Nortek P7RE Series Скачать руководство пользователя страница 10

10

Start-up Procedure

note:

 The control circuit thermostat may consist of an 

anti-short cycle timer that will not let the compressor re-

start before 3 - 5 minutes have elapsed.

1. Set the system mode to OFF and the temperature mode 

to its highest setting.

2. Turn power on at the disconnect switch.

3. Set the system mode to ON or COOL.

4. Set the temperature mode below room temperature. 

Verify that the indoor blower, outdoor fan, and 

compressor energize and the cooling function starts.

5. Verify the discharge air grilles are adjusted and the 

system air is balanced.

6. Verify the duct work has no air leaks.

7. Verify the condensate drain is installed correctly and 

functions properly.

8. Set the temperature mode above room temperature. 

The unit should stop.

9. Instruct the homeowner on unit and thermostat operation 

and filter servicing.

System Cooling

Set the thermostat’s system mode to COOL and the fan 

mode to AUTO. Lower the thermostat temperature selector 

below the existing room temperature. Allow the cooling 

system to operate for several minutes and check for the 

discharge of cool air at the supply registers.

System Heating

(Available only when Electric heat is supplied) Set the 

thermostat’s system mode to HEAT and the fan mode to 

either AUTO (intermittent air) or to ON (continuous air). 

Raise the thermostat’s temperature selector above the 

existing room temperature and check the following:

1. The compressor and outdoor fan should not run.

2. The blower will run according to the thermostat’s fan 

mode setting.

reFrigerant charging

charging the unit

(with Outdoor Temperatures Above 65° F)

 caution:

this air conditioner contains liquid and gaseous 

refrigerant under pressure. adjustment of 

refrigerant charge should only be attempted 

by qualified, trained personnel thoroughly 

familiar with the equipment and safe responsible 

refrigerant handling procedures. under no 

circumstances should the homeowner attempt 

to install and/or service this equipment. Failure 

to comply with this warning could result in 

equipment damage, personal injury, or death.

note:

 The refrigerant charge can be checked and 

adjusted through the service ports provided external to 

the unit. Use only gage line sets which have a “Schrader” 

depression device present to actuate the valve.

Heat / Cool Thermostat

For the highest efficiency, the use of a 2-stage Heating/

Cooling thermostat is recommended. The heat/cool 

thermostat prevents simultaneous operation of the heating 

and cooling units and is equipped with an ON-AUTO fan 

mode that allows the home owner to operate the indoor 

blower when only air circulation is desired.

Connect the red, yellow, green and brown/orange low 

voltage wires to the 

r

 or 

rc

Y

g,

 

or 

W2 

(if applicable) 

terminals on the thermostat base. The black wire is the 24 
volt common required on some thermostats. See 

Figure 8

.

blower Speed - ecM Motor

 Warning:

to prevent electric shock, personal injury, or 

death, turn off the electric power at the disconnect 

or the main service panel before making any 

electrical connections.

For optimum system performance and comfort, it may be 

necessary to change the factory speed setting.

1. Disconnect all electrical power to the unit and remove 

the service panel.

2. Locate the orange and red wires terminated to the 

blower motor. 

note: 

The orange wire controls cooling 

operation and the red wire controls the heating operation.

3. Verify the required speed from the airflow data found 

in 

Table 3, (page 9)

. Place appropriate wire on the 

appropriate motor speed tap for the required airflow.

4. Check all factory wiring as shown in the wiring diagram 

and inspect the connections to make sure none of them 

loosened during shipping or installation.

Start uP & adJuStMentS

Pre-Start checklist

The following check list should be observed prior to 

starting the unit.

 Verify the unit is level and allows proper condensate 

drainage.

 Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/

control panels are in place. Unit must be installed with 
the proper clearances shown in 

Figure 1 (page 4)

.

  Verify that the duct work is sealed to prevent air leakage.

 Verify that the line voltage power leads are securely 

connected and the unit is properly grounded. Check 

the condenser fan to make sure it turns freely.

  Verify the thermostat is wired correctly and installed 

in a proper location. Make sure the low voltage wires 

are securely connected to the correct leads on the low 

voltage terminal strip.

 Verify that the power supply branch circuit overcurrent 

protection is sized properly.

  To achieve rated capacity and efficiency the compressor 

must be exposed to refrigerant for at least 24 hours prior 

to running. After unit startup, the compressor must run 

for a minimum of 12 hours.

Содержание P7RE Series

Страница 1: ...e plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings c...

Страница 2: ...tions 8 Cooling Only Thermostat 8 Heat Cool Thermostat 10 Blower Speed ECM Motor 10 START UP ADJUSTMENTS 10 Pre Start Checklist 10 Start Up Procedure 10 System Cooling 10 System Heating 10 Refrigerant...

Страница 3: ...he information listed below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equip...

Страница 4: ...ly and return ducts If practical place the air conditioner and its ducts in an area where they will be shaded from the afternoon sun when the heat load is greatest The length of the supply and return...

Страница 5: ...ollar so the edge of the unit opening fits between the flange and the bead 2 Overlap the collar ends keeping the small screw holes underneath 3 Align the holes in the crimped area and install one scre...

Страница 6: ...n the air box Connecting the Return Supply Air Flexible Ducts Flexible ducts can be connected to the corresponding fittings with the clamps provided with the ducts See Figure 9 Table 4 page 12 NOTE To...

Страница 7: ...installer should become familiar with the wiring diagram before making any electrical connections to the unit Anelectricaldisconnectmustbelocatedwithinsight of and readily accessible to the unit This...

Страница 8: ...reaker and do not in any case exceed the maximum size listed on the data label of the unit Thermostat Low Voltage Connections The unit is designed to operate from a 24 VAC Class II control circuit The...

Страница 9: ...27 1104 29 1051 30 992 32 Tap T3 1460 22 1415 22 1385 23 1335 24 1275 25 1225 26 1170 27 1120 28 Tap T4 1502 21 1466 22 1437 22 1388 23 1345 23 1305 24 1251 25 1204 26 Tap T5 1565 20 1525 21 1490 21 1...

Страница 10: ...Cool Thermostat For the highest efficiency the use of a 2 stage Heating Cooling thermostat is recommended The heat cool thermostatpreventssimultaneousoperationoftheheating and cooling units and is eq...

Страница 11: ...valve 2 Measure the liquid refrigerant temperature F at the service valve 3 For the temperature measured determine the required liquid refrigerant pressure from Table 5 page 15 Table 6 page 15 Table 7...

Страница 12: ...12 13 1 38 3 2 3 2 5 29 Side View Figure 9 Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View 3 5 4 5 Ton Model Nu...

Страница 13: ...ment des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1...

Страница 14: ...vant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Pack...

Страница 15: ...358 150 146 294 137 316 141 338 145 359 150 381 154 148 317 141 338 145 360 149 381 154 404 158 150 317 141 339 145 361 149 382 153 404 158 152 340 145 362 149 383 153 405 157 154 363 149 384 153 406...

Страница 16: ...55 146 357 182 378 171 398 162 415 160 148 380 181 401 172 421 164 150 403 181 423 173 152 426 182 154 Suct Press OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp...

Страница 17: ...147 378 172 399 172 421 172 443 172 149 403 176 424 177 446 177 151 428 181 449 181 153 453 185 155 Suct Press OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp Li...

Страница 18: ...40 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Remove refrigerant when above curve Add refrigerant when...

Страница 19: ...19...

Страница 20: ...uid Pressure high side _________________________ Stage 1 Suction Pressure low side _________________________ ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity correct YES NO...

Отзывы: