1.0  SPECIAL NOTICES

1.1  The following special notices highlight 

important information in the installation and 

maintenance sections. Each serves a special 

purpose and is displayed in the format shown:
This symbol indicates a potentially hazardous 

situation, which, if not avoided, can result in 

personal injury or damage to the equipment.
This symbol indicates a potentially hazardous 

situation, which, if not avoided, may be a  

shock hazard.
This symbol indicates an imminently hazardous 

situation, which, if not avoided, could result in 

death or serious injury.

2.0  PRE-INSTALLATION

2.1  Initially, inspect the heater for possible 

damage due to shipping and handling. Claims 

for shipping damages shall be placed with the 

carrier.

2.2  Check the heater nameplate to ensure that 

the heater area classification and temperature 

code are suitable for the hazardous area 

classification.  For  details  of  hazardous 

locations with potential for explosion, refer 

to the Canadian Electrical Code or National  

Electrical Code.

2.3  Check to ensure that the heater voltage is the 

same as the supply voltage.

2.4 

The  heater  must  be  installed  by  qualified 

personnel in strict compliance with national 

and local electrical codes.

WARNING

DO NOT CONNECT THE HEATER TO AN 

ELECTRICAL SUPPLY VOLTAGE OTHER 

THAN THAT SHOWN ON THE PRODUCT 

NAMEPLATE.

3.0  INSTALLATION - GENERAL REQUIREMENTS

3.1  Norseman

TM

 XB heaters are approved for wall 

or floor mounting with the terminal housing at 

the bottom. Ensure that is the wall sufficiently 

strong to support the heater which, depending 

on the model, could weigh up to 100 lbs (45 

kg). Otherwise use the brackets supplied to 

stand the heater on the floor.

3.2  Do not recess the Norseman

TM

 XB heater 

into the wall. Use of the brackets supplied will 

ensure that the minimum spacing from the 

wall of 3.75” (95 mm) is maintained.

3.3  If more than one heater is being installed, 

maintain at least 3” (76 mm) between adjacent 

heater extrusions. NEVER INSTALL ONE 

HEATER ABOVE THE OTHER.

3.4  The Norseman

TM

 XB heater relies on natural 

convection and “black heat” radiation to transfer 

heat to the surroundings. Try to maintain a 12” 

(300 mm) clearance and NEVER LESS THAN 

6” (150 mm) clearance in front of and at the 

sides of the heater.

3.5  Use guard rails in front of the heater if there 

is a possibility that moving equipment could 

come in contact with the heater.

TYPE XB EXPLOSION-PROOF

 

CONVECTION PANEL HEATER

INSTALLATION, OPERATION & 

MAINTENANCE INSTRUCTIONS

E-mail: [email protected] 

www.ccithermal.com

Date of Issue: October 2014 

10457.Rev.2.03

Printed In Canada

C         US

®

CAUTION

CAUTION

WARNING

ISO 9001

Содержание XB1

Страница 1: ...codes WARNING DO NOT CONNECT THE HEATER TO AN ELECTRICAL SUPPLY VOLTAGE OTHER THAN THAT SHOWN ON THE PRODUCT NAMEPLATE 3 0 INSTALLATION GENERAL REQUIREMENTS 3 1 NorsemanTM XB heaters are approved for wall or floor mounting with the terminal housing at the bottom Ensure that is the wall sufficiently strong to support the heater which depending on the model could weigh up to 100 lbs 45 kg Otherwise ...

Страница 2: ...nstall baffles CAUTION THE HEATERS SURFACE IS HOT WHEN THE HEATER IS ENERGIZED KEEP ALL COMBUSTIBLES AWAY FROM THE HEATER AND MAINTAIN THE RECOMMENDED INSTALLATIONCLEARANCESATALLTIMES FIGURE 2 DIMENSIONS MOUNTING DETAILS Table 2 HEATER DIMENSIONS Unit B F G M N L in mm in mm in mm in mm in mm in mm XB1 7 250 184 10 250 260 9 625 244 5 125 130 XB1 17 000 432 16 375 416 11 875 300 XB1 23 625 600 23 ...

Страница 3: ...kets with supplied 1 4 20 hex bolts and lock washers Figure 5 FIGURE 5 ATTACH HEATER TO MOUNTING BRACKETS 6 0 FLOOR MOUNTING Step 1 Position heater face down on the floor with terminal box towards the wall Figure 6 FIGURE 6 FLOOR MOUNTING DIAGRAM Step 2 Fasten top stabilizing bracket s and floor mounting bracket s to the unit Floor mounting brackets may be mounted in one of three orientations Figu...

Страница 4: ...C 8 3 Use approved conduit and conduit seals as required by the code for hazardous locations 8 4 To provide maximum protection each NorsemanTM XB heater should be fused individually using the nearest standard fuse size which is not less than 120 of the expected line current 8 5 All heaters come factory prewired and ready for direct connection to the power supply leads a Connect the power leads to ...

Страница 5: ...TER DO NOT EXCEED THE MAXIMUM ALLOWABLE AMBIENT OPERATING TEMPERATURE OF 104 F 40 C 10 0 MAINTENANCE 10 1 Periodically inspect the heater installation to ensure that all connections fittings plugs screws covers etc are tight and free of corrosion 10 2 Check that the reflector baffles if required have not moved upwards or downwards in relation to the heat sink 10 3 Check the extrusions of the heate...

Страница 6: ...6 NOTES ...

Страница 7: ...7 NOTES ...

Страница 8: ... of parts No warranty applies to paint finishes except for manufacturing defects apparent within 30 days from the date of installation The Company neither assumes nor authorizes any person to assume for it any other obligation or liability in connection with the product s The Purchaser agrees that all warranty work required after the initial commissioning of the product will be provided only if th...

Отзывы: