![Nortec NH-EL Series Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/nortec/nh-el-series/nh-el-series_installation-and-operation-manual_1705811036.webp)
33 |
Installation
Steam
Unit ON
Error
Service
NO
COM
NO
COM
NC
NO
COM
NC
NO
COM
Remote Fault Option Wiring
The NH-EL remote fault option includes 4 relays that can provide remote status indication. The
relays are mounted to a remote fault board which is located as shown in Figure 31: Remote
Fault Wiring. The PCB with the relays includes markings which indicate the function of each
terminal on the board. The relays indicate the following status:
1
Unit On
– The normally open relay is closed when the humidifier has power and the On/Off
switch is set to on.
2
Steam
– The normally open relay is closed when the control board detects that the cylinder
is drawing current and steam is being produced.
3
Service
– The relay can be wired to open (NC) or close (NO) when a warning is displayed on
the humidifier display and the yellow service LED is illuminated.
4
Error
– The relay can be wired to open (NC) or close (NO) when a fault is detected by the
humidifier controls.
Figure 31: Remote Fault Wiring
Содержание NH-EL Series
Страница 33: ...Installation 30 Double Unit Control Wiring Continued Figure 26 Double Unit Parallel or Sequence Wiring ...
Страница 87: ...Spare Parts 84 NH EL Plumbing Parts Figure 54 NH EL Plumbing Parts ...
Страница 89: ...Spare Parts 86 NH EL Plumbing Parts Figure 55 NH EL Plumbing Parts ...
Страница 91: ...Spare Parts 88 NH EL Electrical Parts Figure 56 NH EL Electrical Parts ...
Страница 93: ...Spare Parts 90 NH EL Electrical Parts Figure 57 NH EL Electrical Parts ...
Страница 95: ...Spare Parts 92 Blower Pack Parts Figure 1 Blower Pack Parts Figure 58 Blower Pack Parts ...
Страница 97: ...Spare Parts 94 This Page Intentionally Left Blank ...