Page 3
2008-02-15
B.
MOUNTING THE LINKS 2 ASSEMBLY
(1)
Refer to Figure 2 for the mounting location of the Nortec LINKS 2 Bracket on the
GS or SE unit. If pilot holes for the mounting screws are not already present on the
humidifier frame follow steps 2 and 3. If pilot holes are present then disregard
steps 2 and 3.
(2)
Using the bracket assembly as a template, mark locations of pilot holes on the
GS/SE humidifier frame.
(3)
Using 1/8” drill bit, drill pilot holes for the bracket mounting screws.
(4)
Install the bracket assembly using 8-32x ½” hex-drive screws. Be sure to route the
power wires for the I/O Controller-E module through the cutout on the upper right-
hand corner of the bracket, as illustrated in the following figure. After running wires
behind bracket, route the power leads into the main wire track.
Figure 2. LINKS 2 Bracket Placement
Screw
Location