OPX300K2 05/12
16
Sensing Output
Frequency
50
Hz
60
Hz
Voltage
100 Volt Class
100V
(86.5V~110V~120V)
120V
200 Volt Class
200V
(173V~220V~240V)
240V
Phase:
Single Phase
Single Phase
Power Input
Voltage:
100V ~ 127V ~
139V
Frequency:
50 Hz /
60 Hz
Phase:
Single Phase
Single Phase
Sensing Output
Max. Voltage:
87% of Power Input Voltage (DC Voltage)
(F+) – (F-)
Continuous Current: Maximum 3A Current
Current Maximum Forcing: 9A forcing 1 to 5 seconds at 25°C
Field Resistance: Minimum 15 Ohms
Voltage Adjust Range
Minimum ±5% of Normal Voltage
Volt/ Hertz Characteristic
57 Hz in 60 Hz operation mode, 47 Hz in 50 Hz operation mode
Voltage Build-Up
Self-Building Up at over 6V Power Input Voltage
Voltage Changeable Rate
Maximum
±1.5%
Temperature Drift
Within ±0.02%/ degree C
Operating Temperature
-4°F (-20°C) to 140°F (60°C)
Storage Temperature
-4°F (-20°C) to 158°F (70°C)
Outside Dimension
5.6" x 4.0" x 1.57" (140mm x 100mm x 40 mm)
Weight
1.4 lbs. (0.65 kgs)
Automatic Voltage Regulator: DST-100-2FAK