Remote controller cord

• For extensions, a 26' (8m) cord can be purchased (Part # RC-CORD26) or use 18AWG wire.
• Install according to the National Electrical Code and all applicable local codes.

Connecting Remote Controller Cord to Unit

•  Keep the remote controller cord away from the freeze prevention heaters in the unit.
•  Tie the redundant cord outside the water heater. Do not put the extra length inside the equipment.
•  The remote controller cord can be extended up to 300' (90m) with 18AWG wire.
•  Use a Y type terminal with a resin sleeve. (Without the sleeve, the copper wire may corrode and 

cause problems).

•  Be sure to hand tighten when screwing to the terminal block. Power tools may cause damage to 

the terminal block.

1. Check to make sure that the remote controller 

cord has plenty of slack in order to reach the ex-
ternal connection terminal block.

2. Disconnect electrical power to the water heater.
3. Remove the single screw securing the terminal 

block cover and then remove the cover.

4. Pass the remote controller cord through the wiring 

throughway and connect the Y terminals at the end 
of the remote controller cord to the terminal block.

5. Replace the terminal block cover and install the 

screw previously removed in step 3.

6. Reconnect electrical power to the water heater.

External connection 
terminal block

Wiring throughway

 Remote controller cord

     Changing Other Features

  Adjusting the Temperature Display

  Note: The setting must be done within the  rst 10 minutes of connecting electrical power to the water heater.

Table of Setting Items

Item No. 

                       Item                                         Choices (factory defaults shaded)                    

12

Celsius/Fahrenheit 
display mode.

°F (Fahrenheit) 

°C (Celsius)

Display

Power On/Off Button

Flow Meter Alarm Set buttton

Setting Button

      Setting Procedure

1. Turn the water heater off by pressing the Power On/Off Button on the remote controller.
2. Disconnect, then reconnect electrical power to the water heater.
3. Press the Flow Meter Alarm Set Button and hold it in for 2 seconds or more.
4. Press the Flow Meter Alarm Set Button until the remote controller displays item number "12".
5. Press Setting Button "   " for 5 seconds or more to change the display units to °F.
6. Press Setting Button "    " for 5 seconds or more to change the display units to °C.
7. To con rm the setting, turn the water heater on by pressing the Power On/Off Button on the 

remote controller.

     

 

Remote Controller

Содержание NRC83-DV

Страница 1: ...d by erroneous work or work not as instructed in this manual are not covered by the warranty Check that the installation was done properly in accordance with this Installation Manual upon completion A...

Страница 2: ...lation Q ty Shape Part Part Shape Q ty Remote Controller Cord 26ft 8m Quick Connect Cord QC 2 1 1 1 each Isolation Valves includes pressure relief valve Owner s Guide Warranty Installation Manual this...

Страница 3: ...e The hot water temperature will become unstable as the pipe length increases Distance at center 20 3 36 3 in 515 922mm Quick Connect Cord Union Gas Valve Union Shutoff Valve Shutoff Valve Hot Water S...

Страница 4: ...Caution if Using With a Solar Pre Heater Using this unit with a solar pre heater can lead to unpredictable output temperatures and possibly scalding If absolutely necessary use mixing valves to ensure...

Страница 5: ...result Avoid installation in places where special chemical agents e g hair spray or spray detergent are used Ignition failures and malfunction may occur as a result Carbon Monoxide Poisoning Hazard D...

Страница 6: ...nal noises while it is running Before installing make sure that the exhaust ue termination will have the proper clearances according to the National Fuel Gas Code ANSI Z223 1 State of California The w...

Страница 7: ...the unit to facilitate maintenance and service if necessary If possible leave 3 75mm or more above and below the vent pipe to facilitate inspection and repair if necessary Securing of space for repai...

Страница 8: ...Illustration Outdoor Clearances to Opening into Any Building 12 300mm or more 12 300mm or more There must be no building opening within this area Flue terminal 12 300mm or more 12 300mm or more Vent C...

Страница 9: ...aintain clearances in accordance with local installation codes and the requirements of the gas supplier A vent shall not terminate directly above a sidewalk or paved driveway that is located between t...

Страница 10: ...installing Internal parts may be damaged and may become highly dangerous Install the unit on a vertical wall and ensure that it is level Locating Screw Holes Mounting Structure When installing with ba...

Страница 11: ...t accessory on the top of the appliance as illustrated below Or if the vent pipe has already been installed 2 After installing the drain pipe make sure that the area around the appliance is well venti...

Страница 12: ...temperature in excess of 149 F 65 C and schedule 40 PVC pipe may be used as the vent material If required by local code schedule 40 or 80 CPVC may also be used on this appliance Refer to page 13 for a...

Страница 13: ...for the location of the dip switch bank 0 3 6 9 12 15 18 21 24 27 30 32 35 38 41 44 47 50 53 56 62 0 00 0 90 1 80 2 70 3 60 4 50 5 40 6 30 7 20 8 10 9 00 9 90 10 80 11 70 12 60 13 50 14 40 15 30 16 20...

Страница 14: ...practices must be observed o Squarely cut all pieces of pipe o Remove all burs and debris from joints and fittings o All joints must be properly cleaned primed and cemented Use only cement and primer...

Страница 15: ...National Fuel Gas Code ANSI Z223 1 NFPA 54 Slope the horizontal vent 1 4 upwards for every 12 300mm toward the termination Use a condensation drain if necessary In the Commonwealth of Massachusetts a...

Страница 16: ...s fuel equipment Please refer to Technical Bulletin TB 010606 for full installation in structions Slope vent Upwards 4 100mm pipe requires the use of a reducing coupling just prior to the termination...

Страница 17: ...must be supplied from the outdoors as shown on pages 15 16 Terminate at least 6 1 8m from the combustion air intake of any appliance and 3 0 9m from any other building opening gas utility meter servi...

Страница 18: ...a mechanical closet provide a 600mm 24 clearance in front of the unit to the door If combustion air will be provided through a duct size the duct to provide 60 cubic feet of fresh air per minute Supp...

Страница 19: ...ee next page for the pipe capacity charts Noritz Condensing Tankless Gas Water Heater NRC98 DV 180 000 Btuh NRC83 DV 157 000 Btuh Clothes Dryer 35 000 Btuh Barbecue 50 000 Btuh Gas Range Stove 65 000...

Страница 20: ...32 252 511 787 1496 55 112 213 440 675 1260 Maximum Capacity of Flex TracPipe in Cubic Feet per Hour of Natural Gas 0 60 Specific Gravity 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1...

Страница 21: ...to supply potable water may not be connected to any heating system or components previ ously used with a nonpotable water heating appliance When water is required in one part of the system at a higher...

Страница 22: ...eans to en sure that the supply water pressure to the inlet of the heater does not fall below 29 PSI when the maximum amount of water is being demand ed Also install a pressure meter on the inlet If t...

Страница 23: ...een ON and OFF oF PRIORITY LED goes out on PRIORITY LED blinks 6 If 2D also needs to be changed repeat steps 4 and 5 7 To con rm the settings press the Setting Buttons and simultaneously for more than...

Страница 24: ...Treatment Required Install Noritz Isolation Valves to allow for flushing Flushing is required if a water treatment device is not installed Suggested Suggested Install Noritz Isolation Valves to allow...

Страница 25: ...Long runs or applications where the nearest drain is above the water heater will require the use of a condensate pump Size the pump to allow for a maximum condensate discharge of 2 GPH from the water...

Страница 26: ...CLEARANCE DO NOT ADD ANY VALVES DO NOT ADD ANY VALVES NORITZ Condensing Tankless Gas Water Heater NORITZ Condensing Tankless Gas Water Heater Note If the drain line becomes clogged or frozen condensa...

Страница 27: ...the pump Set the Aquastat to 10 F 5 C below the set output temperature 4 Noritz recommends the use of an Isolation Kit with the installation These kits include an integrated shut off and serv ice valv...

Страница 28: ...the water heater will not activate resulting in possible freezing damage Do not let the power cord contact the gas piping Tie the redundant power cord out side the water heater Putting the redundant...

Страница 29: ...FF button on the remote controller To keep the water heater off let the unit sit for 30 sec to return to the original display The NRC98 DV NRC83 DV can be programmed so that it will default to one of...

Страница 30: ...t the end of the remote controller cord to the terminal block 5 Replace the terminal block cover and install the screw previously removed in step 3 6 Reconnect electrical power to the water heater Ext...

Страница 31: ...om a wall circuit to the pump 5 Replace the front cover Pump Wiring This feature is not available when using the Quick Connect Multi System feature Relay connection with larger pumps 85 W 1 Locate and...

Страница 32: ...ling Cord Clamp Ground wire Connector Connector Connecting Quick Connect Cord 2 Caution For Quick Connect Multi System Installation use part QC 2 only sold separately Quick Connect Cord 2 Quick Connec...

Страница 33: ...proper blue color and consistency If the ame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a quali ed service technician Do not ob...

Страница 34: ...ower to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop a...

Страница 35: ...00mm 2 8 70mm 1 4 36mm 6 7 170mm 5 5 140mm 3 9 100mm 2 8 70mm 1 4 36mm 1 6 40mm 2 4 61mm 5 5 140mm 9 4 240mm 1 1 28mm 26 2 665mm 23 1 586mm 0 4 10mm 4 0 5 13mm 6 0 24 x 0 4 6mm x 10mm OBLONG HOLE 0 4...

Страница 36: ...on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the con troller Avoid location...

Страница 37: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Отзывы: