The HeatmiserNeo Driver
19
All Thermostats
Object Type:
[HeatmiserNeo v20\AllThermostat]
Object Type:
[HeatmiserNeo v10\AllThermostat]
The All Thermostats object is used to set common values across all zone thermostat devices.
Description
Reference Type
Standby Mode
Activates standby mode, also called frost
protection mode. In this mode the neoStat
will only turn on heating if the room
temperature falls below the Frost
Protection Setpoint
V46
Obj\OffOn; Adjustable
Frost Protection Setpoint
Temperature maintained in frost protect
or holiday modes
V109
Obj\Num: 7…17; Adjustable
Heat/Cool Mode
V22
Obj\ENum; Adjustable
Values: 0=Vent, 1=Heating, 2=Cooling, 3=Auto
Hold Temperature
Set to activate hold temperature for
Default Hold Time, or ‘0’ to cancel hold
V24
Obj\Num; Adjustable
Hold Time (mins)
Set a time to activate or extend the hold
time, or ‘0’ to cancel hold
V25
Obj\Num; Adjustable
Floor Temperature Limit
Set a floor limiting temperature,
depending on sensor selection.
V108
Obj\Num: 20…45; Adjustable
Comfort Level – day
Contains a list of time-temperature values
to define the profile for a
day
. Refer to
Program Mode for which days are in use.
A profile contains up to four time-
temperature values, referred within
Heatmiser at wake, leave, return, sleep.
The day,
y
, is in the range 1…7 where
1=Monday .. 7=Sunday
P
y
Obj\Profile: 4 or 6 periods; Adjustable
Switching Differential
Controls the switching differential of the
thermostat. The default is 1°, which means
with a setpoint temperature of 20°, the
thermostat will switch the heating on at
19° and off at 20°
V116
Obj\ENum: 0..3; Adjustable
Values: 0=0.5°, 1=1°, 2=2°, 3=3°
Output Delay (mins)
To prevent rapid switching, an output
delay set
V111
Obj\Num: 0…15; Adjustable
User Up/Down Limit
Limits the use of the up/down
temperature keys
V121
Obj\Num: 0…10; Adjustable
Max Preheat (Hrs)
Optimum start will delay the start-up of
the heating system to the latest possible
moment.
V110
Obj\Num: 0…5; Adjustable
Lock
Indicates if the keypad lock is active. Set to
‘Off’ (0) to unlock the keypad
V29
Obj\OffOn; Adjustable
Lock PIN
Set a 4-digit PIN to activate the keypad
lock
V30
Obj\Text: max 4 chars; Adjustable