North Star M165955A Скачать руководство пользователя страница 20

Installation / Initial Set-Up 

 

 

 

20 

  

 

 

Never run the generator inside any closed or semi-enclosed spaces (even if 
outdoors), including homes, garages, basements, sheds, or boxes.  

These 

spaces can trap poisonous gases, even if you run a fan or open windows.

   

 

Never place the generator immediately adjacent to a building or other 
structure – allow at least 20 feet clearance. 

 

Place the generator so that the exhaust fumes will not be directed towards 
people or building air intakes.   

 

Ensure that working, battery-operated or battery back-up carbon monoxide 
alarms are used in any dwelling/structure that is in close proximity to the 
running generator. 

 

Note that this generator is NOT designed or approved for use in vehicles 
or marine applications.  Never run the generator inside RVs or other 
vehicles, on boats, or on pick-up truck beds. 

 

    WARNING: 

Never attempt to attach ductwork to the muffler system to allow for 
installation inside an enclosure.  This could cause hot air deflection, 
heat build-up, and increased exhaust backpressure, resulting in 
possible exhaust leakage or damage to the generator. 

Adequate cooling 
ventilation 

The generator needs adequate, unobstructed flow of air to allow for 
proper cooling of engine and generator head.   

 

   WARNING: 

Heat build-up from inadequate ventilation can result in fire, 
posing a serious risk to nearby persons and structures. 

 

 

Situate so there is adequate clearance around generator to allow for 
cooling airflow so that heat does not build up.    

 

 

Never place the generator immediately adjacent to large objects or 
structures – allow at least a 7 foot clearance. 

 

Do not run the generator in close proximity to other heat-generating 
equipment, such as another generator.  The combined heat that is 
generated may raise air temperature in the immediate area and there will 
not be adequate cooling ventilation. 

 

Do not allow debris to accumulate and block airflow. 

 

Do not operate with a tarp, blanket, or cover surrounding the generator. 

 

No wet conditions  Choose a location where the generator will NOT be exposed to rain, 

snow, or direct sunlight.

  Exposure to water can cause electric shock.   

 

You 

may

 operate the generator under an outdoor, canopy-like structure of 

heat-resistant material that is open on all sides.  Make sure that all parts of 
canopy are at least 7 feet from exhaust, and allow for adequate clearance 
above generator so that heat does not build up. 

 

Hot exhaust 
clearance 

The exhaust gas from your generator is extremely hot and can cause 
combustible materials to catch on fire.   

 

Содержание M165955A

Страница 1: ...or is properly grounded Use only UL listed outdoor rated grounded extension cords of proper size NEVER plug the generator directly into a wall outlet ANY connection to a building s electrical system M...

Страница 2: ...Hazard Signal Word Definitions 2...

Страница 3: ...t up as a PORTABLE or BUILDING BACK UP Power Source 16 5 Selecting a Suitable Site 19 6 Grounding the Generator 22 7 Battery Installation 23 Operation 1 General Safety Rules for Operation 24 2 Prepari...

Страница 4: ...rements for natural gas and propane See the Specifications section of this manual with regard to specific gas flow and pressure requirements In addition note the following Natural gas The standard del...

Страница 5: ...e engine Owner s Manual furnished with the generator NorthStar is constantly improving its products The specifications outlined herein are subject to change without prior notice or obligation The purc...

Страница 6: ...3 Hertz Hz Voltage Regulation 110 129V 110 129V Power Factor 1 0 p f 1 0 p f Engine Honda GX630 Honda GX690 Engine Speed 3390 3798 RPM 3390 3798 RPM Fuel Type LP NG LP NG Pressure Range LP NG 7 11 in...

Страница 7: ...austic acid and explosive gases can cause blindness or severe burns NO smoking sparks or flames NEVER touch both battery terminals at the same time with your hand or any non insulated tools FLUSH imme...

Страница 8: ...f Description Ref Description 1 Air Cleaner 7 Generator Head 2 Engine Key Switch 8 Fuel Inlet 3 Oil Drain Plug 9 Vibration Isolation Mount 4 Oil Fill Port 10 LP NG Regulator Assembly Kit 5 Battery not...

Страница 9: ...ad The electricity producing part of the generator Reference 8 Fuel Inlet A connection point to hook up the fuel supply Reference 9 Vibration Isolation Mount The engine and generator are mounted on ru...

Страница 10: ...wattage The running and starting wattage requirements are often listed on a device s nameplate If wattage is not given on the device s nameplate the wattage may be calculated by multiplying the namepl...

Страница 11: ...Printer 950 Lights Ten 75 Watt light bulbs 750 Microwave Oven 1000W 1000 Milk Cooler 1100 1800 Milker Vacuum Pump 2 HP 1000 2300 Miter Saw 10 1650 2400 Oscillating Fan 200 400 Portable Heater Kerosene...

Страница 12: ...ces on your list This total must be lower than the continuous output rating of your generator Example Device to be Powered Greater of Starting Running Wattage Light Bulbs 10 75 watt 750 W Refrigerator...

Страница 13: ...erator 6 Grounding 7 Battery installation Each of these steps is discussed in detail below 1 Unpacking Delivery Inspection You should inspect the generator immediately after you receive delivery See t...

Страница 14: ...propane WARNING You must have the fuel line system installed by a certified gas technician for NG or LP NG LP Regulator Assembly Kit Set Up Regulator for Intended Gas Usage LP or NG Fuel selection is...

Страница 15: ...ied and installed by your gas utility technician at the time of fuel system hook up o If your standard delivery pressure is lower than 4 6 ounces per square inch 7 11 water column you will need change...

Страница 16: ...n below CAUTION Regardless of whether you use your generator as a back up power source connected to a building or as a portable power source you must not overload the generator Overloading may cause s...

Страница 17: ...ous section of this manual entitled Power Load Planning Management for more information on load application and selection Using as a Portable Power Source When using the generator as a portable power...

Страница 18: ...ver exceed the amperage rating of an outlet 2 Extension cords may be used to power devices that are located at a distance from the generator However use only UL listed outdoor rated grounded extension...

Страница 19: ...ing your generator to avoid equipment damage and or injury and possible death from carbon monoxide poisoning electric shock or fire Choose a site that meets all of the criteria specified Dry level sur...

Страница 20: ...ed flow of air to allow for proper cooling of engine and generator head WARNING Heat build up from inadequate ventilation can result in fire posing a serious risk to nearby persons and structures Situ...

Страница 21: ...familiar with its use Away from dust dirt Do not use the generator in extremely dusty or dirty conditions Excessive dust and dirt can cause premature failure of the machine Hearing protection Generat...

Страница 22: ...re from the clamp to the generator grounding post located on the electrical panel 4 Do not connect the generator grounding post to a water pipe or a ground used by a radio system If a licensed electri...

Страница 23: ...eral battery safety rules and instructions listed below General Battery Safety Rules ALWAYS use eye protection when handling batteries NEVER smoke or work near sparks or other sources of ignition NEVE...

Страница 24: ...t children operate Intended use Carefully read about and understand the intended use of this generator Do not use for other purposes as unforeseen hazards or equipment damage may result Under the infl...

Страница 25: ...ly shut down the source of electrical power If this is not possible attempt to free the victim from the live conductor Avoid direct contact with victim Use a nonconducting implement such as a dry rope...

Страница 26: ...uctions WARNING Burn hazard Never open oil port while engine is running Hot oil can spray over face and body Notes o Low oil shutdown feature prevents the generator from starting without sufficient oi...

Страница 27: ...oving the generator and on a regular basis thereafter This method will help you detect small leaks b Also beware of gas odor Both LP and NG have an odorant added rotten egg sulfur smell that will aid...

Страница 28: ...al WARNING Never open oil port while engine is running Hot oil can spray over face and body 4 Checking Generator Output Although the speed of the engine was carefully adjusted at the factory so that t...

Страница 29: ...you are using the generator o As a portable power source o Connected to a building as a back up power source WARNING Do not overload generator Make sure that combined starting and running loads do no...

Страница 30: ...3 If applicable shut off natural gas line valve Cool engine before storing Let engine cool for at least five minutes before storing A hot engine can be a fire hazard Choose a storage location Store t...

Страница 31: ...working condition Prepare engine for long term storage if needed If you will not be able to exercise the generator regularly you must prepare the engine for long term storage to prevent gum deposits...

Страница 32: ...safety glasses touch opposite terminals of the capacitor together with the tip of the screwdriver If there is stored charge in the capacitor a spark will be generated thereby discharging the capacitor...

Страница 33: ...acturer s service instructions Replace if damaged Keep generator clean Keep generator clean If dust or debris accumulates on the generator clean the generator with a damp cloth or soft bristle brush D...

Страница 34: ...qualified technician for adjustment Generator overheating a Generator is overloaded b Insufficient ventilation a Reduce the load See Power Load Planning Mgt section of this manual b Make sure there is...

Страница 35: ...and will also void the warranty Engine speed Never attempt to modify the engine speed setting The engine speed is preset at 3600 RPM for safe and optimal performance of the generator If speed needs a...

Страница 36: ...ectrical codes If the generator is not isolated from the utility power system by such means generator output will back feed into the utility power grid This may result in injury or death to utility po...

Страница 37: ...fter opening LP NG line supply smell for gas before starting engine If you do smell gas DO NOT start engine DO NOT light a match DO NOT flip on an electrical switch Exit area immediately and call gas...

Страница 38: ...ing Safety After use Cool engine before storing Let engine cool for at least five minutes before storing A hot engine can be a fire hazard Shut off fuel supply Turn off propane tank valve or shut NG l...

Страница 39: ...Generator Exploded View Rev A 39...

Страница 40: ...racket gen head 1 All 19 787371 Upper iso mount bracket gen head 1 All 20 790845 Base 1 All 21 82377 1 4 20 x 7 HHSC gr g zinc 2 All 22 777164 Battery cable positive 1 All 23 785609 Battery stop 1 All...

Страница 41: ...All 4 783053 NEMA 5 20 Receptacle 4 duplexes All 5 783091 30 AMP Circuit Breaker 2 All 6 783085 NEMA L5 30 Receptacle 1 All 7 31953 14 50 Receptacle 1 165956 8 783965 45 AMP Circuit Breaker 2 165956 9...

Страница 42: ...Generator Head Exploded View Rev A 42...

Страница 43: ...5 X 8 10mm Long 4 All 10 N A Rubber Cup 2 All 11 MA306403 Rear Bearing 1 All 12 MA306416 Nyloc Nut and Star Washer 1 All 13 MA30997 Grill 1 All 14 MA31065 Securing Stud Cap 1 All 15 MA30999 Fixing Rin...

Страница 44: ...ether a part is to be replaced or repaired is the sole decision of NorthStar NorthStar will not provide for replacement of complete products due to defective parts Any costs incurred due to replacemen...

Страница 45: ...45 This page left intentionally blank...

Страница 46: ...46 Assembled by Northern Tool Equipment Company Inc Burnsville MN 55306 NorthernTool com...

Отзывы: