Nortek FG7SC Скачать руководство пользователя страница 13

13

For Installations where there is limited clearance for the 

J-Trap (such as an attic where it may be installed between 

ceiling joists), either side of the J-Trap can be shortened to 

a minimum of 3 Inches. See 

Figure 11 (page 15)

.

CIRCULATING AIR REQUIREMENTS

 WARNING:

Do not allow combustion products to enter the 

circulating air supply. Failure to prevent the 

circulation of combustion products into the 

living space can create potentially hazardous 

conditions including carbon monoxide poisoning 

that could result in personal injury or death.
All return ductwork must be secured to the 

furnace with sheet metal screws. For installations 

in confined spaces, all return ductwork must be 

adequately sealed. When return air is provided 

through the bottom of the furnace, the joint 

between the furnace and the return air plenum 

must be air tight.
The surface that the furnace is mounted on must 

provide sound physical support of the furnace 

with no gaps, cracks or sagging between the 

furnace and the floor or platform.
Return air and circulating air ductwork must 

not be connected to any other heat producing 

device such as a fireplace insert, stove, etc. This 

may result in fire, explosion, carbon monoxide 

poisoning, personal injury, or property damage.

Plenums & Air Ducts

• Plenums and air ducts must be installed in accordance 

with the Standard for the Installation of Air Conditioning 

and Ventilating Systems (NFPA No. 90A) or the 

Standard for the Installation of Warm Air Heating and Air 

Conditioning Systems (NFPA No. 90B).

•  On upflow furnaces, if the maximum airflow is 1,600 CFM 

or more, two openings shall be used for return air to 

comply with government mandated efficiency standards. 

Downflow furnaces can only use one return opening.

•  It is recommended that the outlet duct contain a removable 

access panel. The opening should be accessible when 

the furnace is installed in service and shall be of a size 

that smoke or reflected light may be observed inside 

the casing to indicate the presence of leaks in the heat 

exchanger. The cover for the opening shall be attached 

in a way that prevent leaks.

• If outside air is used as return air to the furnace for 

ventilation or to improve indoor air quality, the system 

must be designed so that the return air is not less than 

60° F (15° C) during operation. If a combination of indoor 

and outdoor air is used, the ducts and damper system 

must be designed so that the return air supply to the 

furnace is equal to the return air supply under normal, 

indoor return air applications.

• When a cooling system is installed which uses the 

furnace blower to provide airflow over the indoor coil, the 

coil must be installed downstream (on the outlet side) of 

the furnace or in parallel with the furnace.

• If a cooling system is installed in parallel with the 

furnace, a damper must be installed to prevent chilled 

air from entering the furnace and condensing on the heat 

exchanger. If a manually operated damper is installed, 

it must be designed so that operation of the furnace is 

prevented when the damper is in the cooling position and 

operation of the cooling system is prevented when the 

damper is in the heating position.

• Seal all connections and joints with industrial grade 

sealing tape or liquid sealant. Requirements for sealing 

ductwork vary from region to region. Consult with local 

codes for requirements specific to your area.

Return Air Connections

•  In applications where the supply ducts carry heated air to 

areas outside the space where the furnace is installed, 

the return air must be delivered to the furnace by duct(s) 

secured to the furnace casing, running full size and 
without interruption. 

Do not use the back of the furnace 

for return air.

•  Position the furnace with the return air ductwork ensuring 

even alignment of furnace (or coil casing) air opening 

and return air duct. 

NOTE

: The ductwork must have an 

opening equal to that of the return air opening of the 

furnace (or coil casing). See 

Figure 32 (page 30)

 or 

Figure 33 (page 31)

 for return air opening size.

Upflow & Horizontal Furnaces

•  The return air ductwork may be connected to the left side, 

right side, or bottom of the furnace. 

NOTE

: If using the left 

or right side of the furnace for return air, the bottom panel 

(Figure 32) must not be removed from the bottom of the 

furnace.

 WARNING:

The bottom panel of the furnace must be in place 

when the furnace is installed with side return air 

ducts. Removal of all or part of the base could 

cause circulation of combustible products into 

the living space and create potentially hazardous 

conditions, including carbon monoxide poisoning 

that could result in personal injury or death.

• 

Side Return Installations

: To attach the return air duct 

to the left or right side of the furnace, punch out the 4 

knockouts from the side of the furnace (

Figure 33

). 

Using sharp metal cutters, cut an opening between all 4 

knockouts to expose the blower assembly. Position the 

return air duct over the opening and secure to the side 

with sheet metal screws.

• 

Bottom Return Installations

: If using the bottom of the 

furnace for return air, the bottom panel (

Figure 33

) must 

be removed from the bottom of the furnace. See 

page 

19

 for removal instructions. Position the furnace over 

the return air duct and secure together with sheet metal 

screws. Make sure the screws penetrate the duct and 

furnace casing.

Содержание FG7SC

Страница 1: ...rformed by a qualified installer service agency or the gas supplier Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU...

Страница 2: ...Connections 25 Twinning 25 One stage heating 26 Two stage heating 26 Heat Anticipator 26 START UP ADJUSTMENTS 27 Pre Start Check List 27 Start up Procedures 27 Verifying Adjusting Input Rate 27 Verify...

Страница 3: ...ne cigarette lighter fluid dry cleaning fluids paint thinners or other volatile fluids The installer should become familiar with the units wiring diagram before making any electrical connections to th...

Страница 4: ...ationinstructionsshallremainwiththeappliance or equipment at the completion of the installation The information listed below is for reference purposes only and does not necessarily have jurisdiction o...

Страница 5: ...bovetherequirements Allow24inchesminimum clearance from the front of the unit However 36 inches is strongly recommended See Figure 1 for minimum clearance requirements Operation of Furnace During Cons...

Страница 6: ...ntingsystemforpropersizeand horizontalpitch asrequiredintheNationalFuel Gas Code ANSI Z223 1 NFPA 54 or the CSA B149 1 Natural Gas and Propane Installation Codes and these instructions Determine that...

Страница 7: ...Exhaust fans clothes dryers fireplaces and other appliances that force air from the house to the outdoors can create a negative pressure inside the house resulting in improper furnace operationorunsa...

Страница 8: ...uvers For Unheated Crawl Space Inlet Air Ventilation Louvers each end of attic NOTE Air openings shall each have a free area of not less than one square inch per 4 000 Btuh of the total input rating o...

Страница 9: ...greater than 50 cubic feet per 1 000 Btuh of the combined input rates of all appliances which draw combustion air from that space In general a furnace installed in an unconfined space will not require...

Страница 10: ...rimers must be certified as a system to ULC S636 However this requirement does not apply to the finish flanges or piping internal to the furnace Vent Pipe Length Diameter In order for the furnace to o...

Страница 11: ...ace operation and conformance to applicable codes A vent terminal must be located at least 3 feet above any forced air inlet located within 10 feet This does not apply to the combustion air inlet of a...

Страница 12: ...must be positioned pointing away from the exhaust vent 8 Min 36 Max Plumbing Vent Roof Boot Both Pipes WINTER DESIGN TEMPERATURE MAXIMUM FLUE PIPE LENGTH FEET IN UNCONDITIONED EXTERIOR SPACES WITHOUT...

Страница 13: ...ses the furnace blower to provide airflow over the indoor coil the coil must be installed downstream on the outlet side of the furnace or in parallel with the furnace If a cooling system is installed...

Страница 14: ...ns including installation in the upflow or horizontal positions with either right left or upflow return air SL SM series gas furnaces may only be installed as a downflow application General Requiremen...

Страница 15: ...NING Failure to install the downflow sub base kit may resultinfire propertydamageorpersonalinjury To install an SL SM series gas furnace on combustible flooring a special sub base is required Downflow...

Страница 16: ...nducer assembly 2 Removetheinducerassemblygroundwirefromtheblower deck 3 Remove 3 screws securing the inducer assembly to the header box 4 Rotate the inducer assembly to its new position 5 Secure the...

Страница 17: ...eningbetween the furnace cabinet and the 2 PVC vent pipe The rubber grommet should be installed in the 3 hole prior to running the vent pipe out of cabinet No sealants are required See Figure 19 page...

Страница 18: ...ropriate primer and cement 3 Install the 1 2 x 1 2 hose barb on the 2 PVC reducer NOTE Do not over tighten Use an adequate amount of Teflon tape on the threads Do not use liquid sealants 4 Verify all...

Страница 19: ...ent feet while maintaining 1 4 per foot slope and insulated if located in an unconditioned space THREE GENERAL PRINCIPLES APPLY Each condensate drain must be trapped separately using a J Trap or field...

Страница 20: ...commended for this type of furnace but may be used if allowed by local jurisdiction Only new flexible connectors may be used Do not use a connector which has previously serviced another gas appliance...

Страница 21: ...r changing the regulator pressure or the orifices it is required that you measure the gas input rate This may be accomplished in the usual way by clocking the gas meter and using the local gas heating...

Страница 22: ...eft Side Entry See Note A See Note A Burner Assembly Burner Assembly Burner Assembly Manifold Manifold Manifold Manifold Gas Valve Drip Leg Drip Leg Drip Leg Shut Off Valve Shut Off Valve Shut Off Val...

Страница 23: ...local codes for Shut Off Valve location requirements NOTE B Inducer assembly omitted for clarity of pipe installatio Burner Assembly Manifold Drip Leg Drip Leg Shut Off Valve Shut Off Valve Gas Valve...

Страница 24: ...ee Figure 26 page 25 or the wiring diagram label inside of the control door Any other wiring methods must be acceptable to authority having jurisdiction Proper line voltage polarity must be maintained...

Страница 25: ...OT install the thermostat on an outside wall or any other location where its operation may be adversely affected by radiant heat from fireplaces sunlight or lighting fixtures and convective heat from...

Страница 26: ...ry furnace to the coil side of the relay using field supplied wire and 3 16 terminals Connect C from the primary furnace to the coil side of the relay using field supplied wire and 3 16 terminals NOTE...

Страница 27: ...to obtain the input rate in Btuh See example EXAMPLE Time for 1 revolution of a gas meter with a 1 cubic ft dial 40 seconds From Table 6 read 90 cubic ft gas per hr Local heating value of the gas obta...

Страница 28: ...a green and a red LED labeled Status on the motor control board to provide system faults as described below Refer to Table 15 page 49 for Nordyne UTEC boards or Table 14 page 49 for Emerson boards to...

Страница 29: ...e 51 or Figure 48 page 52 for component location 1 Shut off gas supply to the furnace at the meter or at a manual valve in the supply piping 2 Turn off all power to the furnace and set the thermostat...

Страница 30: ...2 Front Brace LEFT SIDE RIGHT SIDE Electric 7 8 25 1 2 22 1 2 Gas 1 5 8 Vent pipe 3 Cond 1 1 16 B 19 FLANGES TOP VIEW C BOTTOM VIEW Electric 7 8 Vent pipe 3 Cond 1 1 16 FRONT VIEW 28 3 Flue Combustion...

Страница 31: ...23 1 2 C 34 1 2 22 1 2 2 3 4 Bottom Panel 25 3 8 22 1 2 17 1 4 17 7 8 28 B 19 22 1 2 24 7 8 15 23 1 1 4 Front Brace BOTTOM VIEW TOP VIEW 4 Knockouts both sides 1 LEFT SIDE RIGHT SIDE 3 1 4 Gas 1 5 8 T...

Страница 32: ...e original wire as supplied with the furnace must be replaced it must be replaced with wiring material having a temperature of at least 105 C Use copper conductors only Diagnostic Description Green LE...

Страница 33: ...the furnace for the proper heating and cooling speeds for your application If any of the original wire as supplied with the furnace must be replaced it must be replaced with wiring material having a t...

Страница 34: ...TRONIC AIR CLEANER HUMIDIFIER HOT SURFACE IGNITOR INDUCER 120 VAC 24 VAC TRANSFORMER K4 K3 K2 P1 7 EAC P2 3 HUM P2 1 XFORMER NEUTRAL NEUTRAL NEUTRAL NEUTRAL P2 4 P2 6 NEUTRAL SUPPLY AIR LIMIT ROLL OUT...

Страница 35: ...SOR ELECTRONIC AIR CLEANER HUMIDIFIER HOT SURFACE IGNITOR INDUCER 120 VAC 24 VAC TRANSFORMER K4 K3 K2 P1 2 EAC P2 1 HUM P2 2 XFORMER NEUTRAL NEUTRAL NEUTRAL NEUTRAL NEUTRAL NEUTRAL NEUTRAL SUPPLY AIR...

Страница 36: ...44 220 439 84 43 214 429 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 11...

Страница 37: ...SURE 6 000 to 7 999 FT 57 61 57 57 57 57 56 56 ORIFICE SIZE 9 0 8 0 9 0 9 0 9 0 9 0 9 0 9 0 MANIFOLD PRESSURE 8 000 to 10 000 FT 57 61 57 57 57 57 56 56 ORIFICE SIZE 8 5 7 5 8 5 8 5 8 5 8 5 8 5 8 5 MA...

Страница 38: ...000 to 9 999 FT 49 53 49 49 49 49 48 48 ORIFICE SIZE 3 0 2 8 2 8 2 8 2 8 2 8 2 8 2 8 MANIFOLD PRESSURE HIGH ALTITUDE DERATION NATURAL GAS WITH LOW HEATING VALUE ALTITUDE ABOVE SEA LEVEL INPUT BTU 38 0...

Страница 39: ...supply inlet to building or the combustion air inlet to any other appliance 6 inches 15cm for appliances 10 000 Btuh 3kW 6 inches 15cm for appliances 10 000 Btuh 3kW 4 ft 1 2m below or to side of open...

Страница 40: ...Pipe must slope upward 1 4 per foot 5 7 90 Elbows 90 Elbow COMBUSTION AIR Straps or other suitable supports at minimum 5 ft intervals both pipes 90 Elbows Flue Pipe must slope upward 1 4 per foot Firs...

Страница 41: ...llector Box Drain Factory Equipped See NOTE 2 Inline Drain Field Supplied See NOTES 2 3 Collector Box Drain Factory Equipped See NOTE 2 X See NOTE 5 X See NOTE 5 FLUE PIPE X See NOTE 5 X See NOTE 5 FL...

Страница 42: ...TAL RIGHT 1 PIPE OPTIONS Plug VIEW D VIEW E VIEW F VIEW G COMBUSTION AIR FLUE PIPE OPTION 7 OPTION 8 COMBUSTION AIR Rubber Grommet See VIEW D for drain line positions See VIEW E for drain line positio...

Страница 43: ...in Factory Equipped See NOTE 2 Inline Drain Field Supplied See NOTES 2 3 Collector Box Drain Factory Equipped See NOTE 2 Inline Drain Field Supplied See NOTES 2 3 Inline Drain Factory Supplied See NOT...

Страница 44: ...BUSTION AIR PVC Tee PVC Trap X See NOTE 5 X See NOTE 5 X See NOTE 5 X See NOTE 5 Inline Drain Factory Supplied See NOTE 4 Collector Box Drain Factory Equipped See NOTE 2 Inline Drain Factory Supplied...

Страница 45: ...to furnace connection as possible Wall Normal Snow Level COMBUSTION AIR 90 Elbow both ends Seal Caulk Around Pipes at Building 90 Elbow 7 12 Min 90 Elbow 90 Elbow Support System on Vertical Rise COMB...

Страница 46: ...Inline Drain Tube Factory Supplied See NOTE 4 Collector Box Drain Factory Equipped See NOTES 2 3 Inline Drain Tube Field Supplied See NOTE 3 Collector Box Drain Factory Equipped See NOTES 2 3 X See N...

Страница 47: ...ug Plug See VIEW R for drain line positions Flange Flange Option 25 Option 26 SD SERIES HORIZONTAL LEFT 1 PIPE OPTION SD SERIES HORIZONTAL LEFT 2 PIPE OPTION SD SERIES HORIZONTAL RIGHT 2 PIPE OPTION C...

Страница 48: ...ctor Box Drain Factory Equipped See NOTE 2 Inline Drain Factory Supplied See NOTE 4 PVC Trap PVC Tee PVC Trap PVC Tee PVC Trap PVC Tee PVC Trap Collector Box Drain Factory Equipped See NOTE 2 Collecto...

Страница 49: ...and repair the problem If the furnace still doesn t operate check the Flame Roll out Switches and reset if necessary If the furnace operates when the Flame Rollout Switch is reset contact a qualified...

Страница 50: ...e end burner If no flame is detected the furnace will shut down within 4 seconds Flame Roll Out Switch Verifies that the burner flames are drawn into the heat exchanger tubes If the burner flames are...

Страница 51: ...ondensate B C D cabinets only Roll Out Switch Transformer Vent Limit Switch UPFLOW HORIZONTAL FURNACE SC SERIES Burner Assembly Finish Flange Flame Sensor Igniter Roll Out Switch Gas Valve Furnace Con...

Страница 52: ...sure Switch Vent Limit Switch Control Board Main Air Limit Switch Transformer Roll Out Switch DOWNFLOW FURNACE SL SERIES Burner Assembly Flame Sensor Roll Out Switch Finish Flange Blower Assembly behi...

Страница 53: ...53...

Страница 54: ...54...

Страница 55: ...55...

Страница 56: ...S NO Is there proper draft YES NO ATTENTION INSTALLERS It is your responsibility to know this product better than your customer This includes being able to install the product according to strict safe...

Отзывы: