37 |
Operation
On/Off or Modulating Control (J10)
The RH’s output can be controlled by either an On/Off humidistat or a modulating humidistat.
To set the RH to operate with a modulating humidistat remove Jumper J10. (Factory setting =
jumper Installed , On/Off operation)
J10 Removed
– Modulating operation, the controller monitors the demand signal on
terminal point 4 of the control terminal strip and adjusts humidifier output to match it.
J10 Installed
- The RH is configured for On/Off operation. The controller will ignore any
modulating signals even if they are connected.
Modulation Offset (J13)
The RH controller can be configured to work with a modulating humidistat with 4-20 mA or 2-10
VDC output. Modulation offset can be configured with jumper 13. (Factory setting = Jumper
Removed, 0-10 VDC or 0-20 mA control signal)
J13 Removed
– Controller is configured for a 0-10 VDC or 0-20 mA control signal.
J13 Installed
– Controller is configured for a 2-10 VDC or 4-20 mA control signal.
Note:
For mA control a 500
Ω
register is required between terminals 3 and 4 on the low voltage
control terminal.
Table 6: Control Jumper Configuration
Resulting Control
J10
J13
On/Off Installed
No
Affect
Modulating 0-10 VDC or 0-20 mA
Removed
Removed
Modulating 2-10 VDC or 4-20 mA
Removed
Installed
Ground Fault Interrupt (GFI) (J15)
Ground current leakage can occur when the humidifier performs drains. With jumper J15 the
RH can be configured to turn off the power to the electrodes whenever a drain takes place.
J15 Removed
– The power relay is on during drains to control cylinder water concentration.
J15 Installed
– The power relay is turned off during drains to control cylinder water
concentration.
Содержание RH
Страница 7: ...Introduction 4 ...
Страница 9: ...Installation 6 Typical RH Installation Figure 3 Typical Humidifier Installation ...
Страница 19: ...Installation 16 On Off Control Wiring Figure 16 On Off Controls Figure 17 Digital On Off Humidistat ...
Страница 20: ...17 Installation Modulating Control Wiring Figure 18 Modulating Controls ...
Страница 21: ...Installation 18 Figure 19 Modulating Control Wiring Figure 20 Duct Sensor Wiring ...
Страница 31: ...Start Up 28 ...
Страница 36: ...33 Operation Humidifier Schematic Figure 28 Humidifier Schematic ...
Страница 55: ...Spare Parts 52 Exploded View and Spare Parts List ...
Страница 56: ...53 Spare Parts RH Spare Parts Figure 37 RH Spare parts ...
Страница 58: ...55 Warranty ...