DC Inverter Multi VRF System
24
1.Real
line
method;
2.
Broken line method. Please select it based on the installation requirements.
There are two wiring diagrams for power cord:
1.Real line method;
2. Broken line method. Please select it based on the installation requirements.
(3) Selection of air switch and power cord:
Model
Power supply
Max Fuse
Size/Fusible
Max.
(A)
Max Ckt, Bkr
Size/Disjoncteur Max.
(A)
Min. Circuit Ampacity
(A)
V5BV-36WMAK
208/230V~ 60Hz
50
50
32
V5BV-48WMAK
208/230V~ 60Hz
60
60
37
V5BV-60WMAK
208/230V~ 60Hz
70
70
42
(1) Selection of circuit breake
r and power cord in the above table is based upon unit’s maximum power
(maximum current).
(2) Specification of power cord is based on the working condition where ambient temperature is 40
ć
(104
̧
) and
multi-core copper cable (working temperature is 90
ć
(194
̧
), e.g. power cable with YJV cross-linked copper,
insulated PE and PVC sheath) is lying on the surface of slot. If working condition changes, please adjust the
specification according to national standard.
(3) Specification of circuit breaker is based on the working condition where ambient temperature of circuit
breaker is 40
ć
(104
̧
). If working condition changes, please adjust the specification according to national
standard.