background image

6

Figure 2. Panel Removal

DETAIL A

DETAIL B

Figure 3. Panel Installation

AIR CONDITIONER MAINTENANCE

 WARNING:

To prevent electrical shock, personal injury, or 

death, disconnect all electrical power to the unit 

before performing any maintenance or service. 

The unit may have more than one electrical supply.

Proper maintenance is important to achieve optimum 

performance from the air conditioner. The ability to properly 

perform maintenance on this equipment requires certain 

mechanical skills and tools. If you do not possess these 

skills, contact your dealer for maintenance. Consult your 

local dealer about the availability of maintenance contracts. 

Routine maintenance should include the following:

•  Inspect and clean or replace air filters at the beginning of 

each heating and cooling season, or more frequently if 

required.

•  Inspect the condensate drains in the unit's basepan and 

the outdoor coil at the beginning of each cooling season. 

Remove any debris. Clean the outdoor coil and louvers 

as necessary using a mild detergent and water. Rinse 

thoroughly with water.

•  To access the outdoor coil on units equipped with louvered 

panels, refer to 

Figure 2, (page 6)

 for panel removal 

and 

Figure 3, (page 6)

 for panel installation.

• Inspect the electrical connections for tightness at the 

beginning of each heating and cooling season. Service 

as necessary.

•  Do not attempt to add additional oil or grease to motors 

unequipped with oil tubes or grease fittings.  Most outdoor 

unit motors are manufactured with sealed, permanently 

lubricated bearings that are designed for the life of the 

equipment without maintenance.

•  The compressor is hermetically sealed and shipped from 

the factory with the proper oil charge for most installations.  

Lubricating oil should only be added by trained personnel 

and is typically only required for long line-sets or tall riser 

applications.

Panel Removal

1. Remove screws securing the panel.

2. Slide the panel up towards the top pan in order to clear 

the bottom flange from the base pan. See 

Figure 2

.

3. Swing the bottom of the panel out and pull the panel down 

to remove it from the unit.

Panel Installation

1. Insert the top corners of side panel flanges into the corner 

post channels as shown in Detail A in 

Figure 3

.

2. Slide the panel up into the top pan. (You may need to push 

on the center of the panel at the top in order to clear the 

top pan edge).

3. Swing the panel in and push down until the panel is resting 

on the top edge of the base pan wall as shown in Detail 

B.

4. Insert screws into the panel to secure it to the unit.

Содержание SA3BF4M2SN Series

Страница 1: ...llation Return these instructions to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE INSTALLATION INSTRUCTIONS IMPORTANT SAFETY INFORMATION 2 AIR CONDITIONER INSTALLATION 2 General Information 2 Before You Install this Unit 2 Packaging Removal 3 Locating the Air Conditioner 3 Clearance Requirements 3 Ground Installations 3 ...

Страница 2: ...ions Consult local building codes and the National Electrical Code ANSI for special installation requirements All electrical wiring must be completed in accordance with local state and national codes and regulations and with the National Electric Code ANSI NFPA 70 or in Canada the Canadian Electric Code Part 1 CSA C 22 1 This equipment contains liquid and gaseous refrigerant underhighpressure DONO...

Страница 3: ...learancefortheserviceaccesssidetotheunit sservice panel Forinstallationsthatarespaceconstrained onesideofthe unit adjacent to the service panel may have its air side clearance reduced to a minimum of 6 inches The other side adjacent to the service panel requires 24 inches for service access The remaining two sides at a minimum shall require 12 inches of clearance A minimum of 18 inches between two...

Страница 4: ...panel and sized as shown on the unit rating label and according to applicable local codes See the unit rating plate for minimum circuit ampacity MCA and maximum overcurrent protection MOP limits CAUTION When performing brazing operations always protect the system components and seals from the possibility of heat damage Remove all caps plugs and Schrader valve cores on piping system components just...

Страница 5: ...y branch circuits for both the indoor and outdoor equipment is the proper voltage for the equipment and that the overcurrent protection device is properly sized and that the supply wiring is the correct gauge Verifythatthelowvoltageandthermostatwiringaresecurely connected to the proper terminals for all equipment Verify that the low voltage transformer has been properly connected with that unit s ...

Страница 6: ... and Figure 3 page 6 for panel installation Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary Do not attempt to add additional oil or grease to motors unequipped with oil tubes or grease fittings Most outdoor unit motors are manufactured with sealed permanently lubricated bearings that are designed for the life of the equipmen...

Страница 7: ...s perform the following steps 1 Determinetherecommendedchargeaddition ifapplicable for the system being installed This information is in the unit s QRD Quick Reference Data sheet 2 Calculate the amount of additional refrigerant needed for thelinesetlengthoftheactualinstallation Thisinformation is on the first page of the unit s QRD Quick Reference Data sheet 3 Weigh in the additional charge amount...

Страница 8: ...see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Caution The low voltage wiring should not be grounded to this unit 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 volt a la terre 103...

Страница 9: ...Phase 60 Hz WIRING DIAGRAM 10398310 Replaces 7110150 7 21 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE BLACK BLUE YELLOW BLUE BLACK 208 230V H C F CCH R C S S C H L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR FAN MOTOR L FAN RELAY CC OFR NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 volts to ground 4 For rep...

Страница 10: ...Split System Air Conditioner Outdoor Section With ECM Outdoor Motor Single Phase 60 Hz NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 ci...

Страница 11: ...11 ...

Страница 12: ...d serial number of the unit when ordering replacement parts ELECTRICAL Capacitors Temperature Limit Switches Compressors Thermostats Contactors Time Delay Relays Pressure Switches Transformers Relays MOTORS Blower Motor Fan Motor COMPONENTS Blower Assembly Fan Grille Cabinet Panels Filter Driers Expansion Valves Specifications illustrationssubjecttochangewithoutnoticeorincurringobligations 07 22 O...

Отзывы: