4

WARNING

IMPROPER ORIENTATION OF THE HEATER 

COULD AFFECT THE SAFE AND RELIABLE 

OPERATION OF THE HEATER.

7.0  THERMOSTAT INSTALLATION

7.1 

FACTORY  INSTALLED  -  For  shipping 

purposes the thermostat well (located at back 

of unit) has not been installed.
Position thermostat bulb perpendicular to 

housing being careful not to kink the capillary. 

Slide well over bulb and screw into place. Make 

sure that a minimum 5 threads engagement is 

achieved.

7.2 

FIELD  INSTALLED  KIT  -  Most  Norseman

TM

 

XB units are suitable for field installation of a 

thermostat kit with the operator shaft hole on the 

front side of the unit and plugged with a socket 

head cap screw. If a thermostat is to be field 

installed, check to verify that you have been 

supplied with the correct thermostat kit. Single 

phase heaters use a single pole thermostat 

as supplied in kit number XTKW04481. Three 

phase heaters use a double pole thermostat 

as supplied in kit number XTKW04483. Follow 

the instructions supplied with the kit.

8.0  WIRING

8.1  Whenever hazardous materials are present, 

ensure that the terminal housing covers are 

secure before powering the heater.

8.2 

Use supply wires suitable for 221°F (105°C).

8.3  Use approved conduit and conduit seals as 

required by the code for hazardous locations.

8.4  To provide maximum protection each 

Norseman

TM

 XB heater should be fused 

individually using the nearest standard fuse 

size which is not less than 120% of the 

expected line current.

8.5  All heaters come factory prewired and ready 

for direct connection to the power supply 

leads.
(a) Connect the power leads to terminals 

marked L1 and L2 for single phase and L1, 

L2 & L3 for three phase heaters as shown in 

Figure 9.

(b) Connect the ground wire to the ground 

connection located in the heater terminal 

housing.

FIGURE 9 - WIRING DIAGRAM

TABLE 3 - 

REPLACEMENT THERMOSTATS

Part No.

Wiring Diagram (Figure 9)

XB1-1005T6

Fig. 1

-

XB1-1010T4A
XB1-1017T4A
XB1-1030T3B

XB1-1047T2D
XB1-3047T3B
XB1-3075T2D
XB1-4100T2D

XB1-6020T6

XB1-6045T4A

XB1-6125T2D
XB1-6135T2D
XB2-1075T2D

Fig. 2

Fig. 5

XB2-3150T2D
XB2-4100T3B
XB2-4200T2D

XB2-6040T6

XB2-6085T4A
XB2-6150T3B

XB2-6250T2D

XB3-1100T2D

Fig. 3

 

(Except  

XB3-4150T3B 600V 

& XB3-6125T4A 600V 

use Fig. 8)

Fig. 6 

 

(Except  

XB3-4150T3B 600V 

& XB3-6125T4A 

600V use Fig. 9)

XB3-1125T2D
XB3-3100T3B

XB3-3200T2D
XB3-4150T3B
XB3-4300T2D

XB3-6060T6

XB3-6125T4A
XB3-6225T3B

XB3-6375T2D

XB4-1150T2D

Fig. 4 (Except XB4-

6160T4A 600V & 

XB3-3250T2D 600V 

use Fig. 10)

Fig. 7

XB4-3250T2D
XB4-4225T3B
XB4-4375T2D

XB4-6080T6

XB4-6160T4A
XB4-6300T3B

XB4-6450T2D
XB4-6500T2D

Содержание XB1

Страница 1: ...codes WARNING DO NOT CONNECT THE HEATER TO AN ELECTRICAL SUPPLY VOLTAGE OTHER THAN THAT SHOWN ON THE PRODUCT NAMEPLATE 3 0 INSTALLATION GENERAL REQUIREMENTS 3 1 NorsemanTM XB heaters are approved for wall or floor mounting with the terminal housing at the bottom Ensure that is the wall sufficiently strong to support the heater which depending on the model could weigh up to 100 lbs 45 kg Otherwise ...

Страница 2: ...nstall baffles CAUTION THE HEATERS SURFACE IS HOT WHEN THE HEATER IS ENERGIZED KEEP ALL COMBUSTIBLES AWAY FROM THE HEATER AND MAINTAIN THE RECOMMENDED INSTALLATIONCLEARANCESATALLTIMES FIGURE 2 DIMENSIONS MOUNTING DETAILS Table 2 HEATER DIMENSIONS Unit B F G M N L in mm in mm in mm in mm in mm in mm XB1 7 250 184 10 250 260 9 625 244 5 125 130 XB1 17 000 432 16 375 416 11 875 300 XB1 23 625 600 23 ...

Страница 3: ...kets with supplied 1 4 20 hex bolts and lock washers Figure 5 FIGURE 5 ATTACH HEATER TO MOUNTING BRACKETS 6 0 FLOOR MOUNTING Step 1 Position heater face down on the floor with terminal box towards the wall Figure 6 FIGURE 6 FLOOR MOUNTING DIAGRAM Step 2 Fasten top stabilizing bracket s and floor mounting bracket s to the unit Floor mounting brackets may be mounted in one of three orientations Figu...

Страница 4: ...C 8 3 Use approved conduit and conduit seals as required by the code for hazardous locations 8 4 To provide maximum protection each NorsemanTM XB heater should be fused individually using the nearest standard fuse size which is not less than 120 of the expected line current 8 5 All heaters come factory prewired and ready for direct connection to the power supply leads a Connect the power leads to ...

Страница 5: ...TER DO NOT EXCEED THE MAXIMUM ALLOWABLE AMBIENT OPERATING TEMPERATURE OF 104 F 40 C 10 0 MAINTENANCE 10 1 Periodically inspect the heater installation to ensure that all connections fittings plugs screws covers etc are tight and free of corrosion 10 2 Check that the reflector baffles if required have not moved upwards or downwards in relation to the heat sink 10 3 Check the extrusions of the heate...

Страница 6: ...6 NOTES ...

Страница 7: ...7 NOTES ...

Страница 8: ... of parts No warranty applies to paint finishes except for manufacturing defects apparent within 30 days from the date of installation The Company neither assumes nor authorizes any person to assume for it any other obligation or liability in connection with the product s The Purchaser agrees that all warranty work required after the initial commissioning of the product will be provided only if th...

Отзывы: