2

GeNerAl iNFOrmAtiON

These uncased replacement coils are designed for upflow, 
downflow, or horizontal applications.

•  Check the coils orifice size and confirm that it’s suitable 

for application with the intended outdoor unit. Depending 

on application, additional installer supplied orifice or TXV 

may be required.

•  Verify  that  the  air  delivery  of  the  furnace/air  handler  is 

adequate to handle the static pressure drop of the coil, 

filter, and duct work.

•  If precise forming of refrigerant lines is required, a copper 

tubing bender is recommended. Avoid sharp bends and 

contact of the refrigerant lines with metal surfaces.

•  Refrigerant lines should be wrapped with pressure sensitive 

neoprene or other suitable material where they pass against 

sharply edged sheet metal.

•  Horizontal installations require a horizontal drain pan kit 

to be installed. See Table 6 (page 8) for part number.

COil iNStAllAtiON

 WArNiNG:

Shut off all electrical power to the furnace and 

outdoor condensing unit before performing any 

maintenance or service on the system. electric 

furnaces may be connected to more than one 

supply circuit.

 CAUtiON:

the coil must be level to ensure proper 

condensate drainage. An unlevel installation 

may result in structural damage, premature 

equipment failure, or possible personal injury.

1. Disconnect all electrical power to the furnace or air handler.

2. Remove system refrigerant per industry standard practices.

3. Disconnect and remove existing evaporator coil.

System Depressurization

1. Remove the cap (Figure 1) from the end of the liquid line.

2. Verify  pressurization  by  depressing  the  Schrader  valve 

on the end of the liquid line. Listen for any escaping gas. 

If there is no pressure, test the coil for leakage.

•  If leakage is found, clearly mark the location of the leak 

and return the coil to the distributor for processing.

impOrtANt SAFety iNFOrmAtiON

Please read all instructions before servicing this equipment. 

Pay attention to all safety warnings and any other special 

notes highlighted in the manual. Safety markings are used 
frequently throughout this manual to designate a degree or 
level of seriousness and should not be ignored. 

WArNiNG

 

indicates a potentially hazardous situation that if not avoided, 

could result in personal injury or death. 

CAUtiON

 indicates a 

potentially hazardous situation that if not avoided, may result 

in minor or moderate injury or property damage.

 WArNiNG:

this coil must be installed in accordance 

with the instructions outlined in this manual 

during the installation, service, and operation 

of this unit. Unqualified individuals should 

not attempt to interpret these instructions or 

install this equipment. if you do not posses 

mechanical skills or tools, call your local dealer 

for assistance. Under no circumstances should 

the equipment owner attempt to install and/or 

service this equipment. Failure to follow safety 

recommendations could result in possible 

damage to the equipment, serious personal 

injury or death.

 WArNiNG:

prOpOSitiON 65 WArNiNG: this product 

contains chemicals known to the state of 

California to cause cancer, birth defects or other 

reproductive harm.

•  The installer must comply with all local codes and regulations 

which govern the installation of this type of equipment. 

Local codes and regulations take precedence over any 

recommendations contained in these instructions. Consult 

local building codes for special installation requirements.

•  Familiarize  yourself  with  the  controls  that  shut  off  the 

electrical power to the unit. If the unit needs to be shut down 

 WArNiNG:

this coil is pressurized with Nitrogen at the 

factory. Avoid direct face exposure or contact 

with valve when gas is escaping. Always ensure 

adequate ventilation is present during the 

depressurization process. Any uncertainties 

should be addressed before proceeding.

NITROGEN

HEALTH

FLAMMABILITY

REACTIVITY

0 Minimal Hazard

1 Slight Hazard

1

0

0

for an extended period of time, turn off electrical power 

at the circuit breaker. For your safety always turn off the 

electrical power before performing service or maintenance 

on the unit.

•  Installation of equipment may require brazing operations. 

Installer  must  comply  with  safety  codes  and  wear 

appropriate safety equipment (safety glasses, work gloves, 

fire extinguisher, etc.) when performing brazing operations.

•  Follow all precautions in the literature, on tags, and on 

labels provided with the equipment. Read and thoroughly 

understand the instructions provided with the equipment 

prior to performing the installation and operational checkout 

of the equipment.

•  Use caution when handling this equipment or removing 

components. Personal injury can occur from sharp metal 

edges present in all sheet metal constructed equipment.

Содержание 921337

Страница 1: ...his product and using common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or fa...

Страница 2: ...njuryordeath CAUTIONindicatesa potentially hazardous situation that if not avoided may result in minor or moderate injury or property damage WARNING This coil must be installed in accordance with the...

Страница 3: ...Tables 3 5 pages 6 8 CAUTION To prevent damage to the unit or internal components it is recommended that two wrenchesbeusedwhenlooseningortightening nuts Do not over tighten 1 Using two wrenches loos...

Страница 4: ...ult in structural damage premature equipment failure or possible personal injury 6 Braze the individual connections with dry nitrogen flowing through the joints IMPORTANT To prevent internal oxidation...

Страница 5: ...that a wet rag be wrapped around the suction line in front of the close off plate before applying heat Failure to keep components cool during brazing may result in structural damage premature equipmen...

Страница 6: ...4 920672A 921734 B5BM X37K B 919699D 919630D REPLCOIL03M 921484 920670A 921734 B5BM X42K B 904308D 919514D REPLCOIL03M 921484 920671A 921734 B5BM X48K B 919686D 919515D REPLCOIL03M 921484 920672A 9217...

Страница 7: ...REPLCOIL02M 921483 N A 921339 921733 C3DA 047U B 917270D REPLCOIL02M 921483 N A 921339 921733 C3DA 055U B 917271D REPLCOIL02M 921483 N A 921339 921733 C5DA T25U B 919221D REPLCOIL02M 921483 920662A 92...

Страница 8: ...QA X48U B 920694 REPLCOIL03M 921484 920672A 921337 921734 C5QA X37U B 920760 REPLCOIL03M 921484 920670A 921337 921734 C3BA 048U C 917419D REPLCOIL07M 921488 N A N A UC COIL KIT 060 B3 AH 917408D REPLC...

Отзывы: