background image

6

START UP & ADJUSTMENTS

Pre-Start Check List

  Verify the indoor unit is level and allows proper condensate 

drainage.

  Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/control 

panels are in place.

  Verify air filters are cleaned and properly installed.

  Verify duct work is sealed to prevent air leakage. 

  Verify line voltage power leads are securely connected 

and the unit is properly grounded.

  Verify low voltage wires are securely connected to the 

correct leads on the low voltage terminal strip.

  Verify power supply branch circuit overcurrent protection 

is sized properly.

  Verify the thermostat is wired correctly.

Start-Up Procedures

The thermostat's function mode should be set to OFF and 

the fan mode should be set to AUTO. Close all electrical 

disconnects to energize the sy stem.

Air Circulation - Indoor Blower

1.  Set the thermostat system mode on OFF and the fan mode 

to ON.

2.  Verify the blower runs continuously. Check the air delivery 

at the supply registers and adjust register openings for 

balanced air distribution. If insufficient air is detected, 

examine ductwork for leaks or obstructions.

3.  Set the thermostat fan mode to AUTO and verify the blower 

stops running.

System Cooling

1. Set the thermostat’s system mode to COOL and the 

fan mode to AUTO. Gradually lower the thermostat 

temperature setpoint below room temperature and verify 

the outdoor unit and indoor blower energize.

2. Verify blower wheel is spinning in direction indicated by 

arrow. Feel the air being circulated by the indoor blower 

and verify that it is cooler than ambient temperature. Listen 

for any unusual noises. If unusual sounds occur, determine 

the source of the noise and correct as necessary.

3. Verify HI and LO refrigerant pressures.

4. Allow the system to operate for several minutes and then 

set the temperature selector above room temperature. 

Verify the fan and compressor cycle off with the thermostat. 

NOTE:

 The blower should also stop unless fan mode is 

set to the ON position.

System Heating (optional)

1. Set the thermostat's system mode to HEAT and the 

temperature mode above room temperature.

2. Verify the optional heating equipment (furnace or electric 

heat) and indoor blower energize. Feel the air being 

circulated by the indoor blower and verify that it is warmer 

than ambient temperature. Listen for any unusual noises. 

If unusual sounds occur, determine the source of the noise 

and correct as necessary.

AIR CONDITIONER MAINTENANCE

 WARNING:

To prevent electrical shock, personal injury, or 

death, disconnect all electrical power to the unit 

before performing any maintenance or service. 

The unit may have more than one electrical supply.

Proper maintenance is important to achieve optimum 

performance from the air conditioner. The ability to properly 

perform maintenance on this equipment requires certain 

mechanical skills and tools. If you do not possess these 

skills, contact your dealer for maintenance. Consult your 

local dealer about the availability of maintenance contracts. 

Routine maintenance should include the following:

•  Inspect and clean or replace air filters at the beginning 

of each heating and cooling season, or more frequently 

if required.

•  Inspect the condensate drain and outdoor coil at the 

beginning of each cooling season. Remove any debris. 

Clean the outdoor coil and louvers as necessary using a 

mild detergent and water. Rinse thoroughly with water.

•  Inspect the electrical connections for tightness at the 

beginning of each heating and cooling season. Service 

as necessary.

•  To access the internal compnents of the unit, refer to 

Figure 

4

 for panel removal and 

Figure 5

 for panel installation.

 CAUTION:

The unit should never be operated without a 

filter in the return air system. Replace disposable 

filters with the same type and size.

•  Do not attempt to add additional oil to motors unequipped 

with oil tubes. The compressor is hermetically sealed at 

the factory and does not require lubrication.

•  To access the internal compnents of the unit, refer to 

Figure 

4

 for panel removal and 

Figure 5

 for panel installation.

Panel Removal

1. Remove screws securing the panel.

2. Slide the panel up towards the top pan in order to clear 

the bottom flange from the base pan. See 

Figure 4

.

3.  Swing the bottom of the panel out and pull the panel down 

to remove it from the unit.

Panel Installation

1.  Insert the top corners of side panel flanges into the corner 

post channels as shown in Detail A in 

Figure 5

.

2.  Slide the panel up into the top pan. (You may need to push 

on the center of the panel at the top in order to clear the 

top pan edge).

3.  Swing the panel in and push down until the panel is resting 

on the top edge of the base pan wall as shown in Detail 

B.

4. Insert screws into the panel to secure it to the unit.

Содержание SA1BF4M2SN Series

Страница 1: ...IMPORTANT SAFETY INFORMATION 2 AIR CONDITIONER INSTALLATION 3 General Information 3 Before You Install this Unit 3 Locating the Air Conditioner 3 Packaging Removal 3 Ground Level 3 Roof Mount 3 Connec...

Страница 2: ...nt Refrigerant and electrical line should be routed through suitably waterproofed openings to prevent water from leaking into the structure This unit is designed for outdoor installations only and sho...

Страница 3: ...n 18 inches from the outside walls of the facility and in an area free from overhead obstructions to ensure unrestricted airflow through the outdoor unit Sufficient clearance for unobstructed airflow...

Страница 4: ...for loose connections Line Voltage A wiring diagram is located on the inside cover of the electrical box of the outdoor unit The installer should become familiar with the wiring diagram before making...

Страница 5: ...instructions supplied with the thermostat and the indoor equipment Typical AC and thermostat hookups are shown in Figure 3 The outdoor unit is designed to operate from a 24 VAC Class II control circu...

Страница 6: ...ify that it is warmer than ambient temperature Listen for any unusual noises Ifunusualsoundsoccur determinethesourceofthenoise and correct as necessary AIR CONDITIONER MAINTENANCE WARNING To prevent e...

Страница 7: ...unit Use only gage line sets which have a Schrader depression device present to actuate the valve Ahigh pressureswitchisfactory installedandlocatedinthe liquidlineinternaltotheoutdoorunit Theswitchis...

Страница 8: ...the recommended superheat value in the table then ADD refrigerant For TXV systems If your measured subcooling at the liquid valve is LESS THAN the recommended subcooling value in the table then ADD re...

Страница 9: ...uitable for 105 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and opti...

Страница 10: ...R L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR OUTDOOR FAN MOTOR Y2 Y L R C P DC SOL CSC C R Y2 Y LPS HPS CORESENSE COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC Contactor Coil CCH Crankcase He...

Страница 11: ...0 Hz WIRING DIAGRAM 7110150 1209 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE BLACK BLUE YELLOW BLUE BLACK 208 230V H C F CCH R C S S C H L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR FAN MOTOR L FAN REL...

Страница 12: ...e unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avant de faire...

Страница 13: ...HPS COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC 208 230V Two Stage Split System Air Conditioner Outdoor Section With ECM Outdoor Motor Single Phase 60 Hz NOTES 1 Disconnect all power before...

Страница 14: ...rcuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avant de faire letretien 8 Employez uniquement des conducteurs en cui...

Страница 15: ...m 6 Thermostat is malfunctioning Check thermostat sub base or wiring for short circuit Check thermostat installation location level Yellow ALERT Flash Code 2 Compressor Pressure Trip High Refrigerant...

Страница 16: ...ssor bearings are seized Measure compressor oil level Red LOCKOUT Flash Code 5 Yellow Off Compressor Moderate Run Trip 1 Evaporator blower is not running Check blower relay coil and contacts Check blo...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...allon MO Nortek Global HVAC LLC 2018 All Rights Reserved REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when or...

Отзывы: