Page 2
IMPORTANT INSTALLATION INFORMATION
ELECTRICAL CONNECTIONS
Cable - The use of shielded cable is recommended
for all encoder installations. When a Dynapar brand
encoder is ordered, the type of termination is gener-
ally defined (usually the last selectable code in
Ordering Information). If a code for a cable was
indicated, the encoder was manufactured to include a
shielded cable. If any other type of termination was
selected or if selection of termi-nation type was not
requested, a cable assembly must be ordered. (The
cable assembly easily hooks onto the encoder’s
connector making it ready for wiring).
To determine which cable assembly to order, refer to
the Electrical Connections table (in the encoder’s
manual).
GENERAL GUIDELINES
Encoders provide quality measurements and long
life when common sense, care, and accurate
alignments are provided during installation. The
following general guide-lines will help to ensure a
trouble-free installation.
Mounting the Encoder
Do not shock the encoder.
Do not subject the encoder to
axial or radial shaft stresses.
Do not tool the encoder
or its shaft.
Do not use makeshift techniques
to mount the encoder.
Do not use a rigid coupling.
Do not disassemble the encoder.
Wiring the Encoder
•
Never connect or disconnect the encoder connec-
tor or wiring while power is ON. Doing so may
damage the encoder.
•
Power should always be connected to the + side
of DC power.
•
Common should always be connected to the -
side of DC power.
•
Never connect A, B, or Z to the + or - side of DC
power.
In some cases, there may be more than one table or
the table may be broken into sections due to different
output types. If so, refer to the information listed for
the output type selected for the encoder (in Ordering
Information).
Wiring should be run through dedicated conduits or
harnesses (not shared with any other wiring) which
are spaced at least 12 inches apart. This protects the
cable from physical damage while providing a degree
of electrical isolation. Also, do not run cable in close
proximity to other conductors which carry current to
heavy loads such as motors, motor starters,
contactors, or solenoids. Doing so could result in
electrical transients in the encoder cable which cause
undesired signal pulses.
NOTE: Never connect or disconnect the encoder
connector or wiring while power is ON. Doing so
may damage the encoder.
ELECTRICAL CONNECTIONS
(cont.)
Grounding:
For applications with high ground poten-
tial differences, DO NOT ground the encoder through
both machine and controls end. Connect the shield at
the controls end only.
NOTE: If the shield is con-
nected at both ends, grounding problems that
degrade system performance can result.
CE Grounding Measures
–
For best EMC immunity
the cable screen must be grounded on both encoder
and controls end. For cable lengths longer than 30m
or outdoor applications, additional measures must be
implemented to comply with CE requirements. Con-
nection of the encoder to DC power supply network is
prohibited if CE compliance is required. CE-compliant
products are tested to EN61326-1 EMC.
In all cases, system CE compliance is ultimately the
responsibility of the manufacturer integrating the
encoder.
FEATURES
All encoders have the following electrical features:
•
Power (+DC)
•
Common
•
Output Signal(s)
Power (also referred to as supply, power source, and
power +V/VCC) is DC for encoders.
There-
fore, power should always be connected to the
positive (+) side of DC power.
In addition, encoder
power should be regulated to within
±
5% at the
encoder and should be free of induced transients.
Common (also referred to as Com, supply common,
and ground) is generally a black wire (verify via
Electrical Connections table).