Applications

Controlling Three NACs and One Door Holder With One Input

28

FCPS-24S          PN 51977:C1         08/06/03

Notes: The following notes apply to Figure 5.2 on page 27.

1. The Output 4 door holder circuit will deactivate 60 seconds after Control Input 

#1 is activated or AC power is lost.

2. When the FCPS-24S power supply is in an inactive state (control module not 

active), a trouble on the power supply will result in an open circuit condition on 
the control module output circuit (monitored by End-of-Line Resistor across 
Terminals 5 & 6).  As an alternative, the trouble contacts at TB5 of the power 
supply can also be used for independent trouble monitoring.

3. Do not loop wires under screw terminals.  Break wires to maintain proper 

supervision.

4. An End-of-Line Resistor must be installed between terminals 5 & 6 for control 

module wiring supervision (the ELR value is dependent on the module 
employed).

5. For a list of compatible devices, refer to the Device Compatibility Document.

www.PDF-Zoo.com

Содержание FCPS-24S6

Страница 1: ...Field Charger Power Supply FCPS 24S6 FCPS 24S8 Document 51977 8 06 03 Revision C1 PN 51977 C1 ECN 03 396 www PDF Zoo com ...

Страница 2: ...ning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predeter mined rate or reaches a predetermined level Rate of rise heat detectors may be subject to redu...

Страница 3: ...ronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere with battery trans former and printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resulting in reduced ter minal contact pressur...

Страница 4: ...4 FCPS 24S PN 51977 C1 08 06 03 Notes www PDF Zoo com ...

Страница 5: ...ble Supervision 23 4 1 Supervision via FACP Notification Appliance Circuit 23 4 1 1 Supervision of FACP to FCPS wiring 23 4 1 2 Supervision of FCPS 24S Faults 23 4 1 3 Trouble Relay 24 4 2 AC Loss Reporting Delay 24 SECTION 5 Applications 25 5 1 Controlling Four NACs With One Input and Selective Silence 25 5 2 Controlling Three NACs and One Door Holder With One Input 27 5 3 Split Temporal Mode of ...

Страница 6: ...tories Documents UL 464 Audible Signaling Appliances UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired Other NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority H...

Страница 7: ...e power supply will activate its Notification Appliance Circuits During the inactive or nonalarm state the power supply supervises its NAC field wiring for short and open conditions AC fail battery charger and ground fault troubles will also be monitored by the power supply If an NAC or power supply fault is detected the power supply Normally Closed Trouble contact will open If an alarm condition ...

Страница 8: ...he power supply jumpers as described in Jumpers on page 9 2 Install the power supply as described in Installation on page 13 3 Program the power supply as described in Programming Options on page 18 4 Wire the power supply circuits referring to the options described in Trouble Supervision on page 23 and the application examples in Applications on page 25 5 Connect primary power source wiring while...

Страница 9: ...dy voltage input signal the jumper for the corresponding input circuit should be in the default position which jumpers the bottom two pins as illustrated in drawing at left If the source voltage to the input circuit is coded variable voltage the jumper for the corresponding input circuit should be moved to jumper the top two pins 1 5 LED Indicators AC Power on green LED indicates AC power is prese...

Страница 10: ... 24S6 6 0 amps FCPS 24S8 8 0 amps Output Circuit Types Four Style Y NACs require 4 7 KΩ End of Line Resistors or Style Z NACs using the optional ZNAC 4 Class A converter module OR Four resettable or nonresettable 24 VDC power outputs Refer to Notifier Device Compatibility Document for listed compatible devices Trouble Relay Contact Rating TB5 Fail safe Form C relay normally energized transfers wit...

Страница 11: ...C Out 4 NAC Out 4 Supervised Earth AC Neutral AC Hot Trouble Relay Form C Fail safe shown energized Normally Open Normally Closed Common JP1 Ground Fault Detection cut to disable JP2 JP3 Coded Noncoded Input Selection JP4 Supervised Battery Battery 18 AH 24 VDC Nonpower limited LEDs Charger Trouble AC Loss yellow NAC Trouble yellow Battery Trouble yellow Ground Fault yellow AC Power green SW1 Prog...

Страница 12: ...uring the inactive state the remote power supply supervises its NAC field wiring for short and open conditions If a fault is detected the power supply will enter a trouble condition and illuminate the NAC Trouble LED When the NACs are activated the supervision is disabled and the circuits are no longer supervised Supervision of other power supply faults such as low battery battery charger trouble ...

Страница 13: ...ox Set the board and transformers aside in a safe clean place Avoid static discharge which may damage static sensitive components on the board 2 Mark and predrill holes for the top two keyhole mounting bolts 3 Install two upper fasteners in the wall with the screw heads protruding approximately 4 Using the upper keyholes mount the backbox over the two screws 5 Mark the lower two holes remove the b...

Страница 14: ...gure 2 2 Backbox Mounting Dimensions Bottom Height 15 00 38 10 cm 10 625 26 99 cm 0 75 1 9 cm 2 875 7 3 cm Backbox 14 5 36 8 cm Depth 3 050 7 75 cm Top 9 1 23 1 cm 2 7 6 86cm 1 125 2 868 cm Mounting Plate Pem Studs Backbox Mounting Holes rcpscabb cdr www PDF Zoo com ...

Страница 15: ...TB5 TB2 JP1 JP2 OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM 1 2 3 4 5 6 7 8 9 10 8 7 6 5 4 3 2 1 TB2 3 2 1 Figure 2 3 NAC Style Y Class B 4 7KΩELR Horn Strobe Horn Strobe Horn Strobe Alarm Polarity Shown FCPS 24S Circuit Board 24fsclsb cdr TB4 JP3 J3 TB5 TB2 JP1 JP2 OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1...

Страница 16: ...n circuit board 1 2 3 4 5 6 7 8 O N 1 2 3 4 5 6 7 8 ON TB1 J2 TRANSFORMER 2 TRANSFORMER 1 J1 F1 JP4 30V 15A SW1 SW1 TB4 TB4 JP3 JP3 J3 TB5 TB2 JP1 JP2 JP2 EARTH NEUT HOT OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX AUX IN2 IN2 IN2 IN2 OUT1 OUT1 OUT1 OUT1 IN1 IN1 IN1 IN1 SYNC IN SYNC IN SYNC IN SYNC IN AUX AUX NO NC AUX TBL COM BATTERY AC BATT GND FLT NAC TRBL AC CHGR CAUTION HIGH VOLTAGE CAUTION HI...

Страница 17: ...wer limited applications use of conduit is optional 1 2 3 4 5 6 7 8 O N TB1 J2 TRANSFORMER 2 TRANSFORMER 1 J1 F1 JP4 30V 15A SW1 TB4 JP3 J3 TB5 TB2 JP1 JP2 EARTH NEUT HOT OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM BATTERY AC AC BATT CHGR GND FLT NAC TRBL CAUTION HIGH VOLTAGE CAUTION HIGH VOLTAGE NAC 4 CLASS A A A NAC 3 CLASSA A A NAC...

Страница 18: ...acement in the ON and OFF positions Important Change DIP switch settings only when all power AC DC is removed ON 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 ON TB1 J2 TRANSFORMER 2 TRANSFORMER 1 J1 F1 JP4 30V 15A SW1 TB4 JP3 J3 TB5 TB2 JP1 JP2 EARTH NEUT HOT OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 8 7 6 5 4 3 2 1 3 2 1 10 9 8 7 6 5 4 3 2 1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM BA...

Страница 19: ... 2 Sync Input is monitored3 Only nonresettable Auxiliary Power is available from TB4 Terminals 9 10 Output 4 function follows DIP switch 8 setting 5 ON 6 OFF Split Temporal FCPS configured as Master switch 3 OFF Control Input 1 controls NAC Outputs 1 2 and Control Input 2 controls Outputs 3 42 which will generate a Temporal code signal without sync Sync Input is ignored FCPS configured as Slave sw...

Страница 20: ...r supply is the originator of the strobe synchronization pulses on its NAC outputs In sync generator mode the sync type System Sensor Wheelock or Gentex Commander II is selectable via DIP switches 1 and 2 When this power supply is configured as a sync follower Slave Synchronization mode the power supply s NAC outputs track the strobe synchronization pulses present at the supply s Sync Input termin...

Страница 21: ...nput 1 Sync Input is monitored2 Resettable or nonresettable Auxiliary Power Output is available from TB4 Terminals 9 10 Control Input 2 determines if reset will occur must go from On to Off for a 6 second reset to occur OFF ON Split Alarm FCPS configured as Master switch 3 OFF NAC Outputs 1 2 are controlled by Control Input 1 and Outputs 3 41 are controlled by Control Input 2 Sync Input is ignored...

Страница 22: ...l disable the charger It should only be disabled if an external battery charger is being used for the FCPS 24S 3 2 6 Door Closers Output Circuit 4 can be configured as an NAC or door closer circuit Setting DIP switch 8 to the OFF position will configure Output Circuit 4 as an NAC Setting DIP switch 8 to the ON position will configure only Output Circuit 4 as a door closer circuit which will provid...

Страница 23: ... open circuit condition on its NAC An internal trouble contact is located between TB4 Terminal 3 In and TB4 Terminal 5 Out Any of the following conditions will cause the trouble contact to open provided the FACP Notification Appliance Circuit is not in alarm The following trouble conditions will cause a general NAC trouble A field wiring fault on the NAC output of the power supply An AC fail condi...

Страница 24: ... AC Loss Reporting Delay The reporting of AC loss to a central station is usually delayed in order to prevent multiple transmissions of AC loss and restoral thus allowing AC power to stabilize When a host FACP is programmed to delay AC loss reporting the FCPS 24S must be configured to delay the reporting of AC fail This is accomplished by setting SW1 DIP switch 4 to the ON position This will preve...

Страница 25: ... 5 6 7 8 9 10 8 7 6 5 4 3 2 1 8 7 TB2 3 2 1 OUT4 NAC4 8 7 TB2 8 9 8 8 9 9 10 11 12 13 14 15 0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 0 1 2 3 4 7 6 5 TENS ONES ADDRESS LOO P 8 9 8 8 9 9 10 11 12 13 14 15 0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 0 1 2 3 4 7 6 5 TENS ONES ADDRESS LOO P Figure 5 1 Controlling Four Outputs With One Input Control Module Relay Module EOL Power Supervision Relay A77 716B energized SLC SLC ...

Страница 26: ...7 IN2 and Terminal 9 Aux Power 3 Do not loop wires under screw terminals Break wires to maintain proper supervision 4 An End of Line Resistor must be installed between TB4 Terminals 5 6 for control module wiring supervision the ELR value is dependent on the module employed 5 Supervise the power wiring between the FPCS 24S auxiliary 24 VDC output on TB4 Terminals 9 10 with an EOL relay P N A77 716B...

Страница 27: ... panel The module could be replaced with any circuit capable of polarity reversal such as an FACP Notification Appliance Circuit Figure 5 2 Controlling Three NACs and One Door Holder With One Input Style Z Class A Style Y Class B Door Holder Circuit 4 Output NAC 3 Output NAC 2 Output NAC 1 Use listed ELR 4 7KΩ to terminate Style Y Class B NAC ELR not required for Style Z Class A NAC Door Holder Do...

Страница 28: ...pply will result in an open circuit condition on the control module output circuit monitored by End of Line Resistor across Terminals 5 6 As an alternative the trouble contacts at TB5 of the power supply can also be used for independent trouble monitoring 3 Do not loop wires under screw terminals Break wires to maintain proper supervision 4 An End of Line Resistor must be installed between termina...

Страница 29: ...tivate the power supply s temporal output circuits 3 4 Figure 5 3 Split Temporal Mode Application Style Z Class A Style Y Class B Temporal Bell Circuit 4 Temporal Bell Circuit 3 Horn Strobe Circuit 2 Horn Strobe Circuit 1 Use listed ELR 4 7KΩ to terminate Style Y Class B NAC ELR not required for Style Z Class A NAC Note All NACs are supervised and power limited ZNAC 4 Option Module SW1 Switch Sett...

Страница 30: ...ross Terminals 5 6 As an alternative the trouble contacts at TB5 of the power supply can also be used for independent trouble monitoring 2 Do not loop wires under screw terminals Break wires to maintain proper supervision 3 An End of Line Resistor must be installed between terminals 5 6 for control module wiring supervision the ELR value is dependent on the module employed and across terminals 7 8...

Страница 31: ...ettable power source such as the Aux Power output of the FCPS 24S to Control Input 1 For addressable panel applications an addressable monitor module can be used to monitor the trouble contact of the FCPS 24S and the resettable power connection from the FACP using an End of Line power supervision relay If the FCPS 24S enters a trouble condition the Normally Closed trouble contact will open and if ...

Страница 32: ...t for module wiring supervision the ELR value is dependent on the module employed 2 An End of Line power supervision relay must be connected between TB4 Terminals 5 6 The Normally Closed when energized power supervision relay contact must be in series with the End of Line Resistor referred to in note 1 3 Do not loop wires under screw terminals Break wires to maintain proper supervision 4 For a lis...

Страница 33: ...Terminal 3 24 VDC is applied directly to Terminal 4 from the FACP 2 The Normally Closed alarm relay may consist of an actual relay in the FACP or a control module which may be mounted remotely or at the FACP 3 A monitor module may be used to monitor the FCPS 24S Trouble contacts at TB5 Any power supply trouble will cause the contacts to change states 4 A maximum of 4 0 amps from the FCPS 24S6 and ...

Страница 34: ...tification appliances when its Normally Open contact 7 9 closes FACP NAC programmed for Sync NAC 1 TB4 JP3 J3 TB5 TB2 JP1 JP2 OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM 1 2 3 4 5 6 7 8 9 10 8 7 6 5 4 3 2 1 3 2 1 TB4 JP3 J3 TB5 TB2 JP1 JP2 OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC ...

Страница 35: ...ces from the same manufacturer in each system TB4 JP 3 J3 TB 5 TB 2 JP1 JP2 OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM 1 2 3 4 5 6 7 8 9 10 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 3 2 1 TB4 JP3 J3 TB5 TB2 JP1 JP2 OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM 1 2 3 4 5 6 7 8 9 10 3...

Страница 36: ...3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM 1 2 3 4 5 6 7 8 9 10 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 3 2 1 TB4 JP3 J3 TB5 TB2 JP1 JP2 OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM 1 2 3 4 5 6 7 8 9 10 3 2 1 Internal Trouble Contact Internal Trouble Contact ELR for FACP NAC 4 7K ELR for FCPS...

Страница 37: ...requires connection to a separate dedicated AC branch circuit which must be labeled FIRE ALARM This branch circuit must connect to the line side of the main power feed of the protected premises No other non fire alarm equipment may be powered from the fire alarm branch circuit The branch circuit wire must run continuously without any disconnect devices from the power source to the power supply Ove...

Страница 38: ...Table 6 2 shows how to convert milliamperes and microamperes to full amperes 6 3 2 How to Calculate System Current Draw Use Table 6 3 on page 39 to calculate current draws as follows 1 Enter the quantity of devices in all three columns 2 Enter the current draw where required Refer to the Notifier Device Compatibility Document for compatible devices and their current draw 3 Calculate the current dr...

Страница 39: ...em Current Draw Calculations Device Type Calculate Column 1 Primary Non Fire Alarm Current amps Calculate Column 2 Primary Fire Alarm Current amps Calculation Column 3 Secondary Non Fire Alarm Current amps Qty X current draw Total Qty X current draw Total Qty X current draw Total Main Circuit Board 1 X 0 091 1 X 0 145 1 X 0 065 Power Supervision Relay X 0 025 X 0 025 X 0 025 NAC Output 1 X NAC Out...

Страница 40: ...ms require 24 hours of standby power followed by 5 minutes in alarm NFPA 72 Central Auxiliary and Remote Station Fire Alarm Systems require 60 hours of standby followed by 5 minutes in alarm Batteries installed in a system powered by a generator need to provide at least 4 hours of standby power 6 4 2 Selecting and Locating Batteries Select batteries that meet or exceed the total ampere hours calcu...

Страница 41: ...Module 15 see also ZNAC 4 7 Class B see also Style Y 7 Coded Input 9 Coded Noncoded Input Selection 9 coding NAC 7 compatibility input circuit 7 control circuit 7 current 10 see also input circuit 10 voltage 10 current maximum continuous 7 maximum short term 8 standby 10 total continuous 10 total short term 10 D dimensions backbox 14 E ELR installation 23 see also End of Line Resistor 23 End of Li...

Страница 42: ...7 see also NAC output 10 Style 10 voltage rating 10 output power 7 P Power nonresettable 7 resettable 7 power supply board layout drawing 11 connectors and jumpers 11 power supply requirements 37 powering supply 37 power limited 7 power limited wiring 17 R relay trouble 7 8 10 24 reporting delay AC loss 24 resettable power 21 S secondary power see also battery 10 Specific Application Power see als...

Страница 43: ... 12 Clintonville Road Northford Connecticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that NOTIFIER is not an insurer and assumes n...

Страница 44: ...World Headquarters 12 Clintonville Road Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www notifier com NOTIFIER is a company www PDF Zoo com ...

Отзывы: