10
HS-NCM Installation Document —
P/N 54014:B2 04/25/2014
Figure 7 The HS-NCM-W
Switch Functions: Ground Fault Detection.
For UL 864 applications, enable ground fault
detection by setting EF switches “on”:
SW4.1 for Channel A, and SW4.2 for Channel B.
Correct configuration depends on your network
design; for an explanation of design concepts, refer to
the
High-Speed Noti•Fire•Net™ Manual
.
Ground faults are detected when the resistive value
reaches 0 ohms.
Ground Fault monitoring is performed by the FACP
associated with the HS-NCM.
TB4-1
CH-A (+)
Channel-A Driver/Receiver
TB4-2
CH-A (-)
Channel-A Driver/Receiver
TB5-1
CH-B (+)
Channel-B Driver/Receiver
TB5-2
CH-B (-)
Channel-B Driver/Receiver
Table 2 NOTI•FIRE•NET™ Connections: HS-NCM-W
NOTE: Ground fault detection
must
be enabled for UL 864 applications and for ULC applications.
Note:
Wiring from the HS-NCM-W that is installed outside the building:
• Cannot exceed 1000m (3280 ft.).
• Must be in conduit and is to be buried in a trench separate from any power lines.
• Cannot cross any power lines.