R104HD -X48K096C & R104HD -X60K096C
96,000 BTUH, 38”-42” CABINET, 11”X10” BLOWER W- 1 HP ECM MOTOR
230 VOLT OPERATION
SWITCH
SETTINGS
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1
2
3
4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
0
0
0
0
1347
65
1295
68
1242
71
1187
74
1131
78
1077
82
1023
86
970
91
916
96
1
0
0
0
1402
63
1353
65
1305
67
1252
70
1199
73
1147
77
1094
80
1039
85
984
89
0
1
0
0
1457
60
1412
62
1367
64
1317
67
1267
69
1216
72
1165
76
1109
79
1052
84
1
1
0
0
1517
58
1468
60
1420
62
1374
64
1328
66
1279
69
1229
72
1172
75
1115
79
0
0
1
0
1576
56
1524
58
1472
60
1431
61
1389
63
1341
66
1293
68
1236
71
1178
75
1
0
1
0
1625
54
1576
56
1528
58
1485
59
1442
61
1394
63
1346
65
1289
68
1233
71
0
1
1
0
1674
53
1629
54
1583
56
1539
57
1494
59
1446
61
1398
63
1343
66
1287
68
1
1
1
0
1721
51
1675
53
1629
54
1583
56
1538
57
1491
59
1445
61
1390
63
1336
66
0
0
0
1
1768
50
1721
51
1674
53
1628
54
1582
56
1537
57
1491
59
1438
61
1384
64
1
0
0
1
1807
49
1762
50
1717
51
1671
53
1626
54
1580
56
1534
57
1483
59
1433
61
0
1
0
1
1846
48
1803
49
1759
50
1715
51
1670
53
1623
54
1576
56
1529
58
1482
59
1
1
0
1
1889
47
1843
48
1798
49
1754
50
1710
51
1663
53
1617
54
1571
56
1526
58
0
0
1
1
1931
46
1884
47
1837
48
1793
49
1749
50
1703
52
1657
53
1613
55
1569
56
1
0
1
1
1970
45
1925
46
1881
47
1836
48
1792
49
1747
50
1703
52
1658
53
1614
54
0
1
1
1
2008
44
1967
45
1910
46
1880
47
1834
48
1791
49
1748
50
1704
52
1659
53
1
1
1
1
2038
43
1980
44
1939
46
1910
46
1891
47
1874
47
1857
47
1809
49
1760
50
208 VOLT OPERATION
SWITCH
SETTINGS
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1
2
3
4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
0
0
0
0
1308
67
1252
70
1196
74
1139
77
1082
81
1025
86
967
91
915
96
863
102
1
0
0
0
1363
65
1309
67
1255
70
1199
73
1143
77
1088
81
1033
85
979
90
926
95
0
1
0
0
1417
62
1366
64
1314
67
1259
70
1203
73
1151
76
1098
80
1043
84
988
89
1
1
0
0
1470
60
1418
62
1366
64
1315
67
1265
70
1212
73
1159
76
1102
80
1045
84
0
0
1
0
1523
58
1471
60
1418
62
1372
64
1326
66
1273
69
1220
72
1161
76
1102
80
1
0
1
0
1566
56
1515
58
1464
60
1417
62
1371
64
1321
67
1271
69
1211
73
1151
76
0
1
1
0
1608
55
1559
56
1509
58
1462
60
1415
62
1369
64
1322
67
1261
70
1200
73
1
1
1
0
1650
53
1602
55
1554
57
1508
58
1461
60
1411
62
1362
65
1303
68
1245
71
0
0
0
1
1691
52
1645
53
1599
55
1553
57
1507
58
1454
60
1401
63
1345
65
1289
68
1
0
0
1
1737
51
1691
52
1644
54
1599
55
1554
57
1503
59
1451
61
1396
63
1342
66
0
1
0
1
1783
49
1736
51
1689
52
1645
53
1601
55
1551
57
1501
59
1448
61
1394
63
1
1
0
1
1823
48
1776
50
1730
51
1684
52
1638
54
1589
55
1539
57
1488
59
1437
61
0
0
1
1
1862
47
1817
48
1771
50
1723
51
1675
53
1626
54
1577
56
1529
58
1480
59
1
0
1
1
1904
46
1857
47
1810
49
1763
50
1717
51
1672
53
1627
54
1599
55
1572
56
0
1
1
1
1946
45
1898
46
1849
48
1804
49
1758
50
1717
51
1676
52
1670
53
1664
53
1
1
1
1
1977
44
1936
45
1895
46
1878
47
1860
47
1809
49
1757
50
1709
51
1660
53
NOTES:
1. Factory settings are in bold. Use of any other switch setting may result in nuisance trips and should be verified for the application.
2. Temperature rises in tables are approximate. Actual temperature rises may vary.
3. Shaded areas are not recommended or approved for proper heating operation of equipment.
Heat rise: Btu/h (Input) = CFM * Δ T * 1.08
Δ T = (Btu/h * 0.95) / (CFM * 1.08)
Table 13. Blower Performance - 4 & 5 Ton