11

over the combustion air intake opening. The screens hole 

size must be large enough to prevent air restriction.

Existing Installations

 When an existing furnace is removed from a vent system 

serving other appliances, the existing vent system may not be 

sized properly to vent the remaining appliances (For example: 

water heater). An improperly sized venting system can result 

in the formation of condensate, leakage, or spillage. The 

existing vent system should be checked to make sure it is in 

compliance with NFGC and must be brought into compliance 

before installing the furnace.

NOTE:

 If replacing an existing furnace, it is possible you will 

encounter an existing plastic venting system that is subject 

to a Consumer Product Safety Commission recall. The pipes 

involved in the recall are High Temperature Plastic Vent 

(HTPV). 

If your venting system contains these pipes

 

DO 

NOT reuse this venting system!

 This recall does not apply 

to other plastic vent pipes, such as white PVC or CPVC. 

Check for details on the CPSC website or call their toll-free 

number (800) 758-3688.

Condensate Disposal

The method for disposing of condensate varies according 

to local codes. Consult your local code or authority having 

jurisdiction. Neutralizer kit P/N 902377 is available for use 

with this furnace. 

Please follow the instructions provided 

with the kit.

This furnace has multiple options for positioning the vent 

pipe as described in the, Vent and Inducer Assembly Options 

section (

page 13

). Each of the condensate drain lines must 

be J-trapped using field supplied parts. After the condensate 

lines are J-trapped, they may be combined together when 

routed to the drain.
For Installations where there is limited clearance for the 

J-Trap (such as an attic where it may be installed between 

ceiling joists), either side of the J-Trap can be shortened to 

a minimum of 3 Inches. See 

Figure 11 (page 13)

.

CIRCULATING AIR REQUIREMENTS

each other are shown in 

Figure 10

. The roof penetration must 

be properly flashed and waterproofed with a plumbing roof 

boot or equivalent flashing. Vent and combustion air piping 

may be installed in an existing chimney which is not in use 

provided that:
•  Both the exhaust vent and air intake run the length of the 

chimney.

•  The top of the chimney is sealed and weatherproofed.

• The termination clearances shown in 

Figure 10

 are 

maintained.

• No other gas fired or fuel-burning equipment is vented 

through the chimney.

Vent Freezing Protection

 CAUTION:

When the vent pipe is exposed to temperatures 

below freezing (i.e., when it passes through 

unheated spaces, chimneys, etc.) the pipe 

must be insulated with 1/2 inch thick sponge 

rubber insulation, Armaflex-type insulation or 

equivalent. Insulating pipe is important to avoid 

condensate icing.

• 

Table 2

 lists the maximum length of flue pipe that can 

travel through an unconditioned space or an exterior 

space. The total vent length must not exceed the lengths 

noted in 

Table 1 (page 9)

.

• For extremely cold climates or for conditions of short 

furnace cycles (i.e. set back thermostat conditions) 

the last 18 inches of vent pipe can be reduced. It is 

acceptable to reduce from 3” to 2-1/2”, 3” to 2”, or 2” to 

1-1/2” if the total vent length is at least 15 feet in length, 

and the vent length is within the parameters specified in 

Table 1

. The restriction should be counted as 3 equivalent 

feet. Smaller vent pipes are less susceptible to freezing, 

but must not be excessively restrictive. The length of the 

2 inch pipe must not be longer than 18 inches.

•  If furnace is installed horiziontally, make sure the drainage 

port on the in-line drain assembly is pointed downward 

to ensure proper drainage of condensate. See 

Figure 28 

(page 42)

 & 

Figure 29 (page 43)

.

• To prevent debris or creatures from entering the 

combustion system, a protective screen may be installed 

Figure 10. Vertical Vent Termination

Comb

ustion Air

Exhaust 

V

ent

12” Above Maximum

Expected Snow Level

(Both pipes)

Elbows on the combustion air 

inlet must be positioned pointing

 away from the exhaust vent.

8" Min.
36" Max.

Plumbing Vent Roof Boot

(Both Pipes)

WINTER DESIGN

TEMPERATURE

MAXIMUM FLUE PIPE LENGTH (FEET)

IN UNCONDITIONED & EXTERIOR SPACES

WITHOUT INSULATION

WITH INSULATION*

20

45

70

0

20

70

-20

10

60

*NOTE:

 Insulation thickness greater than 3/8 inch, based on an R value 

of 3.5 (ft x F x hr) / (BTU x in.)

Table 2. Vent Protection

Содержание SD Ultra Low Nox Series

Страница 1: ...asoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use...

Страница 2: ...Pressure Switch Location 14 Accessories 15 Finish Flange 15 Rubber Grommets 15 PVC Components 15 Typical Orientation 15 Alternate Orientation 16 Optional PVC Pipe Installation 16 Condensate Drain Line...

Страница 3: ...tallation service and operation of this furnace Failure to follow safety recommendations could result in possible damage to the equipment serious personal injury or death This furnace must be installe...

Страница 4: ...ping Gas Pipe Pressure Testing US NFGC and National Plumbing Codes General Installation US Current edition of the NFGC and the NFPA 90B For copies contact the National Fire Protection Association Inc...

Страница 5: ...36 in Figure 1 Minimum Clearances to Combustible Materials COMBUSTION AIR VENTING REQUIREMENTS WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance c...

Страница 6: ...hat force air from the house to the outdoors can create a negative pressure inside the house resulting in improper furnace operationorunsafeconditionssuchasflameroll out It is imperative that sufficie...

Страница 7: ...ces crawl or attic that freely exchange with the outdoors See Figure 3 Figure 3 Combustion Air Drawn from a Crawl Space or Vented Attic TOTAL INPUT RATING BTUH MINIMUM FREE AREA EACH OPENING ROUND DUC...

Страница 8: ...which draw combustion air from that space In general a furnace installed in an unconfined space will not requireoutsideairforcombustion However inhomesbuiltfor energy efficiency low air change rates...

Страница 9: ...ft for each additional 2 inch short radius elbow 3 5 ft for each additional 3 inch long radius elbow and 7 ft for each additional 3 inch short radius elbow Subtract 5 ft for each 2 tee and 8 ft for e...

Страница 10: ...g horizontally a side wall vent kit is available according to the pipe diameter size of the installation For 2 inch pipe use side wall vent kit 904617 and for 3 inch pipe use kit 904347 Please follow...

Страница 11: ...ustion air piping may be installed in an existing chimney which is not in use provided that Both the exhaust vent and air intake run the length of the chimney The top of the chimney is sealed and weat...

Страница 12: ...and condensing on the heat exchanger If a manually operated damper is installed it must be designed so that operation of the furnace is prevented when the damper is in the cooling position and operat...

Страница 13: ...any combustible material other than wood flooring SD series gas furnaces are shipped with the bottom panel installed as shown in Figure 23 page 31 If the furnace is installed with only side return air...

Страница 14: ...he left or right side of the furnace use the extra screw provided in the parts package 6 Remove the cabinet plug from side of furnace and reinstall in hole on opposite side of cabinet 7 Install in lin...

Страница 15: ...m the top to the bottom section of the cabinet or open grommet holes in the cabinet PVC Components IMPORTANT NOTES Before permanently installing these components it is recommended you dry fit them fir...

Страница 16: ...retighten the clamp It is permissible to locate the trap away from the furnace The condensate drain system J trap and drain tube should be no more than 30 equivalent feet while maintaining 1 4 per foo...

Страница 17: ...building immediately Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department All gas piping mus...

Страница 18: ...y omitted for clarity of pipe installation Gas Valve See Note B See Note A Plug Flexible Gas Line Flexible Gas Line FURNACE INPUT MAIN BURNER ORIFICE SIZE MAIN AIR ORIFICE DIAMETER MANIFOLD PRESSURE 5...

Страница 19: ...page 36 Figure 25 page 37 or the unit wiring label IMPORTANT NOTES An electrical disconnect must be installed readily accessible from and located within sight of the furnace See Figure 24 page 36 or...

Страница 20: ...k White Black White START UP ADJUSTMENTS Pre Start Check List Verify the polarity of the connections are correct the line voltage power leads are securely connected and the furnace is properly grounde...

Страница 21: ...possible The thermometer on the supply air side must be shielded from direct radiation from the heat exchanger to avoid false readings 2 Adjustallregistersandductdamperstothedesiredposition and run t...

Страница 22: ...ower motor is running tP is displayed following with the Tap number For instance If the blower motor has been set for Tap 4 tP4 will be displayed Ifanalarmisdetected theerrorcodedisdisplayedstarting w...

Страница 23: ...3 digit display will show 1dL which means idle Press the MENU button the control will show the options on the display Keep pressing the MENU button the options are Err L6F Cr Cod OdU HOd COF COP HtP...

Страница 24: ...36 and Figure 25 page 37 Heating Cycle 1 ThethermostatcallsforheatbyenergizingtheWterminal with 24VAC 2 The control checks the HLI input for a closed limit 3 The control performs a circuitry check an...

Страница 25: ...eady for the next call Cooling Cycle When Y1 and G or Y1 Y2 and G signals are detected the control will operate in compressor cooling mode The Electronic Air Cleaner EAC relay will energize 5 seconds...

Страница 26: ...be inspected and cleaned if required by a qualified service technician annually to ensure continued safe operation Pay attentiontoanydeteriorationfromcorrosionorothersources WARNING Holes in the vent...

Страница 27: ...ce the recycle count will start over Internal Control Fault E2 3 Internal relay in the control board has failed Replace the board Control senses 24V output to the gas valve If voltage is not sensed to...

Страница 28: ...2 Measure the pressure If the pressure is as expected replacethepressuretransducer There should not be measurable amount of pressure when furnace is idle Atacallforheatthecontrolmonitorsthepressure se...

Страница 29: ...s stuck on the board Replace the board The control senses 24V output from internal relays at all times If power is detected at the HLO output on the 12 pin plug at any time even without a call for hea...

Страница 30: ...nsate Drain Switch The Condensate Drain Switch will shut down the furnace if the condensate drain from the Collector Pan becomes clogged BlowerLimitSwitch Preventsoperationoftheblowermotor when the bl...

Страница 31: ...TTOM VIEW TOP VIEW 4 Knockouts both sides 1 LEFT SIDE RIGHT SIDE 3 1 4 Gas 1 5 8 T stat 7 8 Electric 7 8 Vent pipe 3 Cond 1 1 16 T stat 7 8 Electric 7 8 Gas 1 5 8 Condensate 1 1 16 Vent pipe 3 Combust...

Страница 32: ...0 5 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE 050U T23A 50 000 BTU Hr Input 50 000 Btuh Input Btuh Output Bottom Tap 9 Tap 8 Tap 7 Tap 6 Tap 5 970 45 935 47 915 48 880 50 845 52 Tap 4 875 50 835 53...

Страница 33: ...50 1 315 1 285 1 255 1 225 1 200 Tap 8 1 290 1 260 1 230 1 195 1 160 1 135 1 100 1 070 Tap 7 1 145 1 115 1 090 1 055 1 030 995 960 920 Tap 6 1 045 1 015 980 950 920 885 855 825 Tap 5 935 915 880 845 8...

Страница 34: ...0 Btuh Input 95 000 Btuh Output Bottom Only 9 8 7 6 1 850 48 1 790 49 1 745 50 1 700 52 1 650 53 5 1 745 50 1 690 52 1 645 53 1 590 55 1 535 57 4 1 480 59 1 420 62 1 360 65 3 2 1 Side Only 9 8 7 6 1 7...

Страница 35: ...95 1 015 945 870 790 715 665 615 1 980 905 835 740 665 590 525 440 Bottom Side 9 2 245 2 195 2 155 2 095 2 065 2 070 2 015 1 950 8 2 080 2 030 1 980 1 930 1 880 1 820 1 765 1 705 7 1 915 1 875 1 820 1...

Страница 36: ...GROUND TO CHASSIS TO CHASSIS Refer to the Installation Instructions provided with the furnace for the proper heating and cooling speeds for your application Refer to the Installation Instructions for...

Страница 37: ...R TWIN W2 W1 B C Y2 GND Y1 O R G PRESSURE TRANSDUCER GND P1 5V INDUCER PRESSURE SWITCH 1 INDUCER PRESSURE SWITCH 2 COLLECTOR SWITCH PS2 PS1 PS0 MVC HLI ILI HLO MVL GND 5A FUSE K4 TR TH K2 GAS VALVE FL...

Страница 38: ...88 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 164 327 112 32 161 321 114 32 158 316 116 31 155 310 118 31 153 305 120 30 150 300 CAPACITY OF BL...

Страница 39: ...tended above meter regulator assembly I Clearance to service regulator vent outlet J Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 6 inche...

Страница 40: ...st slope upward 1 4 per foot 5 7 90 Elbows 90 Elbow COMBUSTION AIR Straps or other suitable supports at minimum 5 ft intervals both pipes 90 Elbows Flue Pipe must slope upward 1 4 per foot First suppo...

Страница 41: ...E 2 Inline Drain Field Supplied See NOTES 2 3 Collector Box Drain Factory Equipped See NOTE 2 X See NOTE 5 X See NOTE 5 FLUE PIPE X See NOTE 5 X See NOTE 5 FLUE PIPE Inline Drain Tube Factory Supplied...

Страница 42: ...IGHT 1 PIPE OPTIONS Plug VIEW D VIEW E VIEW F VIEW G COMBUSTION AIR FLUE PIPE OPTION 7 OPTION 8 COMBUSTION AIR Rubber Grommet See VIEW D for drain line positions See VIEW E for drain line positions Pl...

Страница 43: ...d See NOTES 2 3 Collector Box Drain Factory Equipped See NOTE 2 Inline Drain Field Supplied See NOTES 2 3 Field Supplied Drain Line Attached to PVC Trap Do Not Trap COMBUSTION AIR FLUE PIPE Flange COM...

Страница 44: ...ft Installation Inducer Vertical Horizontal Left Installation Inducer Rotated Left Horizontal Right Installation Inducer Vertical Horizontal Right Installation Inducer Rotated Right Alternate Location...

Страница 45: ...lation Inducer Vertical Horizontal Left Installation Inducer Rotated Left Horizontal Right Installation Inducer Vertical Horizontal Right Installation Inducer Rotated Right Alternate Locations Alterna...

Страница 46: ...46...

Страница 47: ...47...

Страница 48: ...instructing the customer on how to operate and maintain the equipment for the life of the product Safety should always be the deciding factor when installing this product and using common sense plays...

Отзывы: