Remote Mounting of the Blower Pack with RH Series 

1

Remote Mounting of the Blower Pack with RH Series 

1.

 

This installation guide is intended to be used in conjunction with the RH Series installation 
manual.  
 

2.

 

The remote mounted blower should be located at least 7’ off the floor to prevent the discharged 
steam from coming in contact with pedestrian traffic or any obstructions. 
 

3.

 

When installing the remote blower pack, ensure the primary voltage to the RH Series has been 
switched off at the electrical panel, or that it is unplugged.  

 
4.

 

Find a suitable location for mounting the remote blower pack. The surface should be flat with 
adequate clearances for the top, side, and front: 

 

Table 1: Clearances of Remote Mounted Blower Pack with RH Series @ 100% Capacity 

Operating Voltage 

Minimum Ceiling  

Clearance 

inches (cm) 

Minimum Side 

Clearance 

inches (cm) 

Minimum Frontal  

Clearance 

inches (cm) 

110-120V 

8" 

5" 

50" 

208V 

55" 

15" 

73" 

220-240V 

62" 

16" 

74" 

*Nominal conditions 70°F, 40% RH 

 
 
 

 

 

          

 

 

Figure 1:  Blower Pack for RH Series – Clearances & Mounting

 

 

5.

 

The blower pack has two teardrop (or keyhole) openings on the back of the cabinet for 

mounting purposes. They are located 8 ¼” apart, and 1” from the top of the blower pack 

cabinet.  

 

6.

 

Measure the screw locations and use two #8 screws, 2” long. The screws should be 

anchored in a standard 2” x 4” wood stud or equivalent to ensure adequate support of the 

blower pack and connecting steam hose.  

 

1” 

(25.4mm) 

1.5” 

(38.1mm) 

8.22” 

(208.8mm) 

Wall Mounting 

Holes 

Frontal 

0” 

Ceiling 

Side 

Содержание RH Series

Страница 1: ...n Manual Includes installation for the Nortec Blower Pack with the RH Series Humidifier This Installation Manual is intended to be used in conjunction with the RH Series Installation Manual 2553198 C 09 MAR 2011 Important Read and save these instructions This guide to be left with equipment ...

Страница 2: ...itten authorization of Nortec Humidity Ltd except to the extent required for installation or maintenance of recipient s equipment Liability Notice Nortec does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts components equipment that are not authorized or approved by Nortec Copyright Notice Copyright 2012 Nortec Humidity Ltd Al...

Страница 3: ...uate clearances for the top side and front Table 1 Clearances of Remote Mounted Blower Pack with RH Series 100 Capacity Operating Voltage Minimum Ceiling Clearance inches cm Minimum Side Clearance inches cm Minimum Frontal Clearance inches cm 110 120V 8 5 50 208V 55 15 73 220 240V 62 16 74 Nominal conditions 70 F 40 RH Figure 1 Blower Pack for RH Series Clearances Mounting 5 The blower pack has tw...

Страница 4: ... the humidifier 12 Once the power is restored the RH Series humidifier is ready for use Remote Mounting of the Blower Pack with the ResDelux The Blower Pack can be combined with the previous residential humidifier model the ResDelux The Blower Pack Kit contains a supplementary set of cables to link the Blower Pack to the humidifier To properly mate the new Blower Pack with the ResDelux humidifier ...

Страница 5: ...emote Mounting of the Blower Pack with RH Series 3 Part Number Description 1581312 Blower Fan Assembly 2548008 Power Supply 2548211 Wire Harness BP built in Figure 2 Spare Parts Blower Pack for RH Series ...

Страница 6: ...U S A 826 Proctor Avenue Ogdensburg NY 13669 CANADA 2740 Fenton Road Ottawa Ontario K1T 3T7 TEL 1 866 NORTEC1 FAX 613 822 7964 EMAIL nortec humidity com ...

Отзывы: