GENERATOR FEATURES

References 1-3  Circuit Breakers.

    

Reference 1

 - two 50A push-to-reset circuit

breakers.

 

  Reference 2

 - one 30A push-to-reset circuit

breaker.

 

Reference 3

 - two 20A  push-to-reset  circuit

breakers.

References 4 - Warning Decals.  

Read and

follow all warnings.

References 5 - 1 3/8” Diameter 6 Spline Input

Shaft.

  540 RPM.  PTO driveline is available from

Northern, Item #165936.

References 6 -  Oil Drain Plug.  

Change oil

after the first 50 hours of use, then after every  500
hours.

References 7 - Voltmeter.

 Voltmeter  needle

should be in green area during  all  generator  load
conditions.  The black line in the center on the
green area indicates 120V.  During no load
conditions, the needle should be at or above the
black line.

References 8-9  120V Receptacles.

 

Reference 8 - 120V Receptacle.  

The

generator has a control panel with two 120V 20A
straight blade receptacle duplexes (two receptacles
in a common housing). National Electrical
Manufacturer’s Association (NEMA) number is 5-
20R.

 

Reference 9 - 

This twistlock receptacle is a

120V 30A receptacle, NEMA number  L5-30R.    This

receptacle accepts NEMA plug number L5-30P,
which is supplied with the generator.

Reference 10 - 120/240V Receptacle.  

This

straight blade receptacle is 120/240V  50A.    This
receptacle accepts a NEMA plug number 14-50P.

ALWAYS

 use grounded male plugs.    The

neutral line of the generator is mechanically
grounded to the frame.  Matching NEMA male
plugs must always be used.

References 11 - Shield.  

Plastic implement

shield.   

NEVER

 operate generator without shield  in

place.

Reference 12 - Gear Box.  

Cast iron frame. 1:7

gear ratio.

Reference 13 - Grounding Screw .  

Ground the

generator via the ground screw, to  a  copper  pipe  or
rod that is driven into moist soil.

Reference 14 - Mounting Holes.  

Use these

three locations to mount the  generator  head  in
place with 7/16” grade 5 bolts.    Mounting  plates
(item #165935) for mounting generator to a  cement
pad are available through  Northern  and  the
NorthStar parts catalog.

Reference 15 - Fan  Vents.   

Never block the

vent slots or insert objects through the slots.  The
closest object should be at least  3  feet  away  from
the vents.

Reference 16 - Oil Lev el Sight.  

When oil is

even with the red dot, the oil level is correct.   Check
oil level daily.  Sight is mounted on  the  gear  box
service panel.  If panel is removed for whatever
reason, reseal using Dow Corning sealant #732.

Figure 2  

(Ref. 10-16) 

00295

Содержание 13000 PTOG

Страница 1: ...DEL 13000 PTOG ITEM 165929 Power Take Off Generator M165929A OWNER S MANUAL 13000 PTOG Any Questions Comments or Problems Call Customer Service at 1 800 270 0810 Hours Monday Friday 7 30 AM to 5 30 PM...

Страница 2: ...Generator IMPORTANT If this machine is used by anyone who is not the owner or is loaned or rented make certain the operator Is instructed in safe and proper operation of this machine Reads and underst...

Страница 3: ...40 Amp A thermal push to reset style Gear Box Gear Ratio 1 7 Gear Oil SAE 80W 90 Oil Capacity 86 Qt 82 L Dimensions Length 28 38 72 1 cm Width 14 25 36 2 cm Height 12 50 31 1 cm Gross Weight 127 lb 57...

Страница 4: ...0A Circuit Breaker 11 Shield 3 20A Circuit Breakers 12 Gear Box 4 Warning Decals 13 Grounding Screw 5 1 3 8 6 Spline Input Shaft 14 Mounting Holes 6 Oil Drain Plug 15 Fan Vents 7 Voltmeter 16 Oil Leve...

Страница 5: ...EMA plug number L5 30P which is supplied with the generator Reference 10 120 240V Receptacle This straight blade receptacle is 120 240V 50A This receptacle accepts a NEMA plug number 14 50P ALWAYS use...

Страница 6: ...r highly electrical conductive areas and on construction job sites to prevent electric shock ALWAYS remove PTO driveline before working on the generator ALWAYS provide adequate ventilation Do not oper...

Страница 7: ...oncrete After the the generator is firmly mounted attach the PTO driveline to the generator then the tractor Use a synchronized PTO driveline rated at 24 HP minimum DANGER Always have proper guarding...

Страница 8: ...tors particularly low cost split phase motors are very hard to start and require 5 to 7 times more current to start than to run Capacitor motors are easier to start and usually require 2 to 4 times as...

Страница 9: ...Compressor 1 2 HP 1400 a Curling Iron 700 Dishwasher 1200 Edge Trimmer 500 Electric Nail Gun 1200 Electric Range one element 1500 Electric Skillet 1250 Freezer 800 b Furnace Fan 1 3 HP 1200 a Hair Dry...

Страница 10: ...ch or a stop watch the clock should be correct within 2 seconds per minute All speed setting adjustments should be done by a qualified technician GENERATOR CARE The generator head is a two pole 3600 R...

Страница 11: ...loose wire c Defective receptacle d Defective stator e Defective rotor f Defective capacitor g Defective circuit breaker h Engine speed too slow I PTO not engaged j Gear box is malfunctioning a Disco...

Отзывы: