B710LP Plug-in Detector Base
Installation Instructions
Before installing detectors, please thoroughly read the system wiring and installation manuals, and manual
System
Smoke Detectors Application Guide
, which provides detailed information on detector spacing, placement, zoning, and
special applications. Copies of these manuals are available from Notifier.
GENERAL DESCRIPTION
The B710LP base is a plug in detector base intended for use in a 2-wire intelligent system, with screw terminals provided
for power (+ and –), and remote annunciator connections. Communication takes place over the power (+ and –) lines.
BASE TERMINALS
NO.
FUNCTION
1
POWER (–), REMOTE ANNUNCIATOR (–)
2
POWER (+)
3
REMOTE ANNUNCIATOR (+)
C0127-00
SPECIFICATIONS
Diameter: 6.1 inches (15.5 cm)
Mounting: 4-inch square box (102 mm) with or without plaster ring
Min. Depth: 1.5 inches (38 mm)
4-inch (102 mm) Octagon Box, Min. Depth: 1.5 inches (38 mm)
3-1/2 inch (89 mm) Octagon Box, Min. Depth: 1.5 inches (38 mm)
Single Gang Box, Min. Depth: 1.5 inches (38 mm)
Operating Temperature Range: 32° to 150°F (0° to 66°C)
STRIPPED WIRE
WIRE WITH
SPADE LUG
3
2
1
BASE
TERMINALS
TAMPER PROOF
TAB
N550-05-00 1 I56-637-06R
Notifier, 12 Clintonville Rd., Northford , CT 06472-1653, (203) 484-7161
N550-05-00 4 I56-637-06R
©2003 Notifier
Please refer to insert for the Limitations of Fire Alarm Systems
REMOTE ANNUNCIATOR, MODEL RA400Z
The remote annunciator is connected between terminals 1 and 3 using the spade lug terminal packed with the remote
annunciator. The spade lug terminal is connected to the base terminal as shown in Figure 5.
It is not acceptable for three stripped wires to be under the same wiring terminal unless they are separated by a
washer or equivalent means. The spade lug supplied with the model RA400Z is considered an equivalent means. See
Figure 5 for proper installation.
C0116-00
Figure 5: Connection to Remote Annunciator Terminal
Figure 1: Terminal Layout
www.PDF-Zoo.com
firealarmresources.com