background image

B710LP  Plug-in Detector Base 

Installation Instructions

 

 

Before  installing  detectors,  please  thoroughly  read  the  system  wiring  and  installation  manuals,  and  manual 

System 

Smoke Detectors Application Guide

, which provides detailed information on detector spacing, placement, zoning, and 

special applications. Copies of these manuals are available from Notifier.   

 

 

 

 

 

 

 

 

 

 

 

 

 

GENERAL DESCRIPTION

The B710LP base is a plug in detector base intended for use in a 2-wire intelligent system, with screw terminals provided 
for power (+ and –), and remote annunciator connections. Communication takes place over the power (+ and –) lines. 

BASE TERMINALS

NO. 

FUNCTION

POWER (–), REMOTE ANNUNCIATOR (–)

POWER (+)

REMOTE ANNUNCIATOR (+)

C0127-00

SPECIFICATIONS

Diameter:                                          6.1 inches (15.5 cm)
Mounting:                                          4-inch square box (102 mm) with or without plaster ring
                                                          Min. Depth: 1.5 inches (38 mm)
                                                          4-inch (102 mm) Octagon Box, Min. Depth: 1.5 inches (38 mm)
                                                          3-1/2 inch (89 mm) Octagon Box, Min. Depth: 1.5 inches (38 mm)
                                                          Single Gang Box, Min. Depth: 1.5 inches (38 mm)
Operating Temperature Range:        32° to 150°F (0° to 66°C)

STRIPPED WIRE

WIRE WITH

SPADE LUG

3

2

1

BASE

TERMINALS

TAMPER PROOF

TAB

N550-05-00                                                                             1                                                                           I56-637-06R
 

 

 

 

   

Notifier, 12 Clintonville Rd., Northford , CT 06472-1653, (203) 484-7161

N550-05-00                                                                             4                                                                           I56-637-06R
                                                                                                                                                                          ©2003 Notifier

Please refer to insert for the Limitations of Fire Alarm Systems

REMOTE ANNUNCIATOR, MODEL RA400Z

The remote annunciator is connected between terminals 1 and 3 using the spade lug terminal packed with the remote 
annunciator. The spade lug terminal is connected to the base terminal as shown in Figure 5.

It is not acceptable for three stripped wires to be under the same wiring terminal unless they are separated by a 
washer or equivalent means. The spade lug supplied with the model RA400Z is considered an equivalent means. See 
Figure 5 for proper installation.

C0116-00

Figure 5: Connection to Remote Annunciator Terminal

Figure 1: Terminal Layout

www.PDF-Zoo.com

Отзывы: