropriate information Function Default is Alarm Select pull down menu to change to another function Function selections Alarm Supervisory Security Non Fire and Tele...

Страница 19: ...FS2 3030 NCA 2 They do not activate for off normal events from legacy panels in Terminal mode Note If Acknowledge Silence and Reset switches are enabled for system control access security must be provided by mounting the LCD2 80 in a locked fire alarm cabinet or annunciator backbox model ABF 1B or ABS 1TB with AKS 1B key switch option Display Step LampTest Drill Acknowledge Signal Silence Reset Al...

Страница 20: ...ill turn on When the panel sends an AC FAIL message the backlight will turn on as follows Alarm events the backlight will turn on and stay on Pressing Step Display will turn on the backlight for 60 seconds Note that an AC Fail message is sent from the panel only when a Starting ACS Circuit Type of SYS is entered in initial programming If ACS is selected in programming as the Starting ACS Circuit T...

Страница 21: ...entarily pressing this switch will illuminate the display for 60 seconds If this switch is pressed and held in excess of 3 seconds the LCD2 80 will go into Lamp Test mode During Lamp Test all LEDs will light all segments of the display will turn on and the piezo will sound for the duration the switch is pressed Upon release of the switch the LCD2 80 software version number will briefly be displaye...

Страница 22: ...fault detection on the remote power supply When employing the LCD2 80 in Terminal Mode Terminate the EIA 485 shields at either the cabinet when not in conduit or at system common when in conduit as outlined below When the EIA 485 shield is not in conduit At each respective LCD2 80 enclosure except the first on the loop terminate the shield coming in from the previous LCD2 80 at the outside of the ...

Страница 23: ...IMS ANY AND ALL OTHER WARRANTIES EITHER EXPRESSED OR IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL...

Страница 24: ...World Headquarters 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www notifier com ...

Отзывы: