R104HD -X48K096C & R104HD -X60K096C

96,000 BTUH, 38”-42” CABINET, 11”X10” BLOWER W- 1 HP ECM MOTOR

230 VOLT OPERATION

SWITCH 

SETTINGS

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1

2

3

4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE

0

0

0

0

1347

65

1295

68

1242

71

1187

74

1131

78

1077

82

1023

86

970

91

916

96

1

0

0

0

1402

63

1353

65

1305

67

1252

70

1199

73

1147

77

1094

80

1039

85

984

89

0

1

0

0

1457

60

1412

62

1367

64

1317

67

1267

69

1216

72

1165

76

1109

79

1052

84

1

1

0

0

1517

58

1468

60

1420

62

1374

64

1328

66

1279

69

1229

72

1172

75

1115

79

0

0

1

0

1576

56

1524

58

1472

60

1431

61

1389

63

1341

66

1293

68

1236

71

1178

75

1

0

1

0

1625

54

1576

56

1528

58

1485

59

1442

61

1394

63

1346

65

1289

68

1233

71

0

1

1

0

1674

53

1629

54

1583

56

1539

57

1494

59

1446

61

1398

63

1343

66

1287

68

1

1

1

0

1721

51

1675

53

1629

54

1583

56

1538

57

1491

59

1445

61

1390

63

1336

66

0

0

0

1

1768

50

1721

51

1674

53

1628

54

1582

56

1537

57

1491

59

1438

61

1384

64

1

0

0

1

1807

49

1762

50

1717

51

1671

53

1626

54

1580

56

1534

57

1483

59

1433

61

0

1

0

1

1846

48

1803

49

1759

50

1715

51

1670

53

1623

54

1576

56

1529

58

1482

59

1

1

0

1

1889

47

1843

48

1798

49

1754

50

1710

51

1663

53

1617

54

1571

56

1526

58

0

0

1

1

1931

46

1884

47

1837

48

1793

49

1749

50

1703

52

1657

53

1613

55

1569

56

1

0

1

1

1970

45

1925

46

1881

47

1836

48

1792

49

1747

50

1703

52

1658

53

1614

54

0

1

1

1

2008

44

1967

45

1910

46

1880

47

1834

48

1791

49

1748

50

1704

52

1659

53

1

1

1

1

2038

43

1980

44

1939

46

1910

46

1891

47

1874

47

1857

47

1809

49

1760

50

208 VOLT OPERATION

SWITCH 

SETTINGS

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1

2

3

4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE

0

0

0

0

1308

67

1252

70

1196

74

1139

77

1082

81

1025

86

967

91

915

96

863

102

1

0

0

0

1363

65

1309

67

1255

70

1199

73

1143

77

1088

81

1033

85

979

90

926

95

0

1

0

0

1417

62

1366

64

1314

67

1259

70

1203

73

1151

76

1098

80

1043

84

988

89

1

1

0

0

1470

60

1418

62

1366

64

1315

67

1265

70

1212

73

1159

76

1102

80

1045

84

0

0

1

0

1523

58

1471

60

1418

62

1372

64

1326

66

1273

69

1220

72

1161

76

1102

80

1

0

1

0

1566

56

1515

58

1464

60

1417

62

1371

64

1321

67

1271

69

1211

73

1151

76

0

1

1

0

1608

55

1559

56

1509

58

1462

60

1415

62

1369

64

1322

67

1261

70

1200

73

1

1

1

0

1650

53

1602

55

1554

57

1508

58

1461

60

1411

62

1362

65

1303

68

1245

71

0

0

0

1

1691

52

1645

53

1599

55

1553

57

1507

58

1454

60

1401

63

1345

65

1289

68

1

0

0

1

1737

51

1691

52

1644

54

1599

55

1554

57

1503

59

1451

61

1396

63

1342

66

0

1

0

1

1783

49

1736

51

1689

52

1645

53

1601

55

1551

57

1501

59

1448

61

1394

63

1

1

0

1

1823

48

1776

50

1730

51

1684

52

1638

54

1589

55

1539

57

1488

59

1437

61

0

0

1

1

1862

47

1817

48

1771

50

1723

51

1675

53

1626

54

1577

56

1529

58

1480

59

1

0

1

1

1904

46

1857

47

1810

49

1763

50

1717

51

1672

53

1627

54

1599

55

1572

56

0

1

1

1

1946

45

1898

46

1849

48

1804

49

1758

50

1717

51

1676

52

1670

53

1664

53

1

1

1

1

1977

44

1936

45

1895

46

1878

47

1860

47

1809

49

1757

50

1709

51

1660

53

NOTES:

1. Factory settings are in bold. Use of any other switch setting may result in nuisance trips and should be verified for the application.

2. Temperature rises in tables are approximate. Actual temperature rises may vary.

3. Shaded areas are not recommended or approved for proper heating operation of equipment.

Heat rise: Btu/h (Input) = CFM * Δ T * 1.08

Δ T =  (Btu/h * 0.95) / (CFM * 1.08)

Table 13. Blower Performance - 4 & 5 Ton

Содержание R104HD Series

Страница 1: ...s supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Nepasentreposerniutiliserdel essencenid autres vapeursouliquidesinflammablesdanslevoisinage de cet appareil ni de tout autre appareil QUE FAIRE SI UNE ODEUR DE GAZ EST DÉTECTÉE Ne mettre en marche aucun appareil Ne toucher aucun interrupteur électrique ne pas u...

Страница 2: ...gle Stage Operation 23 De Humidification Control 23 Fan Mode 23 COMPONENT FUNCTIONS 23 EQUIPMENT MAINTENANCE 24 Heat Exchanger Burner Maintenance 24 Cleaning of Burners 25 REPLACEMENT PARTS 25 TROUBLESHOOTING 25 Cooling Mode 25 Heating Mode 25 FIGURES TABLES 26 Figure 8 Unit Dimensions 26 Table 7 Center of Gravity Shipping Weights 27 Airflow Information 28 Table 8 Cooling Airflow Settings 28 Table...

Страница 3: ...tion maintenance or repair may expose you to fiberglass insulation Breathing this material may cause respiratory irritations Fiberglass insulation may also cause eye irritation skin sensitization or other allergic responses in susceptible individuals Always wear goggles disposable gloves long sleeved shirt and appropriate breathing protection when working near this insulation If contact with skin ...

Страница 4: ...10 page 29 Table 11 page 30 Table 12 page 31 Table 13 page 32 and the rating plate for the proper circulating air flow and temperature rise It is important that the duct system be designed to provide the correct flow rates and external pressure rise An improperly designed duct system can result in nuisance shutdowns and comfort or noise issues Use only with the type of gas approved for this unit R...

Страница 5: ... Please consult your dealer for maintenance information and availability of maintenance contracts Please read all instructions before installing the unit Locating the Equipment Select a solid level position preferably on a concrete slab slightly above the grade level and parallel to the home DO NOT PLACE UNIT UNDER THE HOME Overhead obstructions poorly ventilated areas and areas subject to accumul...

Страница 6: ...pas suivies pour chacun des appareils raccordés au système de ventilation au moment de sa mise en marche cela peut entraîner une intoxication au monoxyde de carbone ou la mort Les étapes suivantes doivent être suivies pour chacun des appareils raccordés au système de ventilation au moment de sa mise en marche alors que tous les autres appareils raccordés au système de ventilation ne sont pas en ma...

Страница 7: ...e icing salts or chemicals Water softening chemicals Vent Termination This unit has been developed for use with a combination heat exchanger condensate drain and venting system designed to operate only with this type of system CondensateDrainandVentKitsareavailableforpurchase as accessory items HorizontalgroundmountapplicationscanuseP N 922323 toattachthe13 25 x2 PVCpipewithinthecontrolareaof this...

Страница 8: ...nternal acoustical lining must be NFPA Class 1 air ducts when tested per UL Standard 181 for Class 1 ducts The vent termination must be located at least 3 feet above any forced air inlet located within 10 feet The vent termination must be located at least 4 feet below 4 feet horizontally from or 1 foot above any door window or gravity air inlet into any building The unit should be installed in a w...

Страница 9: ...clearanceforunobstructedairflowthroughthe outdoor coil must also be maintained in order to achieve rated performance For information about locating the equipment see page 5 Ground Level Ground level installations must be located according to localbuildingcodesorordinancesandtheserequirements Clearances must be in accordance with those shown in Figure 1 page 5 A suitable mounting pad must be provid...

Страница 10: ...e 47 for additional lifting and setting of unit requirements Horizontal to Downflow Conversion The unit is shipped ready for horizontal duct connections Ifdownflowductsarerequired theunitmustbeconverted following the steps below for both the supply and return ducts 1 Remove both horizontal duct caps 2 Locatetheductcapinsidetheductopeningsandremove the screw holding it in place 3 Lift the cap out o...

Страница 11: ... 1 to 2 Filter Conversion section below Horizontal installations require the air filter system be installed in the return air ductwork Installing Filters in the Internal Filter Rack If Equipped 1 Remove access panel screws from return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Slide...

Страница 12: ... ampacity and maximum overcurrent protection limits A wiring diagram is located on the inside cover of the control access panel of the outdoor unit The installer should become familiar with the wiring diagram before making any electrical connections to the outdoor unit See Figure 13 page 37 All 208 240 volt units are shipped from the factory wired for 240 volt transformer operation For 208V operat...

Страница 13: ...to anticipate the space heating rate and time the burner to shutoff accordingly Always refer to the thermostatmanufacturer sinstructionsforcorrectsettings Addthecurrentdrawofthesystemheatingcomponents OR Measure the current flow on the thermostat R W circuit afterthecirculatingblowermotorhasstarted Settheheat anticipator according to the thermostat manufacturer s instructions for heat anticipator ...

Страница 14: ...ify the selected rise is within the specification shown on the furnace rating label or in the tables Dehumidification Options The fixed speed motor control board has a DEHUM connection that allows the system to increase the amount of humidity that is removed from the circulating air This is accomplished by reducing the CFM and allowing the coolingcoiltobecomecolder Thisfunctionisonlyavailable when...

Страница 15: ...y or gas supplier for additional requirements regarding placement of the manual main gas shut off See Figure 6 page 16 Themanifoldpressuremustbesettotheappropriate value for your installation To measure and adjust the manifold pressure see page 19 Gas piping must never run in or through air ducts chimneys gas vents or elevator shafts Compounds used to seal joints on gas piping must be resistant to...

Страница 16: ...hangingtheorifices SeeTable 3 for the correct manifold pressure settings NOTE Ifinstallingthisunitabove2 000feet theinputrate must be reduced 4 per 1 000 feet of altitude Example 12 at 3 000 feet 16 at 4 000 feet etc Deration is necessary to compensate for low atmospheric pressure at high altitudes LP Propane Gas Conversion WARNING This unit was equipped at the factory for use with natural gas onl...

Страница 17: ...ld run continuously Check the air delivery at the supply registers and adjust register openings for balanced air distribution Examine ductwork for leaks or obstruction if insufficient air is detected Set the thermostat fan mode to AUTO The blower should stop running NOTE When FAN ON is selected the blower will operate at 50 of selected airflow when no call for heating or cooling is present Lightin...

Страница 18: ...ctory recommended setting see in Table 8 page 28 Table 9 page 28 Table 10 page 29 Table 11 page 30 Table 12 page 31 Table 13 page 32 If the measured temperature rise falls outside the specified range it may be necessary to change the blower speed Lowering the blower speed increases the temperature rise and a higher speed decreases the temperature rise The unit is equipped with an ECM type motors S...

Страница 19: ...crewdriverorAllenwrench whereappropriate slowly turn the adjustment screw till the appropriate manifold pressure listed in Table 3 or Table 4 or the LOW and or HIGH firing rate for your specific gas HHV is achieved NOTE Turning the screw clockwise increases the pressure turning the screw counter clockwise decreases the pressure To prevent the screw from backing all the way out from the valve turn ...

Страница 20: ...C 10 0 4 5 3 5 96 000 91 200 62 400 59 300 45 40 70 170 0 80 57 000 11 x 10 1 Table 3 Manifold Pressure Setting in WC Orifice Sizes for Natural Gas MANIFOLD PRESSURE IN W C FOR NATURAL GAS INSTALLATIONS ALTITUDE ABOVE SEA LEVEL HEATING VALUE BTU CU FT ORIFICE SIZE 800 TO 899 FT 900 TO 999 FT 1 000 TO 1 100 FT Zero to 1 999 Ft 3 5 3 5 3 5 45 2 000 to 2 999 Ft 3 2 3 2 3 2 45 3 000 to 3 999 Ft 2 9 2 ...

Страница 21: ...l and or service this equipment Failure to comply with this warning couldresultinpropertydamage personalinjury or death CAUTION This unit uses R 410A refrigerant DO NOT use any other refrigerant in this unit Use of another refrigerant will damage the unit 1 Set the thermostat s system mode to COOL and the fan mode to AUTO Gradually lower the thermostat temperature setpoint below room temperature a...

Страница 22: ...on failure occurs the warm up interval is increased by 3 seconds on the next try If successful it remains there Minimum and maximum warm up time limits are set at 9 and 54 seconds 7 Flame Proving Ignition Low Heat Operation The furnace control must prove flame via the flame sensor 5 seconds after the high main gas valve is energized If flame is sensed burners are on and the igniter cools off The Y...

Страница 23: ...nd fan 4 When the thermostat is satisfied the contactor and integratedcontrolde energize Compressorandoutdoor fan will stop running 5 The circulating blower motor de energizes after a 60 second delay De Humidification Control If installing a humidistat install it in the return air duct as directed in the installation instructions included in the accessory kit Run the humidistat wiring through the ...

Страница 24: ...ason or more frequently if required Inspecttheevaporatorcondensatedrainandoutdoorcoil at the beginning of each cooling season Remove any debris Clean the outdoor coil and louvers as necessary using a mild detergent and water Rinse thoroughly with water Inspect the electrical connections for tightness at the beginning of each heating and cooling season The blower compartment should be cleaned month...

Страница 25: ...Fan Motor Inducer Blower Motor COMPONENTS Blower Assembly Fan Grille Burner Manifold Filter Driers Burners Orifices Gaskets Cabinet Panels Heat Exchanger Expansion Valves Table 5 Furnace Control Board Fault Conditions DIAGNOSTIC DESCRIPTION GREEN LED RED LED Control Fault No Power Off Off L1 Neutral Polarity Fault Flash Flash 1 Hour Lockout Alternating Flash Normal Operation On On Pressure Switch ...

Страница 26: ...ZONTAL SUPPLY DUCT OPENING HORIZONTAL RETURN DUCT OPENING 4 0 1 75 9 75 24 75 CONDENSING COIL C 30 89 13 5 16 0 13 5 16 0 4 0 4 0 13 5 16 0 13 5 55 8 12 45 9 75 24 75 1 75 8 75 12 45 17 50 C 16 0 HORIZONTAL SUPPLY DUCT OPENING HORIZONTAL RETURN DUCT OPENING FILTER ACCESS 3 PHASE ONLY CONDENSING COIL BACK VIEW Downflow Application Shown BACK VIEW Horizontal Application Shown TOP VIEW Horizontal App...

Страница 27: ...5 8 47 5 X48K096C 455 482 27 5 26 5 43 39 3 55 8 47 5 X60K096C 485 510 28 0 26 5 47 43 3 55 8 47 5 Table 7 Center of Gravity Shipping Weights 47 50 ELECTRIC SUPPLY ENTRY 1 25 DIA LOW VOLTAGE ENTRY 0 875 DIA GAS SUPPLY ENTRY 14 82 25 65 28 2 03 2 03 BLOWER ACCESS 5 40 CONDENSATE DRAIN AND VENT ASSEMBLY HORIZONTAL APPLICATION SIDE VIEW 28 25 65 14 82 2 03 5 40 6 53 7 03 25 15 2 03 47 50 GAS SUPPLY E...

Страница 28: ...M RISE CFM RISE 1 2 3 4 CFM RISE CFM RISE 0 0 0 0 600 57 800 66 0 0 0 0 885 55 1180 64 1 0 0 0 656 52 875 60 1 0 0 0 938 52 1250 61 0 1 0 0 694 49 925 57 0 1 0 0 990 49 1320 58 1 1 0 0 750 46 1000 53 1 1 0 0 1035 47 1380 55 0 0 1 0 806 43 1075 49 0 0 1 0 1080 45 1440 53 1 0 1 0 844 41 1125 47 1 0 1 0 1125 43 1500 51 0 1 1 0 881 39 1175 45 0 1 1 0 1170 42 1560 49 1 1 1 0 919 37 1225 43 1 1 1 0 1208...

Страница 29: ...0 0 70 0 80 0 90 1 00 1 2 3 4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE 0 0 0 0 783 67 740 71 696 76 645 82 594 89 554 95 514 103 472 112 429 123 1 0 0 0 851 62 808 65 765 69 719 73 672 79 631 84 590 90 549 96 509 104 0 1 0 0 919 57 877 60 834 63 792 67 750 70 708 75 665 79 627 84 588 90 1 1 0 0 994 53 953 55 913 58 871 61 830 64 785 67 741 71 702 75 664 79 0...

Страница 30: ...0 0 80 0 90 1 00 1 2 3 4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE 0 0 0 0 1218 58 1175 60 1132 62 1097 64 1062 66 1024 69 986 71 950 74 914 77 1 0 0 0 1270 55 1230 57 1191 59 1153 61 1116 63 1079 65 1043 67 1005 70 966 73 0 1 0 0 1321 53 1285 55 1249 56 1209 58 1169 60 1135 62 1100 64 1059 66 1018 69 1 1 0 0 1373 51 1335 53 1298 54 1260 56 1222 58 1185 59 11...

Страница 31: ...ETTINGS 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 90 1 00 1 2 3 4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE 0 0 0 0 1308 55 1252 57 1196 60 1139 63 1082 66 1025 70 967 74 915 78 863 83 1 0 0 0 1363 52 1309 54 1255 57 1199 59 1143 62 1088 66 1033 69 979 73 926 77 0 1 0 0 1417 50 1366 52 1314 54 1259 57 1203 59 1151 62 1098 65 1043 68 988 72 1 1 0 0 1470 49 1418 50 ...

Страница 32: ... 0 60 0 70 0 80 0 90 1 00 1 2 3 4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE 0 0 0 0 1308 67 1252 70 1196 74 1139 77 1082 81 1025 86 967 91 915 96 863 102 1 0 0 0 1363 65 1309 67 1255 70 1199 73 1143 77 1088 81 1033 85 979 90 926 95 0 1 0 0 1417 62 1366 64 1314 67 1259 70 1203 73 1151 76 1098 80 1043 84 988 89 1 1 0 0 1470 60 1418 62 1366 64 1315 67 1265 70 12...

Страница 33: ...BIC FEET PER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 150 750 1 500 26 138 692 1 385 28 129 643 1 286 30 120 600 1 200 32 113 563 1 125 34 106 529 1 059 36 100 500 1 000 38 95 474 947 40 90 450 900 42 86 429 857 44 82 409 818 46 78 391 783 48 75 375 750 50 72 360 720 52 69 346 ...

Страница 34: ... compagnie du gaz en utili sant le téléphone d un voisin A défaut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet à gaz à la main seulement Ne jamais utiliser d outils S il n est pas possible de faire tourner ou d enfoncer le robinet à la main ne pas essayer de le réparer Faire appel à un spécialiste Forcer ou tenter de réparer le robinet pourrait être...

Страница 35: ... 253 19 9 110 1 5 7 0 33 3 50 Low 52 000 X48K096C High 96 000 0 30 208 230 1 60 187 253 21 8 117 1 5 7 0 35 7 50 Low 62 400 X60K096C High 96 000 0 30 208 230 1 60 187 253 26 9 171 1 5 7 0 42 1 60 Low 62 400 NOTES LRA Locked Rotor Amps RLA Rated Load Amps Electrical Data COPPER WIRE SIZE AWG 1 VOLTAGE DROP SUPPLY WIRE LENGTH FEET SUPPLY CIRCUIT AMPACITY 200 150 100 50 6 8 10 14 15 4 6 8 12 20 4 6 8...

Страница 36: ... AUTO STAGE BLOWER OFF DELAY THERMOSTAT CONNECTIONS NEUTRALS FLAME 3 AMP FUSE INPUTS ON Figure 12 Ignition Control Board 624817 Figure 10 Two Stage Heating Single Stage Cooling Configuration TERMINAL STRIP THERMOSTAT R G C W2 W1 RED YELLOW GREEN BLACK Optional WHITE C R W1 G Y2 Y1 Y1 Y2 W2 BROWN A1 O E NOT USED NOT USED Blower Auto or Continuous ON 24VAC Common 1ST Stage Heat 24VAC To Blower Contr...

Страница 37: ... Yellow LED Continuous Flash Control Fault No Power Off Off Normal Operation On On Motor Fault On Flash Communications Fault Flash Flash Blower Control Diagnostic Description Green LED Red LED 10414180 NEW 2 22 Y2 E O Y1 G C A1 W1 W2 R COM 230 24V 208 IGNITOR FLAME SENSOR 2 STAGE GAS VALVE HIGH TEMP LIMIT FLAME ROLL OUT LIMIT INDUCER LIMIT HIGH PRESSURE SWITCH 11 4 1 8 7 10 5 2 9 3 12 6 LINE N XMF...

Страница 38: ...emove refrigerant when above curve Add refrigerant when below curve Figure 14 Charging Chart for 2 Ton Units 260 280 300 320 340 360 380 400 420 440 460 480 500 80 85 90 95 100 105 110 115 120 Liquid Temperature F Liquid Pressure psig 2 5 TON CHARGING CHART Remove refrigerant when above curve Add refrigerant when below curve Figure 15 Charging Chart for 2 5 Ton Units ...

Страница 39: ...rant when below curve Remove refrigerant when above curve 220 240 Figure 16 Charging Chart for 3 Ton Units 280 300 320 340 360 380 400 420 440 460 480 500 80 85 90 95 100 105 110 115 120 Liquid Temperature F Liquid Pressure psig 3 5 TON CHARGING CHART 520 Remove refrigerant when above curve Add refrigerant when below curve 125 130 Figure 17 Charging Chart for 3 5 Ton Units ...

Страница 40: ...nt when above curve Add refrigerant when below curve Figure 18 Charging Chart for 4 Ton Units 260 280 300 320 340 360 380 400 420 440 460 480 500 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid Pressure psig 5 TON CHARGING CHART 70 75 80 85 220 240 Remove refrigerant when above curve Add refrigerant when below curve 520 Figure 19 Charging Chart for 5 Ton Units ...

Страница 41: ...41 1 Inch Filter Installations 2 Inch Filter Installations Figure 20 Filter Comversion Internal Filter Conversion ...

Страница 42: ...e Depth for unit on standard 2 concrete pad NOTE For a trench style drain installation page 3 you will also need 4 x36 min corrugated flexible pipe w drain holes a 2 x4 PVC reducer 4 corrugated piping connection 2 x90 degree PVC elbow and 4 filtration sleeve or permeable barrier material Not Shown 40 80 Lb Rock or chat Limestone rock or lime pellets if required by local code for neutralizing the c...

Страница 43: ... by code with the initial rock base 2 Measure the distance between the top of the rock base and bottom of drain fitting 3 Cut the field supplied 2 PVC pipe to the measured length 4 Cutthedrainhoseandinsulationtothemeasuredlength less 3 so the drain cannot become blocked 5 Connect vinyl drain tube to the barbed drain connection at bottom of 2 PVC Tee and secure with spring hose clamp 6 Install flex...

Страница 44: ...ng hose clamp 8 Install flexible insulation over the entire length of drain tube and cut away any excess then secure at the top with wire tie provided 9 Cement the 2 PVC pipe into the elbow reducer assembly 10 Work the drain hose assembly into the pipe until the entire length is inside and the PVC pipe is vertical 11 Glue or use two 1 2 long screws field supplied to secure the 2 PVC Tee to the uni...

Страница 45: ...ND CONDENSATE DISPOSAL USING A VERTICAL DRAIN PIT Figure 21 Condensate Disposal Using A Vertical Drainage Pit BACK FILL ROCK ROCK BASE GRADE LEVEL PAD GRADE LEVEL SLAB MOUNT FLUE GAS AND CONDENSATE DISPOSAL USING A HORIZONTAL DRAIN TRENCH Figure 22 Condensate Disposal Using A Horizontal Drainage Trench ...

Страница 46: ...urb and 1 2 in from the long side of curb See Figure 23 If drilling a hole is not an option routing the condensate drainhoseovertotheductpassageopeningwithenough slope is acceptable as long as drain line is secured to curb and duct ensuring no kinks or traps can form betweenthecollectorboxdrainorinteriorofthebuilding Leave a minimum of 24 drain line extending out the top of roof curb front close o...

Страница 47: ...ition of the condensate drain valve be changed from the horizontal H to downflow D position The condensate drain valve is located in the bottom left corner of the heat exchanger collector box to the left of the inducer motor See Figure 24 Carefully rotate the valve 90 degrees in a clockwise direction until the arrow is pointing vertically downward 1 Slide the rubber grommet large diameter first do...

Страница 48: ... Degree Elbow 1 4 Mesh Screen 1 2 ID x 84 Drain Hose Flexible Insulation Optional Condensate Drain Valve D Position for Downflow Applications Only To building drain per State and Local Codes J Trap Height 3 Min DRAIN TRAP REQUIRED INTERIOR OF BUILDING Figure 24 Condensate Disposal ...

Страница 49: ...49 ...

Страница 50: ...50 ...

Страница 51: ...51 ...

Страница 52: ...ES NO SINGLE PHASE UNITS Rated Voltage VOLTS L1 L2 Volts VOLTS VENTING SYSTEM Is the heat exchanger condensate drain and vent pipe installed YES NO Is pipe free of restrictions YES NO Filter s secured in place YES NO Filter s clean YES NO ATTENTION INSTALLERS It is your responsibility to know this product better than your customer This includes being able to install the product according to strict...

Отзывы: