Refrigerant pipe installation
Installation
97
5 Refrigerant pipe installation
5.1 Maximum pipe length and height drop
Considering the allowable pipe length and height drop to decide the installation position. Make sure the
distance and height drop between indoor and outdoor unit not exceeded the date in the following table.
Model
Max. Length
Max. Elevation
12,000Btu/h 25m 10m
18,000Btu/h 30m 20m
24,000Btu/h
50m
25m
36,000Btu/h-48,000Btu/h 65m
30m
5.2 The procedure of connecting pipes
5.2.1 Choose the pipe size according to the specification table.
5.2.2 Confirm the cross way of the pipes.
5.2.3 Measure the necessary pipe length.
5.2.4 Cut the selected pipe with pipe cutter
Make the section flat and smooth.
90
Lean
Crude
Burr
o
5.2.5 Insulate the copper pipe
Before test operation, the joint parts should not be heat insulated.
5.2.6 Flare the pipe
Insert a flare nut into the pipe before flaring the pipe
According to the following table to flare the pipe
Pipe diameter
Flare dimension A (mm)
Flare shape
Min Max
1/4" (6.35)
8.3
8.7
R0.4~0.8
A
45°
90
°
4
-+
3/8" (9.52)
12.0
12.4
1/2" (12.7)
15.4
15.8
5/8" (15.9)
18.6
19.1
3/4" (19)
22.9
23.3
After flared the pipe, the opening part must be seal by end cover or adhesive tape to avoid duct or
exogenous impurity come into the pipe.
5.2.7 Drill holes if the pipes need to pass the wall.
5.2.8 According to the field condition to bend the pipes so that it can pass the wall smoothly.
5.2.9 Bind and wrap the wire together with the insulated pipe if necessary.
Содержание MOC-12HFN1-MS0W
Страница 2: ......
Страница 4: ......
Страница 19: ...Service Space Indoor Units 15 4 Service Space ...
Страница 20: ...Wiring Diagrams 16 Indoor Units 5 Wiring Diagrams MCA2U 12HRFN1 M MCA2U 18HRFN1 M MCA2U 12HRFN1 M B ...
Страница 21: ...Wiring Diagrams Indoor Units 17 MCD 24HRFN1 M MCD 36HRFN1 M MCD 48HRFN1 M MCD 24HRFN1 MW ...
Страница 32: ...Wiring Diagrams 28 Indoor Units 4 Wiring Diagrams MTBU 12HRDN1 M MTBU 18HRDN1 M MTBU 12HRDN1 M B ...
Страница 33: ...Wiring Diagrams Indoor Units 29 MTB 24HRFN1 MW ...
Страница 34: ...Wiring Diagrams 30 Indoor Units MTB 24HRFN1 M MTB 36HWFN1 M MTB 48HWFN1 M ...
Страница 48: ...Service Space 44 Indoor Units 3 Service Space 12K 18K C 35mm 35mm 35mm 1000mm 24K 48K ...
Страница 50: ...Wiring Diagrams 46 Indoor Units MUE 24HRFN1 M MUE 36HRFN1 M MUE 48HRFN1 M ...
Страница 57: ...Dimensions Indoor Units 53 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Страница 58: ...Service Space 54 Indoor Units 3 Service Space ...
Страница 59: ...Wiring Diagrams Indoor Units 55 4 Wiring Diagrams MFAU 12HRFN1 M MFAU 12HRFN1 M B ...
Страница 63: ...Field Wiring Indoor Units 59 9 Field Wiring MFAU 12HRFN1 M MFAU 12HRFN1 M B ...
Страница 66: ...Dimensions 62 Outdoor Units Model Unit mm A B C D E F H MOU 48HFN1 M 938 634 404 448 370 392 1369 ...
Страница 70: ...Wiring Diagrams 66 Outdoor Units 4 Wiring Diagrams MOC 12HFN1 MV0W ...
Страница 71: ...Wiring Diagrams Outdoor Units 67 MOZ 12HFN1 MW0W ...
Страница 72: ...Wiring Diagrams 68 Outdoor Units MOC 12HFN1 MS0W MOF 18HFN1 MS0W MOF 18HFN1 MU0W ...
Страница 73: ...Wiring Diagrams Outdoor Units 69 MOU 24HFN1 M ...
Страница 74: ...Wiring Diagrams 70 Outdoor Units MOG 24HFN1 MT0W ...
Страница 75: ...Wiring Diagrams Outdoor Units 71 MOU 36HFN1 M MOU 48HFN1 M ...
Страница 100: ...Indoor unit installation 96 Installation ...
Страница 138: ...Troubleshooting 134 Electrical Control System 2 4 4 5 E3 malfunction ...
Страница 143: ...Troubleshooting Electrical Control System 139 2 4 4 10 P1 malfunction Only for 36K 48K ...
Страница 149: ...Troubleshooting Electrical Control System 145 2 4 4 16 P7 malfunction ...