background image

Flex Match 

5

2.6 Connection of the Refrigerant Pipe

 When connecting the pipe to the unit use a wrench and torque wrench as shown in Fig. 5.

 Spread refrigerant oil lubricant to inside and outside of flare nut. Begin turning flare nut by 

hand, then tighten with a wrench.

 Refer to Table 1 to check for required torque (Note: over-tightening can cause damage to the 

nut or pipe and cause refrigerant leakage).

 Examine the connection pipe for leaks. Apply heat insulation, as shown in the Fig. 5.

Wrap tubes and heat preservation sheath with PTFE tape as shown

 Smear freeze motoroil 

here

Spanner

Thread fasten(X4

)

Median sponge (attachment) 

(entwine the wiring interface 

with seal mat)

Gas collection tube

Liquid inlet tube

Heat preservation 

sheath of liquid inlet 

tube (attachment) (for 

liquid tube

)

Heat preservation 

sheath of gas collection

 

tube (attachment)(for 

gas tube

)

Flare nut

Wiring interfac

e

Torque wrench

Fig. 5

Table 1: The moment of torque for tightening nut

Diameter

Inch

Surface thickness

mm

Moment of torque (N

·

m)

φ1/4’’

0.5

15-30 (N

·

m)

φ3/8’’

0.71

30-40 (N

·

m)

φ1/2’’

1

45-50 (N

·

·m)

φ5/8’’

1

60-65 (N

·

m)

φ3/4’’

1

70-75 (N

·

·m)

If  the  diameter  of  the  outdoor  unit  pipe  joint  does  not  match  the  indoor  unit,  the  joint 

specification of the outlet pipe of the indoor unit takes precedence. A reducing nipple should be 
installed at the joint of the outdoor unit to make the joint of the outdoor unit compatible with the 

indoor unit.

2.7 Drain Hose

(1). Install the drain hose

 The diameter of the drain hose should be larger than or equal to the connection pipe 

diameter. (The diameter of polythene pipe: Outer diameter 25mm (1 in) Surface thickness 

1.5mm) 

Содержание Flex Match GKH24(77.0)FMK4DH

Страница 1: ...Heat Pump Owner s Manual Models GKH24 77 0 FMK4DH Cassette Type Indoor Unit Please read this owner s manual carefully before operation and retain it for future reference Specifications illustrations...

Страница 2: ...o restart the operating modes must be reconciled The HEAT mode conflicts with of the COOL mode DRY mode and FAN mode while the COOL mode DRY mode and FAN mode are compatible between each other If ther...

Страница 3: ...2 5 Main Body of Hoisting Air Conditioner 4 2 6 Connection of the Refrigerant Pipe 5 2 7 Drain Hose 5 2 8 Electrical wiring 8 2 9 Install the Panel 10 3 Parts and Components of Cassette Type Indoor U...

Страница 4: ...d Don t apply or spray paint insecticide or other flammable liquids on the surface of unit otherwise fire may occur Once air conditioner is installed it should not be removed and installed in a differ...

Страница 5: ...vel when mounted 5 Select location where connections to outdoor unit and condensate drain are convenient 6 Be sure to leave sufficient space around unit for service and maintenance Unit should be moun...

Страница 6: ...opening 840mm 33 1 16 in Indoor unit 680mm 26 3 4 in Hoisting screws 950mm 37 3 8 in Decorated surface boards 890 mm 35 1 16 in Ceiling opening 840mm 33 1 16 in Indoor unit 780mm 30 11 16 in Hoisting...

Страница 7: ...n location Refer to the Fig 4 4 Check if the unit is level Inner drainage pump and bobber switch are included in the indoor unit Check if unit is level If the unit is slanted away from the condensate...

Страница 8: ...tube Heat preservation sheath of liquid inlet tube attachment for liquid tube Heat preservation sheath of gas collection tube attachment for gas tube Flare nut Wiring interface Torque wrench Fig 5 Tab...

Страница 9: ...amp included Insert the drain hose to the drain vent and then tighten the clamp Wrap the big sponge on the clamp of drain hose to insulate heat Heat insulation should be applied to indoor drain hose S...

Страница 10: ...in 75mm 3 in Fig 9 If drain hoses from several units are being installed together please install according to the following diagram 100mm 4 in Fig 10 2 Check the smoothness of drain after installatio...

Страница 11: ...nge on the electric wire to prevent condensation Attach tightly with fastener after connection and then secure the electric box Lead the 4 core cable through the hole in the chassis and the bottom of...

Страница 12: ...Flex Match 9 RXH36 10 6 FMV4DH POWER INDOOR UNIT D INDOOR UNIT C INDOOR UNIT B INDOOR UNIT A XT XT XT2 OUTDOOR UNIT N L...

Страница 13: ...he panel to the indoor unit body by matching the position of the swing flap motor of the panel to the piping position of the panel to the piping position of the indoor unit as shown by Fig 13 2 Instal...

Страница 14: ...t 15mm 1 2 in The panel will rise 4 Adjust the panel by turning it toward the direction pointed by the arrow as shown in Fig 13 so that the adjust board connect the ceiling well 5 Tighten the screws u...

Страница 15: ...on panel after tightening the screws readjust the height of the indoor unit As shown in Fig 15 If the raising lever and drain hose are not affect can adjust the height of indoor unit by the hole on th...

Страница 16: ...Cassette Type Indoor Unit Air outlet vent Air filter purifire in air inlet grille Air inlet grille Guide louver placed in air outlet vent Drainage equipment inside type Discharge cindensate water fro...

Страница 17: ...bulb temp Wet bulb temp Rated Cooling 80 0 26 7 67 0 19 4 95 0 35 0 75 0 23 9 Max cooling 80 0 26 7 67 0 19 4 115 0 46 1 75 0 23 9 Min cooling 67 0 19 4 57 0 13 9 67 0 19 4 57 0 13 9 Rated Heating 70...

Страница 18: ...ct power correctly Low batteries in wireless remote controller Change batteries Wireless controller out of control range Move remote to within 8m 25 ft of air conditioner Air conditioner runs but stop...

Страница 19: ...when running or after running Sound of drainage system Creaking sound heard when running or after running It is the sound of the skin plate expanding contracting due to temperature change Dust is blo...

Страница 20: ...if the filter is too dirty for example oil stain use some warm water but not over 45 C 113 F with mild detergent then dry in the shade Note Do not clean the filter with hot water more than 45 C 113 F...

Страница 21: ...Close air inlet grille refer to the 1st step 6 3 Install and Change of Air Purifier 1 Open air inlet grille the same the 1st step of Clean Air Filter 2 Disassemble purifier As shown in Fig 22 disassem...

Страница 22: ...y Install the protruding edge of both end into grooves on both end of guide louvre and then tighten bolts 6 5 Maintenance before or after Seasonal Use Preseason checklist Check if there is blockage in...

Страница 23: ...Specifications illustrations subject to change without notice or incurring obligations O Fallon MO 12 15 Nortek Global HVAC LLC 2015 All Rights Reserved 56 8 E 1215 66179400002...

Отзывы: