42
Vent Clearances When Heater is In-
stalled Indoors
• 1.2m(4') below, 1.2m(4') horizontally
from, or 0.3m(1') above any door, oper-
able window, or gravity air inlet into any
building.
0.9m(3') above any forced air inlet within
3m(10').
Maintain the following clearances to any
opening in any building:
Illustration
(Noritz vent cap)
• 0.3m(1') below, 0.3m(1') horizontally from,
or 0.3m(1') above any door, operable
window, or gravity air inlet into any building.
0.9m(3') above any forced air inlet within
3m(10').
Vent Clearances When Heater is In-
stalled Outdoors With a Vent Cap
Clearance Requirements from Vent Terminations to Building Openings
* All clearance requirements are in accordance with ANSI Z21.10.3 and the National Fuel Gas Code,
ANSI Z223.1.
* For Installations in Canada, clearances are as follows: To windows, doors, & gravity air inlets:
914mm(36"). To forced air inlets: 1.8m(6'). These clearance requirements hold true for all of the
above situations: Indoor, Outdoor w/vent cap, & Recess Box.
0.9m(3')
0.3m(1')
1.2m(4')
1.2m(4')
0.9m(3')
0.3m(1')
0.3m(1')
0.3m(1')
SAR8209-1̲035̲045̲E̲J.p65
06.1.12, 8:31 AM
Page 42
Adobe PageMaker 6.5J/PPC
Содержание N-084M-CA
Страница 65: ...65 SAR8209 1 062 067 E J p65 06 1 12 8 16 AM 65...
Страница 66: ...66 N084M 62 67 e p65 05 11 28 4 15 PM Page 66 Adobe PageMaker 6 5J PPC...
Страница 67: ...67 N084M 62 67 e p65 05 11 28 4 15 PM Page 67 Adobe PageMaker 6 5J PPC...
Страница 132: ...65 SAR8198 1 062 067 F E J p65 06 1 12 7 53 AM 65...
Страница 133: ...66 SAR8198 062 067 F E J p65 05 11 28 3 29 PM Page 66 Adobe PageMaker 6 5J PPC...
Страница 134: ...67 SAR8198 062 067 F E J p65 05 11 28 3 29 PM Page 67 Adobe PageMaker 6 5J PPC...