35
Table 16. Electrical Data.
SINGLE PHASE MODELS
MODEL
NUMBER
R104HD
HEATING
INPUT
(BTUH)
INDUCER
MOTOR
NOMINAL
ELECTRICAL
SUPPLY
VOLTAGE
RANGE
COMPRESSOR
FAN
AMPS
BLOWER
MOTOR
AMPS
MINIMUM
CIRCUIT
AMPACITY
MAXIMUM
OVER-
CURRENT
PROTECTION
RLA
MIN.
MAX.
RLA
LRA
X24K060C
High - 60,000
0.30
208/230-1-60
187
253
12.8
58
1.0
5.4
22.4
35
Low - 39,000
X30K060C
High - 60,000
0.30
208/230-1-60
187
253
14.1
73
1.5
5.4
24.5
35
Low - 39,000
X36K080C
High - 80,000
0.30
208/230-1-60
187
253
15.4
84
1.5
7.0
27.7
40
Low - 52,000
X42K080C
High - 80,000
0.30
208/230-1-60
187
253
19.9
110
1.5
7.0
33.3
50
Low - 52,000
X48K096C
High - 96,000
0.30
208/230-1-60
187
253
21.8
117
1.5
7.0
35.7
50
Low - 62,400
X60K096C
High - 96,000
0.30
208/230-1-60
187
253
26.9
171
1.5
7.0
42.1
60
Low - 62,400
NOTES:
LRA = Locked Rotor Amps; RLA = Rated Load Amps
Electrical Data
COPPER WIRE SIZE — AWG
(1% VOLTAGE DROP)
SUPPLY WIRE LENGTH-FEET
SUPPLY CIRCUIT
AMPACITY
200
150
100
50
6
8
10
14
15
4
6
8
12
20
4
6
8
10
25
4
4
6
10
30
3
4
6
8
35
3
4
6
8
40
2
3
4
6
45
2
3
4
6
50
2
3
4
6
55
1
2
3
4
60
NOTE:
Wire Size based on N.E.C. for 60° type copper conductors.
Table 17. Copper Wire Size
Table 18. Thermostat Wire Gauge
THERMOSTAT
WIRE GAUGE
RECOMMENDED T-STAT WIRE
LENGTH (UNIT TO T-STAT)
2-WIRE
(HEATING)
5-WIRE
(HEATING / COOLING)
24
55
25
22
90
45
20
140
70
18
225
110