System controller
External operation switch Terminal
External operation switch
Connect to terminals
External
operation
switch
Pressure
switch
Remote
controller
● Connect the external operation switch when you want to turn ON/OFF the water heater from external
in addition to the Power ON/OFF Button of the remote controller.
- If the terminal of the external operation switch is switched from open to short, the Power ON/OFF
Button of the water heater is turned "ON".
- If the terminal of the external operation switch is switched from short to open, the Power ON/OFF
Button is turned "OFF".
15VDC, 2.7mA
Thermostat Terminal
Thermostat of
the hot water storage tank
Connect to terminals
Thermostat
Remote
controller
15VDC, 2.7mA
External
operation switch
Thermostat
● Use the normally open relay with the contact for low voltage.
● For the external operation switch
- Whether the Power ON/OFF Button is synchronized or not to the cycle operation can be changed by
switching the setting.
(it can be changed only for recirculation system).
If the external switch is switched from open to short, the setting is switched as shown below.
Power ON/OFF Button is synchronized: Power ON/OFF Button is turned "ON",
cycle operation is turned "ON"
Power ON/OFF Button is not synchronized: only Power ON/OFF Button is turned "ON"
● Connect the thermostat of the hot water storage tank.
- If the temperature of the hot water storage tank exceeds the temperature set with the thermostat,
the contact in the thermostat is opened and the circulation pump stops.
- A platinum resistance temperature detector cannot be connected directly.
● This terminal is short-circuited when the product is shipped from factory.
When you use this feature, disconnect a short-circuit connector as shown below.
● This terminal is short-circuited when the
product is shipped from factory.
When you use this feature, disconnect a
short-circuit connector as shown below.
Disconnect this connector
when external operation switch is connected.
Disconnect this connector
when thermostat is connected.
─31─