background image

4

GENERAL INFoRMAtIoN

This appliance has been tested for capacity and efficiency 

in accordance with AHRI Standards and will provide many 

years of safe and dependable comfort, providing it is properly 

installed and maintained. Abuse, improper use, and/or 

improper maintenance can shorten the life of the appliance 

and create unsafe hazards. Please read all instructions 

before installing the unit.

Before You Install this unit

 This equipment is securely packaged at the time of 

shipment and upon arrival should be carefully inspected 

for damage prior to installing the equipment at the job 

site. Claims for damage (apparent or concealed) should 

be filed immediately with the carrier.

 it is recommended that the cooling load of the area to 

be conditioned should be calculated and a system of the 

proper capacity selected.

 Check the electrical supply and verify the power supply 

is adequate for unit operation. The system must be wired 

and provided with circuit protection in accordance with 

local building codes. If there is any question concerning 

the power supply, contact the local power company.

 Verify the duct system is appropriate for the air handler 

being installed. Please note that when replacing an existing 

system with lower air-flow, the duct system may require 

modification.

Locating the Air Handler

•  Survey  the  job  site  to  determine  the  best  location  for 

mounting the unit. Consideration should be given to 

availability of electric power, service access, and noise.

•  The dimensions of the room or alcove must be able to 

accommodate the overall size of the unit and the installation 

clearances listed in 

Table 1

. Physical dimensions for this 

air handler are also shown in 

Figure 11 (page 15)

.

•  The air handler should be set into position before routing 

the refrigerant tubing.

Minimum clearances

•  This  appliance  must  be  installed  in  accordance  with 

clearances listed in 

Table 1

. The air handler must be 

installed with ample clearance for easy access to the air 

filter, blower assembly, heater assembly, controls, and 

vent connections. Applicable building codes may require 

additional clearance to equipment. Refer to applicable 

building codes for details.

•  Static  pressure  drop  through  louvered  openings  and 

through return air plenums should be considered in the 

overall duct design in the determination of the total external 

static pressure.

Installation in a Garage

 WARNING:

Do not place combustible materials on or against 

the cabinet. Do not place flammable materials, 

(gasoline, paint thinners, etc.) or any other 

flammable vapors and liquids, in the vicinity of 

the air handler.

The B6 Series air handler may be installed in a residential 

garage with the provision that the unit must be located or 

protected to prevent physical damage by vehicles.

table 1. 

Minimum unit clearances

INStALLAtIoN cLEARANcES

Left Side ............. 0 Inches

Right Side ......... 0 Inches

Back .................. 0 Inches

Front ...............†See Notes

 

NotE:

Alcove Installations - Allow 24 in. minimum clearance from front 

of unit to nearest wall or partition for servicing. Recommended 

clearance is 36 in.

REAR

RIGHT

SIDE

LEFT
SIDE

FRONT

Plenums & Air Ducts

•  Plenums and air ducts should be installed in accordance with 

the standards of the National Fire Protection Association 

Standard for Installation of Air Conditioning Systems 

(NFPA 90A), Standard for Installation of Residence Type 

Warm Air Heating and Air Conditioning Systems (NFPA 

90B), and all applicable local codes. NFPA publications 

are available by writing to: National Fire Protection 

Association, Batterymarch Park, Quincy, ME 02269 or visit  
www.NFPA.org online.

 WARNING:

All return ducts must be secured to the air 

handler using appropriate methods. All return 

ducts must be adequately sealed. When return 

air is provided through the bottom of the unit, 

the joint between the air handler and the return 

air plenum must be air tight.
Return air and circulating air ducts must not be 

connected to any other heat producing device 

such as a fireplace insert, stove, etc. this may 

result in fire, explosion, carbon monoxide 

poisoning, personal injury, or property damage.

•  Design the duct work according to methods described by 

the Air Conditioning Contractors of America (ACCA).

•  This unit is designed only for use with a return and supply 

duct. The return air duct must have the same free area as 

the opening provided on the air handler. The ducts should 

be appropriately sized to the capacity of the air handler to 

ensure its proper airflow rating.

Содержание B6BM Series

Страница 1: ...ole as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious...

Страница 2: ...tion 12 Turning the Blower Off 12 System Cooling 12 System Heating 12 Selecting Minimum Electric Heat Airflow 12 Blower Configurations 12 Determining Nominal System Capacity 12 3 Speed Units 12 High E...

Страница 3: ...installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could resu...

Страница 4: ...ment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums should be considered in the overallductdesigninthedeterminationoftheto...

Страница 5: ...install all the needed gaskets and grommets around penetrations into the air handler such as for electrical wiring Air handler INSTALLATION B6 series air handler s are shipped ready for vertical upflo...

Страница 6: ...oil and drain pan assembly out of the unit 3 Remove the sheet metal hairpin covers if supplied from the back of the coil and discard 4 Place the horizontal drain pan on the opposite side of the coil O...

Страница 7: ...equipment damage personal injury or death The installer should make every effort to ensure the field installed refrigerant containing components of the system have been installed in accordance with t...

Страница 8: ...htenanadditional1 4turnusingtwowrenches The movement of the two lines will show how much the nut is tightened If a torque wrench is used tighten to 10 12 ft lbs or 14 16 Nm Connecting the Linesets The...

Страница 9: ...d tubing or pvc pipe and adequately trapped Both drain tubes must have a minimum diameter of 3 4 and be trapped separately IMPORTANT Failure to install a trap may result in condensation overflowing th...

Страница 10: ...of the original wires supplied with the unit the replacement wire must be copper wire consisting of the same gauge and temperature rating Provide power supply for the unit in accordance with the unit...

Страница 11: ...ions The motor control board has a DHUM or D connection that allows the system to increase the amount of humidity that is removed from the circulating air See Figure 17 Figure 18 page 27 This is accom...

Страница 12: ...control boards do not support non electric heat because the heating air flow cannot be set independently Blower Configurations Determining Nominal System Capacity To select the appropriate airflows f...

Страница 13: ...ed the basic cooling heat pump airflow selected may be too low Verify the setting selected is within the range shown in Table 9 and that the the system is properly charged Please refer to the instruct...

Страница 14: ...etailers WARNING Never operate the air handler without a filter in place Dust and lint in the return air can build up on internal components resulting in loss of efficiency equipment damage and possib...

Страница 15: ...11 4 15 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A Cabinet Size H W A Detail D A 43 5 16 14 3 16 12...

Страница 16: ...Motor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Filter Door Upper Door Assembly Lower Door...

Страница 17: ...764 701 631 555 Corrected ESP1 0 00 0 04 0 16 0 27 0 39 0 51 0 62 0 74 Medium 1265 1232 1188 1133 1067 991 903 805 Corrected ESP1 0 00 0 00 0 03 0 15 0 28 0 41 0 54 0 68 High 1427 1385 1333 1270 1196...

Страница 18: ...805 750 1 1 1 0 1155 1105 1060 1010 965 920 870 825 0 0 0 1 1230 1185 1140 1090 1045 1010 965 920 1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010 0 1 0 1 1330 1290 1245 1205 1170 1125 1085 1045 1 1 0...

Страница 19: ...ttings for these airflows A Cabinet B Cabinet C Cabinet CFM Nominal Capacity CFM Nominal Capacity CFM Nomical Capacity 525 1 5 TON 525 1 5 TON 1100 3 TON 560 560 1200 3 5 TON 600 600 1250 625 650 2 TO...

Страница 20: ...1100 1 0 1 0 0 700 1 15 1300 1 0 1 0 1 750 1 20 1500 1 0 1 1 0 800 1 25 n a 1 0 1 1 1 850 1 30 n a 1 1 0 0 0 875 1 1 0 0 1 950 1 1 0 1 0 1050 1 1 0 1 1 1150 1 1 1 0 0 1250 1 1 1 0 1 1350 1 1 1 1 0 14...

Страница 21: ...7 67 6 50 25 70 020H XX 52 6 50 0 102 6 60 60 110 46 0 43 3 89 3 50 45 90 009Q XX 29 7 30 26 1 30 015Q XX 45 9 50 40 2 45 B 42 48 None 3 1 3 1 15 15 3 1 3 1 15 15 005H XX 28 1 28 1 30 30 24 8 24 8 25...

Страница 22: ...ase MCA MOP MCA MOP Circuit A Circuit B Circuit C Single Circuit Circuit A Circuit B Circuit C Single Circuit Circuit A Circuit B Circuit C Single Circuit Circuit A Circuit B Circuit C Single Circuit...

Страница 23: ...seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay Stage 6 Heat on after 25 seconds delay Off Heat stages off instantly...

Страница 24: ...econd delay Stage 2 Heat on after 5 seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay 30 KW Stage 1Heat on instantly Co...

Страница 25: ...Typical 2 Stage Heat Pump with 2 Stage Air Handler Y2 Y2 Y2 Y2 OUT W E R Air Conditioner Air Handler Air Conditioner Air Handler Heat Pump Air Handler Heat Pump O R C Y Air Handler Heat Pump NOTE Jum...

Страница 26: ...1 BLWDTC BLWDTC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 Figure 15 Single Stage Control Board C R G Y2 Y O 1W 2W 1Y L LED 1 HEATER P1 L 2 HUM EAC P2 3A Fuse P3 Figure 16 Two Stage Contro...

Страница 27: ...N TEST PORT BLOWER MOTOR RED INPUTS COOL HEAT FAN SPEED OUTPUTS STATUS LIGHTS 2 3 4 5 6 7 8 OFF ON A B Figure 18 Variable Speed Motor Control Board Figure 17 Fixed Speed Motor Control Board 3A Fuse EA...

Страница 28: ...e transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension de l installation 4 Si le c blage interne est remplac utilisez seulement un fil de cui...

Страница 29: ...sse du moteur du ventilateur peut diff rer de l illustration Consultez les Instructions d installation 2 D branchez toutes les sources d alimentation avant l entretien 3 Le transformateur peut avoir u...

Страница 30: ...ons d installation 2 D branchez toutes les sources d alimentation avant l entretien 3 Le transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension...

Страница 31: ...31...

Страница 32: ...INSTALLERS Itisyourresponsibilitytoknowthisproductbetterthanyourcustomer This includes being able to install the product according to strict safety guidelines and instructing the customer on how to o...

Отзывы: