Applications
Controlling Three NACs and One Door Holder With One Input
28
FCPS-24S PN 51977:C1 08/06/03
Notes: The following notes apply to Figure 5.2 on page 27.
1. The Output 4 door holder circuit will deactivate 60 seconds after Control Input
#1 is activated or AC power is lost.
2. When the FCPS-24S power supply is in an inactive state (control module not
active), a trouble on the power supply will result in an open circuit condition on
the control module output circuit (monitored by End-of-Line Resistor across
Terminals 5 & 6). As an alternative, the trouble contacts at TB5 of the power
supply can also be used for independent trouble monitoring.
3. Do not loop wires under screw terminals. Break wires to maintain proper
supervision.
4. An End-of-Line Resistor must be installed between terminals 5 & 6 for control
module wiring supervision (the ELR value is dependent on the module
employed).
5. For a list of compatible devices, refer to the Device Compatibility Document.
www.PDF-Zoo.com