background image

15

CORESENSE

TM

 TROUBLESHOOTING

Table 1. CoreSense

TM 

LED Diagnostics

STATUS LED

STATUS LED DESCRIPTION

STATUS LED TROUBLESHOOTING INFORMATION

Solid Green 

“RUN”

Module has power and

operating normally

Supply voltage is present at module terminals

Solid Red 

“TRIP”

Thermostat demand signal Y is 

present, but the compressor is not 

running

1. Compressor protector is open

•  Check for high head pressure

•  Check compressor supply voltage

2. Outdoor unit power disconnect is open

3. Compressor circuit breaker or fuse(s) is open

4. Broken wire or connector is not making contact

5. High pressure switch open if present in system

6. Compressor contactor has failed open

ALERT FLASH CODES

Yellow “ALERT”

Flash Code 1

Long Run Time

Low Refrigerant Charge

Compressor is running extremely 

long run cycles

1. Low refrigerant charge

2. Evaporator blower is not running

•  Check blower relay coil and contacts

•  Check blower motor capacitor

•  Check blower motor for failure or blockage

•  Check evaporator blower wiring and connectors

•  Check indoor blower control board
•  Check thermostat wiring for open circuit

3. Evaporator coil is frozen

•  Check for low suction pressure

•  Check for excessively low thermostat setting

•  Check evaporator airfl ow (coil blockages or return air fi lter)
•  Check ductwork or registers for blockage

4. Faulty metering device

•  Check TXV bulb installation (size, location and contact)

•  Check if TXV/fi xed orifi ce is stuck closed or defective

5. Liquid line restriction (fi lter drier blocked if present in system)
6. Thermostat is malfunctioning

•  Check thermostat sub-base or wiring for short circuit

•  Check thermostat installation (location, level)

Yellow “ALERT”

Flash Code 2

Compressor (Pressure) Trip

High Refrigerant Charge 

Discharge pressure out of limits or 

compressor overloaded

1. Condenser fan is not running

•  Check fan capacitor

•  Check fan wiring and connectors

•  Check fan motor for failure or blockage

2. High head pressure

•  Check high pressure switch if present in system

•  Check if system is overcharged with refrigerant

•  Check for non-condensable in system

3. Condenser coil poor air circulation (dirty, blocked, damaged)

4. Return air duct has substantial leakage

Yellow “ALERT”

Flash Code 3

Pressure Switch Cycling

Compressor is running only briefly 

due to pressure switch cycling

1. Time delay relay or control board defective

2. If high pressure switch present go to Flash Code 2 information

Yellow “ALERT”

Flash Code 4

Locked Rotor

1. Run capacitor has failed

2. Low line voltage (contact utility if voltage at disconnect is low)

•  Check wiring connections

3. Excessive liquid refrigerant in compressor

4. Compressor bearings are seized

•  Measure compressor oil level

Yellow “ALERT”

Flash Code 5

Compressor (Moderate Run)

Trip

1. Evaporator blower is not running

•  Check blower relay coil and contacts

•  Check blower motor capacitor

•  Check blower motor for failure or blockage

•  Check evaporator blower wiring and connectors

•  Check indoor blower control board

•  Check thermostat wiring for open circuit

2. Faulty metering device

•  Check TXV bulb installation (size, location and contact)

•  Check if TXV/fi xed orifi ce is stuck closed or defective

3. Condenser coil poor air circulation (dirty, blocked, damaged)

4. Low refrigerant charge

Содержание SA1BF4M2SN Series

Страница 1: ...IMPORTANT SAFETY INFORMATION 2 AIR CONDITIONER INSTALLATION 3 General Information 3 Before You Install this Unit 3 Locating the Air Conditioner 3 Packaging Removal 3 Ground Level 3 Roof Mount 3 Connec...

Страница 2: ...nt Refrigerant and electrical line should be routed through suitably waterproofed openings to prevent water from leaking into the structure This unit is designed for outdoor installations only and sho...

Страница 3: ...n 18 inches from the outside walls of the facility and in an area free from overhead obstructions to ensure unrestricted airflow through the outdoor unit Sufficient clearance for unobstructed airflow...

Страница 4: ...for loose connections Line Voltage A wiring diagram is located on the inside cover of the electrical box of the outdoor unit The installer should become familiar with the wiring diagram before making...

Страница 5: ...instructions supplied with the thermostat and the indoor equipment Typical AC and thermostat hookups are shown in Figure 3 The outdoor unit is designed to operate from a 24 VAC Class II control circu...

Страница 6: ...ify that it is warmer than ambient temperature Listen for any unusual noises Ifunusualsoundsoccur determinethesourceofthenoise and correct as necessary AIR CONDITIONER MAINTENANCE WARNING To prevent e...

Страница 7: ...unit Use only gage line sets which have a Schrader depression device present to actuate the valve Ahigh pressureswitchisfactory installedandlocatedinthe liquidlineinternaltotheoutdoorunit Theswitchis...

Страница 8: ...the recommended superheat value in the table then ADD refrigerant For TXV systems If your measured subcooling at the liquid valve is LESS THAN the recommended subcooling value in the table then ADD re...

Страница 9: ...uitable for 105 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and opti...

Страница 10: ...R L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR OUTDOOR FAN MOTOR Y2 Y L R C P DC SOL CSC C R Y2 Y LPS HPS CORESENSE COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC Contactor Coil CCH Crankcase He...

Страница 11: ...0 Hz WIRING DIAGRAM 7110150 1209 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE BLACK BLUE YELLOW BLUE BLACK 208 230V H C F CCH R C S S C H L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR FAN MOTOR L FAN REL...

Страница 12: ...e unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avant de faire...

Страница 13: ...HPS COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC 208 230V Two Stage Split System Air Conditioner Outdoor Section With ECM Outdoor Motor Single Phase 60 Hz NOTES 1 Disconnect all power before...

Страница 14: ...rcuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avant de faire letretien 8 Employez uniquement des conducteurs en cui...

Страница 15: ...m 6 Thermostat is malfunctioning Check thermostat sub base or wiring for short circuit Check thermostat installation location level Yellow ALERT Flash Code 2 Compressor Pressure Trip High Refrigerant...

Страница 16: ...ssor bearings are seized Measure compressor oil level Red LOCKOUT Flash Code 5 Yellow Off Compressor Moderate Run Trip 1 Evaporator blower is not running Check blower relay coil and contacts Check blo...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...allon MO Nortek Global HVAC LLC 2018 All Rights Reserved REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when or...

Отзывы: