2

 

Remote Mounting of the Blower Pack with RH Series

  

 

7.

 

Remove the front cover from the humidifier.  

 

8.

 

Install the steam line as per the RH Series installation manual.  

Note:  Maximum recommended length of steam line is: 8 ft. for 5lbs/hr, 15 ft. for 10lbs/hr.   

 

9.

 

Put the power leads from the blower pack through knock out at the bottom right of the unit.  

 

10.

 

Connect the power leads for the blower pack to the terminal 19 and 20 on the RH Series’ 

control terminal strip. 

Note: Improper wiring could damage the blower pack or the RH Series PCB.  

 

11.

 

Replace the front cover on the humidifier.  

 

12.

 

Once the power is restored, the RH Series humidifier is ready for use.  

 

Remote Mounting of the Blower Pack with the ResDelux 

The Blower Pack can be combined with the previous residential humidifier model, the ResDelux.  

The Blower Pack Kit contains a supplementary set of cables to link the Blower Pack to the 

humidifier.  To properly mate the new Blower Pack with the ResDelux humidifier, follow these 

steps: 

 

1.

 

Open up Blower Pack. 

2.

 

Replace with supplementary wire harness provided. 

3.

 

Hookup is described in ResDelux manual. 

4.

 

Run new wire harness in same location as previous wire. 

5.

 

Close Blower Pack. 

 

Note: If more length between humidifier and Blower Pack is required, extend the harness by 

adding additional wire (by others).  Suitable wire is 18 AWG. 

 

Содержание RH Series

Страница 1: ...n Manual Includes installation for the Nortec Blower Pack with the RH Series Humidifier This Installation Manual is intended to be used in conjunction with the RH Series Installation Manual 2553198 C 09 MAR 2011 Important Read and save these instructions This guide to be left with equipment ...

Страница 2: ...itten authorization of Nortec Humidity Ltd except to the extent required for installation or maintenance of recipient s equipment Liability Notice Nortec does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts components equipment that are not authorized or approved by Nortec Copyright Notice Copyright 2012 Nortec Humidity Ltd Al...

Страница 3: ...uate clearances for the top side and front Table 1 Clearances of Remote Mounted Blower Pack with RH Series 100 Capacity Operating Voltage Minimum Ceiling Clearance inches cm Minimum Side Clearance inches cm Minimum Frontal Clearance inches cm 110 120V 8 5 50 208V 55 15 73 220 240V 62 16 74 Nominal conditions 70 F 40 RH Figure 1 Blower Pack for RH Series Clearances Mounting 5 The blower pack has tw...

Страница 4: ... the humidifier 12 Once the power is restored the RH Series humidifier is ready for use Remote Mounting of the Blower Pack with the ResDelux The Blower Pack can be combined with the previous residential humidifier model the ResDelux The Blower Pack Kit contains a supplementary set of cables to link the Blower Pack to the humidifier To properly mate the new Blower Pack with the ResDelux humidifier ...

Страница 5: ...emote Mounting of the Blower Pack with RH Series 3 Part Number Description 1581312 Blower Fan Assembly 2548008 Power Supply 2548211 Wire Harness BP built in Figure 2 Spare Parts Blower Pack for RH Series ...

Страница 6: ...U S A 826 Proctor Avenue Ogdensburg NY 13669 CANADA 2740 Fenton Road Ottawa Ontario K1T 3T7 TEL 1 866 NORTEC1 FAX 613 822 7964 EMAIL nortec humidity com ...

Отзывы: