(1) FIELD CONVERSION OF A NHTC SERIES HUMIDIFIER WITH NORTEC
LINKS 2
BACNET, LONWORKS AND N2 MODULES:
Figure 1. Component Identification
A. MOUNT THE LINKS 2 ASSEMBLY
(1) The Nortec LINKS 2 assembly mounts on the top, right corner of the electrical
compartment.
(2) Ensure that the rear, upwards facing hook engages the proper cooling louver at the
back of the humidifier cabinet.
(a)
Fasten the bracket assembly to the humidifier ‘top’ using the 3 8-32 X ½” self-
tapping screws provided with the kit.
LAN Router
or Switch
(BACnet/IP)
OnLine
Module
LINKS 2
Module
Router Power
Supply